Bill BurrBy William (Bill) Burr

The Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the information you need. This series of articles provides a guide to help users find their way through this critical document. This is not intended to replace the notes in Appendix B or the explanations of individual requirements contained in the CEC Handbook** but will hopefully provide some help in navigating, while reading the code.

The 24th Edition of the CE-C, Part I, (C22.1-18)* is now available from CSA Group. This discussion of Section 78 — Marine Wharves, Docking Facilities, Fixed and Floating Piers, and Boathouses is based on the new edition.

Rule 84-000 notes that this is a supplementary or amendatory section of the code and applies only to the installation of power production sources interconnected with a supply authority system. Appendix B and the CEC Handbook have additional information and descriptions of these installations.

Rule 84-002 states that arrangements for interconnection must be in accordance with the requirements of the supply authority.

Rule 84-004 requires provision of protection against backfeed into a supply authority system fault on all interconnected electric power sources.

Rule 84-006 requires that electric power production sources be equipped with the means and equipment to establish and maintain a synchronous condition with the interconnected supply system and prevent any adverse effect.

Rule 84-008 requires that where there is a loss of voltage in one or more phases of the supply authority system, the interconnected electric power production source must be automatically disconnected and not be reconnected until normal voltage of the supply authority system is restored. An alternate procedure may be followed, if in accordance with the requirements of the supply authority. If approved by the supply authority, an inverter designed to also serve as a disconnection device that is suitable for interconnection with electric power production sources may be used.

Rule 84-010 requires that where energization of conductors and equipment is from both directions, overcurrent protection must be provided from each source of supply.

Rule 84-012 requires that the rating of overcurrent protection for a transformer that is energized from both directions is determined under Section 26, by considering first one side of the transformer and then the other side, as the primary.

Rule 84-014 requires that each interconnected electric power production source installation must have additional devices as necessary for system stability and equipment protection.

Rule 84-016 requires ground fault protection in accordance with Rule 14-102 to be provided.

Rule 84-018 requires that where an electric power production source loses voltage in one or more of its phases it must have provisions to automatically disconnect all phases from the interconnected system.

Rule 84-020 requires that all ungrounded conductors of any electric power production source of an interconnected system, be provided with a disconnecting means that simultaneously disconnects all circuits supplied by the electric power production source equipment.

Rule 84-022 requires that all ungrounded conductors of any electric power production source of an interconnected system, be provided with a disconnecting means that simultaneously disconnects all circuits supplied by the electric power production sources from the supply authority system. This provides the supply authority a single point of access to isolate one or more power production sources.

Rule 84-024 outlines the specifications that the disconnecting means must

• be capable of being energized from both sides
• plainly indicate whether it is in the open or closed position
• have contact operation verifiable by direct visible means if required by the supply authority (in accordance with 84-002, to provide added assurance to supply authority workers that the circuit is open before work is initiated)
• have provision for being locked in the open position
• conform to Sections 14, 28, and 36 if it includes an overcurrent device
• be capable of being opened at rated load
• be capable of being closed with safety to the operator with a fault on the system
• disconnect all ungrounded conductors of the circuit simultaneously
• bear a warning to the effect that inside parts can be energized when the disconnecting means is open
• be readily accessible, and
• where a main fusible disconnecting means is used, an isolating switch must be provided to allow the fuses to be dead during handling

Rule 84-026 requires that isolating means be provided to isolate equipment that is energized from both directions from all ungrounded conductors of each source of supply.

Rule 84-028 specifies that the grounding means at the service entrance may serve as the grounding means for the electric power production source in accordance with Sections 10 and 36. In the case of a dc power source connected through a solid-state inverter, the inverter must not be grounded unless the inverter ac power is separated from the supply authority system by means of an isolating transformer.

Rule 84-030 requires that a warning notice and a single-line, permanent, legible diagram of the interconnected system shall be installed in a conspicuous place at the supply authority disconnecting means of Rule 84-022 and at the supply authority meter location.

In the next instalment, we will be discussing Section 86 – Electrical Vehicle Charging Systems.

William (Bill) Burr is the former Chair of the Canadian Advisory Council on Electrical Safety (CACES), former Director of Electrical and Elevator Safety for the Province of BC, and former Director of Electrical and Gas Standards Development and former Director of Conformity Assessment at CSA Group. Bill can be reached at Burr and Associates Consulting; billburr@gmail.com

* The source for this series of articles is the Canadian Electrical Code, Part I, published by CSA.
**Note the CEC Handbook is also published by CSA.

 

Changing Scene

  • Prev
Is it possible for the Ideal Nationals competition to be even more exciting? That question will be ...
The Solar Energy Society of Alberta and Energy Efficiency Alberta, in partnership with the ...
Nat will develop and execute on key sales strategies along with leading his team to drive strong ...
John MacDonald (better known as Satch) has decided that he will retire from Ideal Supply at the end ...
Aspiring skilled trades participants recently descended upon annual Skills Competitions held in ...
Join WiRE and partners 20/20 Catalysts Program and the Aboriginal Apprenticeship Board of Ontario ...
A new program launched by Nova Scotia with federal government support will provide rebates of up to ...
The National Electrical Contractor Association announced on June 18 that Southwire has been ...
Located 160 kilometres west of the Porcupine mine in Chapleau, Ontario, Borden is set to be ...
  Schneider Electric, the leader in the digital transformation of energy management and ...

Electrician Forum Brought to you by Schneider Electric

Schneider Electric

June 25, 2018

Sponsored by Schneider Electric

Today we are all concerned with the energy we consume within our homes. But how many truly understand the ins and outs of home energy use, and where exactly does the electrician and the development of energy management systems come into play. There is much to consider when discussing home energy use. The consumer first off needs to be informed about energy use, how it is calculated and ultimately billed if they are to make changes to their energy consumption rates. But in terms of educating consumers does the residential electrician have a role? And beyond that are manufacturers developing products designed to help electricians and consumers better understand residential energy use? Throughout this article we will deal with each of these important questions.

Read More

Codes and Regulations Brought to You by the CSA Group

  • Prev
In this article: Section 58 — Passenger Ropeways and Similar Equipment. Rule 58-000 ...
  Unauthorized CSA Group certification marks have been found on wiring by Triumph Cable ...
In this article: Section 52 — Diagnostic imaging installations. The CE code is a ...
In this article: Section 46 — Emergency Power Supply, Unit Equipment, Exit Signs, and ...
  In this article: Section 44 — Theatre Installations. The CE Code is a ...
CSA has published C22.2 No. 60947-7-3, the harmonized standard for low-voltage switchgear and ...
  Electric welders. The CE Code is a comprehensive document. Sometimes it can seem ...
  In this article: Section 40 — Electric cranes and hoists. The CE Code is a ...

 

Schneider

A new “future ready” circuit breaker from Schneider Electric is described by the company as the next generation of power distribution for the Internet of Things (IoT) era. Masterpact MTZ increases efficiency and can adapt to ever-evolving needs for safety, reliability and sustainability. The world is becoming more connected, electric, digitized, decarbonized, and decentralized, says Schneider Electric. Power distribution is facing new regulations, becoming more seamless and connected. 

Masterpact MTZ is the latest in a series of circuit breaker innovations, following Masterpact M, and then Masterpact NT/NW.

Read More



Tools for the Trade

  • Prev
  IDEAL Industries has introduced Combination Drill Taps to its tool lineup. Combining the ...
  Stripping and crimping device, 100 - 240 V input voltage, for insulated ferrules with a ...
Professional all-in-one cutter/stripper for coaxial and twisted pair cables     ...
  Klein Tools' Coax Explorrer 2 tests coaxial cable and maps up to 4 locations   ...
  Ideal Industries' T-14 wire stripper s are ideal for all professionals working within the ...
  The ATS850 conveyor eliminates all types of electro static discharge requirements. ...
  Lorik Tool & Automation has the experience and ability to manufacture a variety of ...
  Ideal Industries' 26 piece insulated Journeyman kit is ideal for new electricians or for ...
  Klein Tools Deluxe Fish Rod Set comes in 19 pieces that when assembled can fish wire and ...
  BendWorks Software was designed to help electrical contractors adopt this new process ...

Product News

  • Prev
  The HALO Home smart LED floodlight incorporates Bluetooth® Mesh technology into a ...
  Douglas Lighting Controls 8700 series light switches provide control over facility ...
  With 4 wattage options (20W, 28W, 36W, 40W) and lumen outputs ranging from 2,000 to ...
  BL areaBEAM BX Series are a family of high-performance box floodlight luminaires ...
  The LHB-Series Linear High Bay luminaire provides high efficacy and energy savings to ...
  Our Concept series provides proven LED technology in over 100 different models that can ...
  Features: NEW Integrated COB LED for uniform light spread. Adjustable Stainless ...
  The Philips Gardco EcoForm Gen-2 luminaire features narrow spectrum amber LEDs combined ...
  Sigma2 LED fixture features a small aperture and small profile, allowing for installation ...
  Low Voltage Mini Flood Lights provide exceptional illumination in a variety of beam ...

 

Peers & Profiles

  • Prev
David Johns is a unique and dedicated individual both at home and in the workplace. At home he is a ...
    Sean Freeman is a vibrant, enthusiastic and selfless individual who has taken his ...
  Automation companies are drivers of innovation, and have penetrated near every industry ...
Total Electrical Solutions was founded in 2013 by Jeremy Herrington in Quispamsis, on the outskirts ...
Andrew MacLeod is a territory sales manager with Leviton Manufacturing of Canada in British ...
  Floyd Lau founded Amptek Technologies in 2002 as an end to end engineering design ...
Mike Marsh, President and CEO of SaskPower, has been a leading figure in Saskatchewan’s ...
Gordon MacDonald is a cheerful, driven individual who loves to be challenged, a trait that suits ...
  Most of us have a difficult enough time managing one job and a home life. However, some ...
  Since 2012 Barnstormer has advanced the abilities of their brewery with the installation ...

Copper $US Dollar price per pound


Jeremy Herrington

Total Electrical Solutions was founded in 2013 by Jeremy Herrington in Quispamsis, on the outskirts of Saint John, New Brunswick. Since 2013 Jeremy has steadily grown Total Electrical Solutions in the residential, commercial and construction sectors. The growth is primarily the result of Jeremy’s customer first philosophy, plus his over 20 years of industry experience.

Jeremy grew up learning about the industry from his father who was an electrical contractor. Jeremy spent his early years helping and watching his father as a contractor and business owner. After high school Jeremy was, like many, not wholly aware of the course he wished to take and so he began an electrical apprenticeship at his father’s company.

Read More

Kerrwil Publications

538 Elizabeth Street, Midland,Ontario, Canada L4R2A3 +1 705 527 7666
©2018 All rights reserved

Use of this Site constitutes acceptance of our Privacy Policy (effective 1.1.2016)
The material on this site may not be reproduced, distributed, transmitted, cached or otherwise used, except with the prior written permission of Kerrwil