LightingInstallation By William (Bill) Burr

In this article: Section 30 - Installation of Lighting Equipment. The code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the information you need. This series of articles provides a guide to help users find their way through this critical document. The series is not intended to replace the notes in Appendix B or the explanations of individual requirements contained in the CEC Handbook, but will hopefully provide some help in navigating the code.

Section 30, as outlined in rule 30-000 Scope, is a supplementary or amendatory section of the code and provides additional and specific requirements for the location, installation, wiring, protection, and control of all lighting equipment. Appendix B contains important additional helpful notes and the CEC Handbook contains helpful information on determining conductor sizes and protection ratings.

Rule 30-002 - Special terminology, has definitions for terms specifically used in this section for specific types of lighting:

  • Cabinet lighting systems, undercabinet lighting systems and landscape lighting systems are complete extra-low-voltage lighting assemblies that are packaged by the manufacturer and which include installation instructions.
  • Cable lighting systems are extra-low-voltage lighting systems with bare secondary conductors for one or more luminaire heads, commonly referred to as trapeze lighting.
  • Recessed luminaires, Type IC, Inherently protected, Non-IC, and Non-IC with marked spacing are luminaires intended to be wholly or partially recessed in a ceiling or surface and are either intended to be in contact with insulation, not in contact with insulation, in contact with insulation but inherently thermal protected, or not in contact with specifically marked spacing.

General

Rules 30-100 to 30-110 cover general requirements for the installation and wiring of luminaires, lampholders, incandescent filament lamps, electric discharge lamps and associated electrical equipment.

Rule 30-102 requires that branch circuits for luminaires, etc. be limited to a nominal system voltage of 347/600volts and 150 volts-to-ground in dwelling units.

Rule 30-104 requires that the rating of protection of luminaires be based on the voltage involved, whether in a dwelling unit or non-dwelling unit, and type and arrangement of the luminaire as per sub rules (a) to (d).

Rule 30-106 requires that the overcurrent device for high-intensity discharge lighting equipment shall not be included in the luminaire or ballast box unless the combination is so marked.

Rule 30-108 requires that, except for cases of line-to-line voltage, luminaires shall be polarized so that the identified conductor is attached to the identified terminal.

Rule 30-110 requires the non-current carrying metal parts of luminaires to be bonded to ground as per the rules of Section 10.

Location of lighting equipment

Rule 30-200 provides requirements for luminaires when installed near or over combustible material.

Rule 30-202 outlines the requirements for luminaires installed in show windows.

Rule 30-204 gives restrictions on the location of luminaires installed in, and prohibits the installation of some types of luminaires in clothes closets.

Installation of lighting equipment

Rules 30-300 to 30-308 provide requirements for the installation of all lighting equipment. These rules cover such areas as preventing exposure of live parts, proper supporting of luminaires, providing covers for associated outlet boxes, providing adequate wiring space for conductors and connections and preventing temperatures exceeding conductor ratings.

Rules 30-308 to 30-310 provide requirements for circuit connections and for the insulation of conductors when the luminaire is used as a raceway.

Rules 30-312 to 314 provide requirements governing the installation of luminaires with combustible shades and enclosures and protection of luminaires below a minimum height. (Note that these requirements reflect requirements in the National Building Code as referenced in Appendix G.)

Rules 30-316 to 30-322 provide requirements for luminaires installed in damp or wet locations, lighting equipment in damp locations near grounded metal, where exposed to flying objects, and for totally enclosed gasketted luminaires.

Wiring of lighting equipment

Rules 30-400 to 30-412 provide requirements for wiring of all lighting equipment. They cover wiring of luminaires, colour coding of conductors, conductor insulation, exposed wiring on suspended luminaires, wiring of ceiling outlet boxes, wiring of show window luminaires and the use of tap connection conductors.

Luminaires in buildings of residential occupancy

Rules 30-500 to 30-510 provide specific requirements and locations for lighting equipment installed in any and all residential occupancies. These rules specify the location of lighting equipment at entrances, in dwelling units, stairways, basements, storage rooms, garages and carports. (Note that these requirements reflect requirements in the National Building Code as referenced in Appendix G.)

Lampholders

Rules 30-600 to 30-608 are the requirements for the installation of lampholders. These rules cover the connection of the identified conductor to lampholders, switched lampholders used on an unidentified circuit, luminaires with pull-type switch mechanisms, lampholders in wet or damp locations, and pendant lampholders.

Electric-discharge lighting systems operating at 1000 V or less

Rules 30-702 to 30-712 provide the requirements for the non-use of oil-filled transformers, installation on DC circuits, voltages in dwelling units, installation of auxiliary equipment such as reactors, capacitors, and resistors, control of luminaires, and branch circuit capacity.

Electric-discharge lighting systems operating at more than 1000 V

Rules 30-802 to 30-822 cover prohibition of equipment with voltage of more than 1000 volts in dwelling units, installation of lighting system control, transformer ratings, prohibition of liquid –filled transformers except for non=flammable liquids, secondary connection of transformers, location of transformers, wiring methods, transformer loading, lamp supports, lamp terminals and lampholders, and marking.

Recessed luminaires

Rules 30-902 to 30-908 provide the requirements for the installation and spacing of various types of IC, non-IC and designed-for-non-combustible-surfaces luminaires recessed in cavities in ceilings or walls.

Rule 30-910 provides requirements for the wiring of recessed luminaires.

Permanent outdoor floodlighting installations

Rule 30-1000 specifies that the requirements of this part are for installation of permanent outdoor floodlighting installations mounted on poles or towers and with the understanding that, except for changing of lamps, all maintenance is done by qualified persons.

Rules 30-1002 to 30-1014 cover service equipment, underground wiring methods, wiring methods on poles, disconnecting means at poles, overcurrent protection of pole-top branch circuits, branch circuit wiring, and joints.

Rules 30-1016 and 30-1020 are requirements for the location and overcurrent protection of transformers.

Rule 30-1020 covers the switching requirements for floodlights.

Rules 30-1022 to 30-1032 cover the grounding and bonding of outdoor floodlight installations.

Rules 30-1034 and 30-1036 covers types of equipment permitted and climbing steps on poles.

Exposed wiring for permanent outdoor lighting

Rules 30-1100 to 30-1120 provide the requirements for the installation of exposed wiring for permanent outdoor lighting other than floodlighting where the circuits are run between buildings or poles. These rules cover conductor types, use of insulators, height of conductors, spacing from combustible material, spacing of conductors, lampholders, protection of lampholders, use and construction of messenger cables, and branch circuit loading and protection.

Extra-low-voltage lighting systems

Rules 30-1200 to 30-1208 are the requirements for extra-low-voltage lighting systems and provide guidelines for sources of supply and the installation of landscape, cable and cabinet and undercabinet lighting systems.

In the next instalment, we will be discussing Section 32 - Fire Alarm Systems, Fire Pumps, and Carbon Monoxide Alarms.

* The source for this series of articles is the Canadian Electrical Code, Part I, published by CSA

William (Bill) Burr is the former Chair of the Canadian Advisory Council on Electrical Safety (CACES), former Director of Electrical and Elevator Safety for the Province of BC, and former Director of Electrical and Gas Standards Development and former Director of Conformity Assessment at CSA Group. Bill can be reached at Burr and Associates Consulting billburr@gmail.com.

 

Changing Scene

  • Prev
ESA’s response team has been working diligently to address the emerging issues. We are moving into ...
Littelfuse invites plant engineers, facility managers, and maintenance professionals to join its ...
This recall involves Legrand / Pass & Seymour commercial-grade tamper resistant duplex ...
In response to the current COVID-19 crisis, IDEAL Canada was looking for ways to contribute to the ...
Join Nexans for a free webinar as Isaac Müller, Applications Engineer for Nexans discusses this ...
IDEAL INDUSTRIES has made the difficult but necessary decision to cancel the original ...
The Regional Electrical Inspector performs physical inspections on all types of electrical ...
The Alberta Electrical Alliance (AEA) released a video message from their Provincial Board of ...
A new white paper published by Mohawk College’s Energy and Power Innovation Centre explains how ...
With the COVID-19 crisis underway, EFC is working diligently to provide current electrical ...

How to select the Best Protection against Surge



Schneider ElectricEvery household requires Surge Protection Devices to protect plug strips and all-important household appliances, from higher-level surge.

Join us on Wednesday, May 27, 2020 at 1:00PM ET, to find out how Surge Protection Devices can prevent damage to important household appliances by suppressing the surge, and how to select the right one!

Login/Register to your Electrician Portal for this free 30-minute webinar. Access to more learning sessions also available.  Login/Register Now

EIN Rittal webinar 400Rittal is putting on a free webinar for their Canadian customers discussing how IoT enabled climate control solutions can help reduce energy costs by 75%. 

Time & Date: Tuesday, May 12 at 2PM EDT

Go HERE to register

 

 

 

 

 

 

 

OntarioThe Ontario government has introduced grant funding for apprentices to purchase tools, protective equipment and clothing for their trade, along with forgiving previous loans to purchase tools. Which will be available later this year. The announcement also included support for laid off and unemployed hospitality workers.

The announcement was made by Premier Doug Ford, Christine Elliott, Deputy Premier and Minister of Health, and Monte McNaughton, Minister of Labour, Training and Skills Development.

Read More

 

 

Worker RiskMany of us take risks in their daily lives, such as using our cell phone while driving or exceeding the speed limits, while fortunately avoiding any potential injury and damage. We are rewarded by a certain convenience when we take risks, such as apparent time savings as well as the tacit approval of observers who do not oppose our risky behaviour.

To reduce injuries in the workplace, we must all recognize that we are accepting certain risks on a daily basis and acknowledge the factors influencing risk tolerance.

Read More

 

 

Product News

  • Prev
In 2020, Louis Poulsen and BIG Ideas present a comprehensive new lamp series, Keglen, especially ...
Architectural sound absorbing 100% Merino Wool Felt. Made from carbonized wool treated with ...
Universal Lighting Technologies recently introduced 180W PWX LED drivers. These drivers are ideal ...
Venture Lighting International has partnered with Synapse Wireless to enhance the capabilities of ...
In its aim to develop high-performance, long-lasting, and robust lighting solutions, LUBO Lighting, ...
The highly-efficient Juno® UPLD swivel LED undercabinet in 9, 14, 22 and 30” lengths have an easily ...
Lumenpulse has launched the Lumenblade family: a collection of contemporary classic rectilinear ...
The Lithonia Lighting FML4W is a new wide housing LED Wraparound. While suitable for new ...
Douglas Lighting Controls, a member of the Panasonic family of companies, recently introduced the ...
Arlington's new low profile 5x8" TV Box™ features a steel back box for use with MC, AC and flexible ...

 

Louis Poulsen Lamp SeriesIn 2020, Louis Poulsen and BIG Ideas present a comprehensive new lamp series, Keglen, especially characterised by its distinctive design as well as classic superior lighting quality.

The key pieces in the Keglen series are four pendants (Ø175), (Ø250), (Ø400) and (Ø650) that each provide their very own diffusion of light using a curved glass insert, which is built into and adapted to each version of the shade.

The main feature of the lamp is the organic shaped glass that sits perfectly beneath the cone as a small water droplet shaped by physics and cohesive forces in nature, says Jakob Lange, Partner, BIG Ideas.

 

Read More

Universal Lighting EVERLINE PWX LED DriversUniversal Lighting Technologies recently introduced 180W PWX LED drivers. These drivers are ideal for outdoor luminaire applications, such as street, roadway and site area lighting, as well as, indoor highbays using non-Class 2 drivers.

“As the outdoor and industrial lighting segments continues to expand, Universal is focused on providing solutions that help our customers capture more market opportunities by increasing controllable options,” said Kevin Boyce Director of Product Management for Universal. “The PWX drivers are available with 12Vdc or 24Vdc auxiliary power for lighting applications with on-board sensors or radios.”

Read More

 

Peers & Profiles

  • Prev
Hazmasters was founded with a dedication and focus on creating safer work environments. It is ...
ELG Electric is an electrical contractor based out of Goderich, Ontario serving the area’s ...
Founded by Warren Osak, Electromate specializes in Robotic and Mechatronic Solutions, distributing ...
 Will West is a first-year apprentice working in the solar industry with Hakai Energy ...
“It’s definitely the Olympics of our trade,” said Lance Giesbrecht of the Ideal National ...
Tommy Carducci is a 14-year industry veteran working with Seneca Electrical and was one of 18 ...
Legend Power Systems is an innovative Canadian company headquartered out of Vancouver, B.C. Their ...
Founded in 1942, Franklin Empire is Canada’s largest independent electrical distributor.   ...
Nick Foster is Territory Manager, New Brunswick & P.E.I for Leviton. Foster was recently ...
Held from November 7th to 9th in Orlando, Florida and aired on ESPN 2, the Ideal National ...

HazmastersHazmasters was founded with a dedication and focus on creating safer work environments. It is distributor of safety products servicing customers in the industrial, construction, commercial, institution, and government markets.

The company supplies safety products, conduct safety inspections and tests, as well as service and repair safety products it. A company that educates and trains. A company that delivers every aspect of workplace safety to the employer and follows up to make those solutions easy to implement and sustain.

 

Read More

 

 

Copper $US Dollar price per pound

Kerrwil Publications Great Place to Work. Certified December 2019 - December 2020

538 Elizabeth Street, Midland,Ontario, Canada L4R2A3 +1 705 527 7666
©2020 All rights reserved

Use of this Site constitutes acceptance of our Privacy Policy (effective 1.1.2016)
The material on this site may not be reproduced, distributed, transmitted, cached or otherwise used, except with the prior written permission of Kerrwil