Canadian Electrical Industry News Week


Steve Douglas

Read Part 1 of CE 2015 Code Changes here.
Read Part 3 of CE 2015 Code Changes here.
Read Part 4 of CE 2015 Code Changes here.
Read Part 5 of CE 2015 Code Changes here.

This is the second of three articles detailing significant changes for the 2015 Canadian Electrical Code Part I (CE Code). The rules in this article are limited to changes already adopted by CE Code Technical Committee and not subject to further changes.

Table 10
Table 10 now has four tables with the addition of 10C and 10D. Table 10C has been added for the dimensions of solid conductors for calculating conduit and tubing fill, and Table 10D is for the dimensions of DLO cables for calculating conduit and tubing fill. In addition to the new tables, stranded conductor classes have been added to Tables 10A and 10B. The main reason for the Table 10 changes was to recognize that the data in Tables 10A and 10B are for stranded conductors and to provide the required conductor and cable dimensions for solid conductors and DLO cable.

Photo 1. DLO cable covered now by CE Code Table 10D
DLO Cable

Rule 12-1402
The permitted use of electrical metallic tubing has been expanded to include wet locations. The rationale for this change was to recognize the change for the designation of connectors and coupling from rain-tight to wet location type in CSA Standard C22.2 No 18.3 Conduit, Tubing, and Cable Fittings, and the change in the corrosion protection requirements of electrical metallic tubing in CSA Standard C22.2 No 83.1 Electrical Metallic Tubing — Steel.

EMT Outdoor Application
Photo 2. An example of EMT installed outdoor with wet location connectors and couplings.

Rule 12-1412
The bonding requirements for electrical metallic tubing has been moved to a new Rule 12-1402, including a new requirement for a bond conductor in all electrical metallic tubing installed in a wet location.
 
Rule 26-700
New Subrule (13) has been added to Rule 26-700; receptacles located 2 m from the floor or finished grade or installed for dedicated stationary appliances shall not be required to be tamper resistant.

Stationary Appliance
Photo 3. An example of a stationary appliance

Rule 26-956
In Rule 26-956 regarding the installation of submersible pumps, the words “lakes, rivers, and streams” have been replaced with “bodies of water”. The intent of this change was to add other bodies of water such as seas and oceans, to ensure the requirements of this rule apply to all bodies of water.

Rule 28-900
Rule 28-900 regarding the disconnecting means required for generators has been rewritten. This new requirement for generators will require a separate disconnecting means for each generator and for each circuit supplying all protective devices and control apparatus required for operation of the generator. The disconnecting means can be an integral part of the generator or installed as part of the installation. The rationale for this new wording is to provide clearer requirements, consistency of installations, and to remove product standard requirements from the CE Code.

Rule 34-110
Subrule (2) of Rule 34-110 has been revised to allow subassemblies of sign or outline lighting systems not to be bonded provided the subassemblies are supplied by a remote Class 2 power supply with an output not exceeding 30V. The rationale for this change was to provide consistency with existing bonding requirements in Sections 10 and 16.

Class 2 Sign
Photo 4. An example of a class 2 sign that does not require bonding.

Section 50
Section 50 Solar photovoltaic systems have been amalgamated with Section 64 Renewable energy systems. The definition of Panel has been deleted, and the definitions of Array and Module have been revised.

The definition of module has been changed to “Photovoltaic module — the smallest a complete and environmentally protected assembly of interconnected solar cells.” The definition of array is “a mechanically integrated assembly of photovoltaic modules with the reference to panel removed.” The rationale for these changes was to have consistent definitions with the new CSA Standard C22.2 No 61730-1 Photovoltaic module safety qualification — Part 1: Requirements for construction.

Photovoltaic Array
Photo 5. A photovoltaic array with 10 photovoltaic modules

Rule 50-006
Two new subrules have been added to the existing Rule 50-006. New Subrule (4) will limit the maximum DC voltage from photovoltaic source and output circuit voltage in or on dwelling units to 600V. This subrule will also require access to energized parts over 150V to qualified persons only, and circuits inside the building that are over 30 volts to be installed in metallic raceways, metal enclosures, or cables with a metal armour or metal sheath. The rationale for this subrule was to address installation in dwelling units between 30 and 600V DC and to harmonize with exiting requirements in Section 64.

New Subrule (5) addresses non-dwelling unit installations with a maximum DC circuit voltage between 750 and 1000V. This new subrule will exempt DC photovoltaic installations between 750 and 1000V from meeting the visible isolation and interlocking requirements of Rules 36-204, 36-208, and 36-214 for high voltage installations. This subrule was added to address the increasing number of photovoltaic farms with DC voltages up to 1000V.

Breaker Nameplate
Photo 6. A 1000V DC breaker nameplate. Note: this breaker is not of the drawout type and does not provide visible isolation

50-018
Two new subrules have been added to Rule 50-018. The first addition requires photovoltaic module interconnecting cables be supported at intervals of not more than 1 m and within 300 mm of every box or connector, and that the cables be protected against mechanical damage during and after the installation. An Appendix B note has also been added to clarify that the intent of subrule is to prevent damage to solar photovoltaic cable from rubbing on surfaces such as roofing and array structures. The second new subrule will require photovoltaic source circuits installed on or above a building to be protected against damage from rodents unless DC arc-fault protection is located at the module. An Appendix B note has also been added indicating that material such as expanded metal, solid metal, and screening can be used to enclose photovoltaic source circuit conductors as protection against damage from rodents. The rationale for this subrule was to address concerns raised during the development of the recently published CSA SPE-900 Solar photovoltaic rooftop-installation best practices guideline.

 

 

Circuit Cables
Photos 7 and 8 are photovoltaic source circuit cables damaged by rodents
Cable damage from rodents

New rule for conductor marking or colour coding
A new rule will require DC photovoltaic circuits installed between the modules and the power conditioning unit to be identified as red for positive and black for negative, or black conductors manufactured with permanent surface printing indicating the polarity on the conductor. This subrule will not allow field marking or labelling of single conductors; the cable must be supplied with permanent identification. Field colour-coding for conductors of multi-conductor cables will be permitted provided the colour-coding for conductors is at every point where the separate conductors are accessible. An Appendix B note has been added to indicate that CSA Standard C22.2 No 271 Photovoltaic Cables allows the positive or negative identification on RPV or RPVU conductor cables to be “+/–”, “pos/neg”, or “positive/negative”. The rationale for this new rule was a direct result of photovoltaic installation fires caused by unidentified and misidentified conductors connected reverse polarity.

Midway
Photo 9. A typical midway where ground-fault circuit interrupters of the Class A type is are required for all 15- and 20-amp 125V receptacles intended to supply loads in outdoor or damp locations.

Rule 66-404
This new rule will require ground-fault circuit interrupters of the Class A type for all 15- and 20-amp 125 V receptacles intended to supply loads in outdoor or damp locations in midways, carnivals, fairs and festivals. The proposal for this rule change was an IAEI-endorsed proposal. The majority of these rides and shows are set up in temporary locations, and have cords running through mud and water and strung around the aluminium barricades protecting and enclosing the rides. The condition of these cords is constantly in question and unless caught they are often not of the hard usage type as required by the code. By requiring the supply of power to be ground-fault circuit interrupter protected, we are reducing the risk of a possible fault from resulting in a fatality.

Wharf
Photo 10. 125 V receptacles on a wharf

Rule 78-052 and 78-102
Subrule (4) of Rule 78-052 and Subrule (3) of Rule 78-102 covering receptacles installed outdoors or on fixed or floating piers, docks, or wharves has been revised, deleting the exception for receptacles supplying shore power to boats. All 125-V, 15- and 20-amp receptacles installed on fixed or floating piers, docks, or wharves will now be required to be protected by a ground-fault circuit interrupter of the Class A type. The rationale for these changes was to address a shock hazard when wiring systems supplying shore power become damaged inadvertently.


208 V Motor
Photo 11. A 208 V motor now recognized in Table 44.
208 V Motor Nameplate
Photo 12. A sample of a motor nameplate for a 208V motor.

Table 44 Three-phase AC motors
Full load current values have been added for induction type, squirrel cage and wound rotor, 208V motors. The easier to use addition of this new column for 208V motors removes the need to calculate any value, which makes the table.

Read Part 1 of CE 2015 Code Changes here.
Read Part 3 of CE 2015 Code Changes here.
Read Part 4 of CE 2015 Code Changes here.
Read Part 5 of CE 2015 Code Changes here.



Steve Douglas is an IAEI International Past President. He is also the Senior Technical Codes Specialist for QPS Evaluation Services. As the International Association of Electrical Inspectors representative on Part I and Part II of the Canadian Electrical Code, Steve is the vice chair of the CE Code Part I, chair of CE Code Part I Subcommittees for Section 2, and 12, and a member on Sections 40, 64, 68, 76 and Appendix D. In addition, Steve is Chair of the CSA Standards C22.2 No. 273 Cablebus, C22.6 No. 1, Electrical Inspection Code for Existing Residential Occupancies committee, Chair of the SPE-1000 Working Group, and a member on committees for the Objective Based Industrial Electrical Code, Safety Management Systems, Solar Photovoltaic Modules, Photovoltaic Cable, Fuel Cells, Wind Turbines, Distribution transformers, Outlet Boxes, and Wiring Fittings Hardware and Positioning Devices.

 The Evolution Series. Poke-Thru Devices, Floor, Wall and Ceiling Boxes 

Legrand Wiremold EvoFrom poke-thru devices to floor, wall and ceiling boxes, the Evolution Series has continued to increase device efficiency and reliability while providing durability and quality. Customizing your space and maximizing access to all the power, A/V and communications you could ever need. Evolution Series boxes bring power, communications and A/V to walls, floors and ceilings. Evolution adds flexibility, functionality and stylish good looks to every room you create when planning office buildings, airports, schools and hospitals.

 

 

Watch the video Here

 

Changing Scene

  • Prev
Global data cable, network and CCTV tester manufacturer IDEAL Networks has donated 26 testers to ...
Stanpro and Standard Products have officially completed their merger agreement announced in early ...
Prior to joining ABB in 2017 as Executive Vice President of the Electrification business, Deschenes ...
Susan Uthayakumar, country president, Schneider Electric, has been named a Women's Executive ...
ABB presented its electrification solutions that will allow customers to take full advantage of the ...
Electricity Human Resources Canada has introduced a new Board of Directors, effective as of their ...
Jacques Fiset, the new president of the EFC Quebec section, told us in a recent interview that his ...
Organised by the Hong Kong Trade Development Council (HKTDC), the twin lighting shows - the  ...
A Friday night, the end of summer, the weather is mild, and 2,500 people — customers, ...
Eaton focuses on developing personable connections in every aspect. In September, our team will be ...

Eplan and Scholle IPNInnovation comes in all shapes and sizes. One company perfectly positioned to validate this piece of wisdom is Scholle IPN Canada, a packaging company recognized as a pioneer in providing bag-in-box solutions that themselves come in all shapes and sizes. Since 1947, they have provided innovative solutions in the packaging industry. The company specializes in aseptic packaging, a manufacturing process in which packages and containers are sterilized separately from their content. Their breakthroughs in the industry have helped brands add convenience to customers looking to get their hands-on packaged food and beverages. 

Read More

 

 

 

Investment In Building Construction - NovemberTotal investment in building construction decreased 2.0% from October to $13.7 billion in November. Both the residential (-2.2% to $9.4 billion) and non-residential (-1.6% to $4.3 billion) sectors declined. On a constant dollar basis (2012=100), investment in building construction decreased 2.1% to $11.6 billion.

In the residential sector, investment in single dwelling construction was down 2.0% to $4.9 billion, while investment in multiple dwelling construction (which includes doubles, row homes and apartments) declined 2.5% to $4.5 billion.

Read More

 

 

Tools for the Trade

  • Prev
  IDEAL Industries has introduced Combination Drill Taps to its tool lineup. Combining the ...
  Stripping and crimping device, 100 - 240 V input voltage, for insulated ferrules with a ...
Professional all-in-one cutter/stripper for coaxial and twisted pair cables     ...
  Klein Tools' Coax Explorrer 2 tests coaxial cable and maps up to 4 locations   ...
  Ideal Industries' T-14 wire stripper s are ideal for all professionals working within the ...
  The ATS850 conveyor eliminates all types of electro static discharge requirements. ...
  Lorik Tool & Automation has the experience and ability to manufacture a variety of ...
  Ideal Industries' 26 piece insulated Journeyman kit is ideal for new electricians or for ...
  Klein Tools Deluxe Fish Rod Set comes in 19 pieces that when assembled can fish wire and ...
  BendWorks Software was designed to help electrical contractors adopt this new process ...

Product News

  • Prev
Professionals searching for a reliable voltage detection solution have two new Greenlee options — ...
The new generation of the Oslon Square Hyper Red with a wavelength of 660 nm is the flagship ...
Conceived for small to mid-sized data centers, ABB’s modular Conceptpower DPA 120 uninterruptible ...
The Bulletin 1609-B Industrial Uninterruptible Power Supplies feature the rugged industrial design ...
With the new SCT current converters, Beckhoff Automation completes the power measurement chain that ...
Eureka has announced the immediate availability of Cycle in super high output (SHO) and of Cycle XL ...
Eureka has released the Cliff luminaire. Ideal for illuminating exterior facades, entrances, yards ...
LEDtronics is proud to announce a new addition to their industry-leading offering of i ...
Littelfuse has announced the availibility of their Gate Drive Evaluation Platform (GDEV).   ...
Schneider Electric’s Square D brand has announced that its patented arc flash mitigation ...

 

Juna AIMeet Juno AI, a portfolio of lighting devices that form the “backbone” of your smart and connected space.The Juno AI Speaker Light with Alexa Built-In is an advanced LED downlight that features a JBL® speaker and Amazon Alexa voice service in a single patent pending ceiling light fixture. It’s a 6” downlight, but much, much more.

Juno AI takes advantage of the most ideal location in the home – the ceiling – to create a smart ecosystem. It can control any smart home device that works with Alexa. No hub required. It not only illuminates a room, but also locks the doors, adjusts your thermostat, tells your family dinner is ready, runs the vacuum, reads you a book, dims the lights, plays music through

Read More

 

 

ABB ConceptpowerConceived for small to mid-sized data centers, ABB’s modular Conceptpower DPA 120 uninterruptible power supply (UPS) fulfill power requirements from 20 kW to 600 kW at 208V and provide maximum availability for those who aim for zero downtime as well as a low cost of ownership.  

Total vertical and horizontal scalability

The Conceptpower DPA 120 delivers power protection from 20 to 600 kW at 208V, both input and output, (one to six modules) in a single cabinet frame. Horizontal scalability is also given, with up to five frames in parallel, to increase total power up to 600 kW.

Read More

 

Peers & Profiles

  • Prev
Headquartered in Vancouver, Legend Power Systems is a global onsite energy management technology ...
LDS caught up with General Manager of EiKO’s Canadian division, Stephen Lee who was kind enough ...
“I had an awesome time, it was a lot of fun,” said Zach Agombar, who competed his way to 8th place ...
Held from November 7th to 9th in Orlando, Florida, and recently aired on ESPN 2, the Ideal National ...
Panel Upgrade Experts is an electrical contracting company started seven years ago by Paul ...
Chad Alexander is a Branch Manager with Contact Automation, which provides automation integration ...
Rob Milner is the Canadian National Science, Automation, Optical Gas Imaging & sUAS Manager for ...
EIN sat down with WiRE President & CEO Joanna Osawe to learn more about WiRE and the ...
For the second consecutive year, Paul Hannania was among the 162 professionals and apprentices to ...
Alexander Couckuyt, Director of Operations for Southwire Canada, spent the majority of his ...

 

Legend Power SystemsHeadquartered in Vancouver, Legend Power Systems is a global onsite energy management technology company. They help buildings to overcome grid volatility challenges common to utilities around the world. Legend’s industry-proven flagship product, SmartGATE enables dynamic power management of an entire building. The proprietary and patented system reduces total energy consumption and power costs, while also maximizing the life of electrical equipment. Legend’s unique solution is also a key contributor to both corporate sustainability efforts and the meeting of utility energy efficiency targets.

Read More

 

 

Copper $US Dollar price per pound

Kerrwil Publications Great Place to Work. Certified December 2019 - December 2020

538 Elizabeth Street, Midland,Ontario, Canada L4R2A3 +1 705 527 7666
©2020 All rights reserved

Use of this Site constitutes acceptance of our Privacy Policy (effective 1.1.2016)
The material on this site may not be reproduced, distributed, transmitted, cached or otherwise used, except with the prior written permission of Kerrwil