Canadian Electrical Industry News Week

 

Wiring MethodsWilliam (Bill) Burr

The CE Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the information you need. This series of articles provides a guide to help users find their way through this critical document. This is not intended to replace the notes in Appendix B or the explanations of individual requirements contained in the CEC Handbook, but will hopefully provide some help in navigating the code.In this article: Section 12 — Wiring Methods.

It should be noted that while many other sections of the code are commonly used by designers, installers and regulators, Section 12 is mostly used byelectricians, who must clearly understand all aspects of wiring, and by electrical inspectors, who audit compliance of the wiring methods with the code requirements. Electrical inspection authorities must always be consulted on specific issues related to wiring methods.

Section 12 is a general section and applies to all wiring installations except for
•    Class 2 circuits
•    community antenna distribution and radio and television circuits
•    opticalfibre cables
•    communication circuit conductors
•    conductors integral to factory-built equipment

That is, unless specified in the respective code sections covering those type of installations. We will discuss this later when dealing with Sections 16, 54, 56, and 60in future instalments.

The rules of this section may also be modified by the provisions of Section 32 — Fire alarm systems, Section 36 — High voltage installations or Section 45 — Emergency power supply, unit equipment exit signs and life safety systems.

Section 12 of the Code is divided into six parts:
•    General Requirements
•    Conductors
•    Raceways
•    Cablebus
•    Manufactured wiring systems
•    Installation of boxes, cabinets, outlets and terminal fittings

Generally the definitions in Section 0 apply throughout, but there are some special terminology definitions in the sub-section rules covering flat conductor cable type FCC.

In the General Requirements part, rules 12-010 to 12-020 apply specifically to locations where fire, mechanical, moisture or other environmental issues must be considered or locations where wiring may be prohibited, such as ducts and plenum chambers, underground installations, hoistways, lightning down conductors, entry of raceways and cables into buildings, and wiring under raised floors for data processing.

The Conductors part includes the rules applying to the installation of all types of conductors.It is divided into a general subdivision and individual subdivisions for each type of conductor.

In the General subdivision of Conductors,Rule 12-100 establishes that types of conductors must be chosen for their location with respect to moisture, corrosive action, temperature, degree of enclosure and mechanical protection as set out in Table 19. The Appendix B notes offer additional specifications on choosing the appropriate type of conductor.

Rules 12-102 to 12-120 provide general considerations for the installation of all conductors, such as:
•    the treatment of insulated conductors
•    flame test coverings
•    multi- and single-conductor cables
•    conductors in parallel
•    radii of bends in conductors
•    conductor joints and splices
•    treatment of the ends of insulated conductors
•    termination of conductors
•    termination and splicing of aluminum conductors
•    supporting of conductors

You will find, again, that extensive notes in Appendix B provide additional helpful information, including a diagram outlining configurations for installing parallel conductors.

The rest of the Conductor subdivision deals with the rules for specific types of conductors:
•    open wiring Rules 12-200 to 12-224 apply to single conductors run as open wiring (colloquially referred to as “knob and tube wiring”)
•    exposed wiring on exteriors of buildings and between buildings on the same premises —Rules 12-302 to 12-318
•    barebusbars and risers —Rules 12-400
•    non-metallic-sheathed-cable: Rules 12-500 to 12-526 (NMSC)
•    armoured cable —Rules 12-600 to 12-618
•    mineral-insulated cable, aluminum-sheathed cable, and copper-sheathed cable —Rules 12-700 to 12-716
•    flat conductor cable Type FCC —Rules 12-800 to 12-824

The third part, Raceways, includes the rules applying to the installation of all types of raceways.It is divided into a general subdivision and subdivisions for each type of raceway.

The General subdivision,Rules 12-902 to 12-944, governs the installation of all
•    raceways and conductors run in raceways
•    types of conductors and cable suitable for use in raceways as per Table 19
•    conductors in raceways
•    protection of conductors at the ends of raceways
•    inserting conductors in raceways
•    conductors, in conduit and tubing
•    joints or splices within raceways
•    stranding of conductors, electrical continuity of raceways
•    mechanical continuity of raceways
•    junction of open wiring and raceways
•    entry of underground conduits into buildings
•    raceways installed underground or where moisture may accumulate
•    metal raceways in plaster
•    protection for raceways installed in concrete, cinder concrete, and cinder fill
•    raceways completely installed before conductors are installed
•    capping of unused raceways
•    maximum number of bends in raceways
•    metal raceways embedded in slabs, pavement or roadbeds

The rest of the Raceways part documents the rules for specific types of raceways:
•    rigid and flexible metal conduit:Rules 12-1000 to 12-1014
•    rigid PVC conduit: Rules 12-1100 to 12-1124
•    rigid types EB1 and DB2/ES2 PVC conduit: Rules 12-1150 to 12-1166
•    rigid RTRC conduit: Rules 12-1200 to 12-1220
•    liquid-tight flexible conduit: Rules 12-1300 to 12-1308
•    electrical metallic tubing: Rules 12-1400 to 12-1414
•    electrical non-metallic tubing: Rules 12-1500 to 12-1514
•    surface raceways: Rules 12-1600 to 12-1614
•    underfloor raceways: Rules 12-1700 to 12-1718
•    cellular floors: Rules 12-1800 to 12-1820
•    auxiliary gutters: Rules 12-1900 to 12-1904
•    busways and splitters: Rules 12-2000 to 12-2020
•    wireways: Rules 12-2100 to 12-2112
•    cable trays: Rules 12-2200 to 12-2210

The fourth part, Cablebus, includes the rules applying to the installation of cablebus as a complete system.Rules 12-2252 to 12-2260 include:
•    the use of Cablebus
•    methods of installation
•    connection to other wiring methods
•    provisions for bonding
•    ampacities of conductors in cablebus

The fifth part, Manufactured wiring systems, includes Rules 12-2500 and 12-2502 specifying the uses permitted, and Installation of Manufactured wiring systems

The sixth sub-section, Installations of boxes, cabinets, outlets, and terminals, includes Rules 12-3000 to 12-3036 that cover
•    outlet boxes
•    outlet box covers
•    terminal fittings
•    terminal fittings behind switchboards
•    boxes in concrete construction
•    outlet box supports, boxes, cabinets and fitting supports
•    accessibility of junction boxes, outlet boxes, cabinets and fittings
•    outlet boxes attached to existing plaster work
•    outlet boxes, etc., in damp places
•    entrance of conductors into boxes, cabinets and fittings
•    unused openings in boxes, cabinets, and fittings
•    extensions from existing outlets
•    multi-outlet assemblies
•    conductors in boxes, cabinets or fittings
•    wiring space in enclosures
•    maximum number of conductors in a box,
•    pull box or junction box sizes

 In the next installment we will be discussing Section 14 — Protection and control.

* The source for this series of articles is the Canadian Electrical Code, Part I, published by CSA

Read the rest of the instalments in the series:
Part 1: Guide to the CE Code, Part I – A Roadmap (Installment 1 in a Series)
Part 2:
A Road Map to the CE Code, Part I – Installment 2
Part 3: Guide to the Canadian Electrical Code, Part I – Installment 3
Part 4: A Road Map to the CE Code, Part 1 – Installment 4
Part 5: Guide to the Canadian Electrical Code, Part I — Installment 5
Part 6: Guide to the Canadian Electrical Code, Part I — Installment 6
Part 7: Guide to the Canadian Electrical Code, Part I — Installment 7
Part 8: Guide to the Canadian Electrical Code, Part I — Installment 8
Part 9:
Guide to the Canadian Electrical Code, Part I — Installment 9
Part 10: Guide to the Canadian Electrical Code, Part 1 - Installment 10
Part 11: Guide to the Canadian Electrical Code, Part 1 - Installment 11


 

William (Bill) Burr is the former Chair of the Canadian Advisory Council on Electrical Safety (CACES), former Director of Electrical and Elevator Safety for the Province of BC, and former Director of Electrical and Gas Standards Development and former Director of Conformity Assessment at CSA Group. Bill can be reached at Burr and Associates Consulting billburr@gmail.com.

 

Changing Scene

  • Prev
ESA’s response team has been working diligently to address the emerging issues. We are moving into ...
Littelfuse invites plant engineers, facility managers, and maintenance professionals to join its ...
This recall involves Legrand / Pass & Seymour commercial-grade tamper resistant duplex ...
In response to the current COVID-19 crisis, IDEAL Canada was looking for ways to contribute to the ...
Join Nexans for a free webinar as Isaac Müller, Applications Engineer for Nexans discusses this ...
IDEAL INDUSTRIES has made the difficult but necessary decision to cancel the original ...
The Regional Electrical Inspector performs physical inspections on all types of electrical ...
The Alberta Electrical Alliance (AEA) released a video message from their Provincial Board of ...
A new white paper published by Mohawk College’s Energy and Power Innovation Centre explains how ...
With the COVID-19 crisis underway, EFC is working diligently to provide current electrical ...

Vallen CanadaIn the midst of the pandemic crisis, safety & MRO specialist Vallen Canada moved its 6,000 square foot West Edmonton, Alberta branch to a new 20,000 square foot location, enabling the branch to triple its inventory. How did the company keep everyone safe during the transition? Vallen Canada simply relied on its own expertise.

“We had to really do a good gut check on whether this was the right decision to move the branch during the pandemic,” says Vallen Canada President Karen Chester. “The reality is the show must go on… our culture is such that we pull together in tough times and we need to get the job done. The final step in the process was to make sure we keep people safe.”

Read More

 

Emergency HospitalsAs the battle against COVID-19 continues, medical providers all over the world are expanding their capacity to treat patients through the construction of temporary hospital facilities and tents. Eaton and its partners recently helped realize a project by the United States Army Corps of Engineers at Stony Brook University Hospital in New York, supplying essential power distribution equipment for four temporary medical facilities with the capacity to treat more than 1,000 patients. Construction on the facility is expected to be completed this week, with nearly 100 Eaton heavy-duty safety switches providing reliable power distribution to support life-saving ventilators and other devices.

Read More

 

 

Step-Down TransformersBy Max Ezzati

Step-down transformers allow any electrical product to be installed on 347V circuits, which is why many electrical contractors keep a few in their car stock. Selecting the correct step-down transformer ensures the physical dimensions of the transformer are as small as possible to fit easily in the junction box while keeping costs as low as possible. Here are our tips on selecting the best step-down transformer for your job.

 

 

Read More

 

 

Product News

  • Prev
In 2020, Louis Poulsen and BIG Ideas present a comprehensive new lamp series, Keglen, especially ...
Architectural sound absorbing 100% Merino Wool Felt. Made from carbonized wool treated with ...
Universal Lighting Technologies recently introduced 180W PWX LED drivers. These drivers are ideal ...
Venture Lighting International has partnered with Synapse Wireless to enhance the capabilities of ...
In its aim to develop high-performance, long-lasting, and robust lighting solutions, LUBO Lighting, ...
The highly-efficient Juno® UPLD swivel LED undercabinet in 9, 14, 22 and 30” lengths have an easily ...
Lumenpulse has launched the Lumenblade family: a collection of contemporary classic rectilinear ...
The Lithonia Lighting FML4W is a new wide housing LED Wraparound. While suitable for new ...
Douglas Lighting Controls, a member of the Panasonic family of companies, recently introduced the ...
Arlington's new low profile 5x8" TV Box™ features a steel back box for use with MC, AC and flexible ...

 

Louis Poulsen Lamp SeriesIn 2020, Louis Poulsen and BIG Ideas present a comprehensive new lamp series, Keglen, especially characterised by its distinctive design as well as classic superior lighting quality.

The key pieces in the Keglen series are four pendants (Ø175), (Ø250), (Ø400) and (Ø650) that each provide their very own diffusion of light using a curved glass insert, which is built into and adapted to each version of the shade.

The main feature of the lamp is the organic shaped glass that sits perfectly beneath the cone as a small water droplet shaped by physics and cohesive forces in nature, says Jakob Lange, Partner, BIG Ideas.

 

Read More

Universal Lighting EVERLINE PWX LED DriversUniversal Lighting Technologies recently introduced 180W PWX LED drivers. These drivers are ideal for outdoor luminaire applications, such as street, roadway and site area lighting, as well as, indoor highbays using non-Class 2 drivers.

“As the outdoor and industrial lighting segments continues to expand, Universal is focused on providing solutions that help our customers capture more market opportunities by increasing controllable options,” said Kevin Boyce Director of Product Management for Universal. “The PWX drivers are available with 12Vdc or 24Vdc auxiliary power for lighting applications with on-board sensors or radios.”

Read More

 

Peers & Profiles

  • Prev
Hazmasters was founded with a dedication and focus on creating safer work environments. It is ...
ELG Electric is an electrical contractor based out of Goderich, Ontario serving the area’s ...
Founded by Warren Osak, Electromate specializes in Robotic and Mechatronic Solutions, distributing ...
 Will West is a first-year apprentice working in the solar industry with Hakai Energy ...
“It’s definitely the Olympics of our trade,” said Lance Giesbrecht of the Ideal National ...
Tommy Carducci is a 14-year industry veteran working with Seneca Electrical and was one of 18 ...
Legend Power Systems is an innovative Canadian company headquartered out of Vancouver, B.C. Their ...
Founded in 1942, Franklin Empire is Canada’s largest independent electrical distributor.   ...
Nick Foster is Territory Manager, New Brunswick & P.E.I for Leviton. Foster was recently ...
Held from November 7th to 9th in Orlando, Florida and aired on ESPN 2, the Ideal National ...

HazmastersHazmasters was founded with a dedication and focus on creating safer work environments. It is distributor of safety products servicing customers in the industrial, construction, commercial, institution, and government markets.

The company supplies safety products, conduct safety inspections and tests, as well as service and repair safety products it. A company that educates and trains. A company that delivers every aspect of workplace safety to the employer and follows up to make those solutions easy to implement and sustain.

 

Read More

 

 

Copper $US Dollar price per pound

Kerrwil Publications Great Place to Work. Certified December 2019 - December 2020

538 Elizabeth Street, Midland,Ontario, Canada L4R2A3 +1 705 527 7666
©2020 All rights reserved

Use of this Site constitutes acceptance of our Privacy Policy (effective 1.1.2016)
The material on this site may not be reproduced, distributed, transmitted, cached or otherwise used, except with the prior written permission of Kerrwil