By William (Bill) Burr

In this article: Section 32 — Fire Alarm Systems, Fire Pumps, and Carbon Monoxide Alarms. The code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the information you need. This series of articles provides a guide to help users find their way through this critical document. This is not intended to replace the notes in Appendix B or the explanations of individual requirements contained in the CEC Handbook, but will hopefully provide some help in navigating the code.

Section 32, as outlined in rule 32-000 Scope, is a supplementary or amendatory section of the code and provides additional and specific requirements for the location, installation, wiring, and protection of fire alarm systems, fire pumps and smoke and carbon monoxide alarms required by the National Building Code of Canada as referenced in Appendix G. For further information, refer to Canadian Standard CAN/ULC - S524 Standard for the Installation of Fire Alarm Systems published by ULC Canada. Appendix B contains important additional helpful notes, and the CEC Handbook also contains helpful information.

Fire alarm systems

Rule 32-100 specifies the requirements for conductors in fire alarm systems, which include copper material, ampacity, use of optical fibre cables, use of stranded conductors, insulation rated at 300 volts, determining wire size for raceways or integral assemblies, and selection in accordance with rules 4-008(1) or 4-020(1).

Rule 32-102 outlines wiring methods for installation of conductors either in metal, non-metallic raceway, or having a metal armour or sheath. Where installed in buildings of combustible construction, conductors may be installed in accordance with Section 12. Conductors need to be installed independent of any other wiring except for point of supply, signal, ancillary device or communication circuits and must be insulated for the highest voltage rated conductor. Communication circuits must conform to Section 60.

Rule 32-104 requires that all exposed non-current-carrying parts of electrical equipment be bonded to ground in accordance with Section 10. In addition, non-metallic fire alarm wiring systems must incorporate a bonding conductor.

Rule 32-106 denotes that for electrical supervision, each circuit conductor terminal shall be independently terminated.

Rule 32-108 specifies that the fire alarm system power supply, except for included additional control units or transponders, be on a separate circuit and that the overcurrent devices and disconnecting means be permanently identified as a fire alarm system, be coloured red, and lockable in the on position.

Rule 32-110 provides installation requirements for permanently connected smoke alarms and carbon monoxide alarms in dwelling units that are required by the National Building Code of Canada (see Appendix G). The rule requires that smoke and carbon monoxide alarms be supplied from a circuit, such as a lighting only or mixed lighting and receptacle circuit, that will provide an indication if shut off. The circuit shall also have no disconnect or a GFCI or AFCI device between the alarms and the branch circuit overcurrent device. Interconnection of alarms may use a class 2 power supply in accordance with Rules 12-506 to 12-524.

Fire pumps

Rule 32-200 requires that conductors for the supply of a fire pump supplied from the emergency power source have an ampacity not less than 125% of the full load current rating of the motor or sum of multiple motors and auxiliary motors, and be protected from fire exposure to provide continuing operation during a fire as required by the National Building Code of Canada (see Appendix G).

Rule 32-202 outlines the requirements for wiring methods of fire pumps to be installed in metal raceways, in armour or metal sheathed cable, selected in accordance with Rule 4-888(1), in rigid non-metallic conduit embedded in concrete, or electrical non-metallic tubing embedded in concrete.

Rule 32-204 provides that a separate service box for a fire pump and equipment may be installed in conformance with rule 32-206 below and, notwithstanding rule 6-102(2), may be located remote from other service boxes.

Rule 32-206 requires that no disconnecting means, overcurrent protection or device capable of interrupting the fire pump circuit may be placed between the service box and the fire pump transfer switch or controller, except a circuit breaker that is permanently labelled identifying it as a fire pump disconnect. In addition, the circuit breaker must be lockable in the closed position and may be in the separate service box as in rule 32-204 above. In the case where this circuit breaker is installed in an emergency power supply circuit between the emergency power source and the fire pump transfer switch, the rating of the circuit breaker shall be as per rule 28-200. Where it is installed in a normal supply circuit the rating should be not less than the overcurrent protection of the fire pump controller.

Rule 32-208 requires that where an on-site electrical transfer switch is used to provide emergency power supply to a fire pump, it must be provided solely for the fire pump, located in a barriered or separate compartment or enclosure, permanently labelled as the fire pump power transfer switch, and approved for fire pump service. Where more than one fire pump is provided, a transfer switch is required for each fire pump.

Rule 32-208 provides that overload and overheating protection for branch circuit, control or equipment conductors shall not be required but shall be protected by the motor branch circuit overcurrent device.

Rule 32-210 specifies that ground fault protection shall not be installed in a fire pump circuit.

In the next instalment, we will be discussing Section 34 – Signs and Outline Lighting.

* The source for this series of articles is the Canadian Electrical Code, Part I, published by CSA

William (Bill) Burr is the former Chair of the Canadian Advisory Council on Electrical Safety (CACES), former Director of Electrical and Elevator Safety for the Province of BC, and former Director of Electrical and Gas Standards Development and former Director of Conformity Assessment at CSA Group. Bill can be reached at Burr and Associates Consulting, billburr@gmail.com.

Changing Scene

  • Prev
Government Relations Minister Lori Carr announced the transfer of gas and electrical licensing ...
IDEAL continues to recognize the essential work electricians are doing during this global crisis. ...
Total investment in building construction increased 60.1% to $13.4 billion in May, ...
IDEAL Industries recently put together a new supply catalogue focused on panel builders and ...
ECAO is piloting a young leaders group, named Future Leaders Advisory Council (FLAC).   ...
Cooper Lighting extends its commitment to education and support of its customers and specifiers. ...
Stay Wired to Win is a monthly at-home challenge designed to keep your competitive spark going ...
Join the Electrical Contractors Association of Ontario (ECAO) for a live webinar on July 7 at 2:00 ...
Following the latest COVID-19 announcements from the Ontario Government, ESA has decided to ...
Introducing Stay Wired to Win – a series of monthly at-home challenges designed to keep your ...


 

LDS Aug Products Eaton AL Series Dimmers 400Eaton's Wiring Devices AL series dimmers offer a versatile option for any dimming application - fine tune the dimming performance to match your exact needs and change colors as needed to suit any décor.

Color change kits come with three color faceplates, offering design flexibility within one product. Select models are available in 4 different color combination packs.

 

 


Read More

 

ESAAs the government continues a gradual, staged approach to reopen Ontario, ESA is assessing how they can safely resume in-person classroom training while adhering to Ontario Public Health guidelines. ESA is continuing to monitor key public health indicators and Stage 3 restrictions as efforts begin to reschedule previously postponed in-person classroom courses.

If you are registered in a postponed ESA course, they will notify you in the next couple of weeks of the rescheduled date. Please note that online courses are continuing as scheduled.

 

Read More

 


 



Case Study: EikoPro Electric LLC had a customer that had just constructed a new horse barn and was looking to light it quickly. The barn was designed to be lit with ten high bay lights for maximum efficacy and efficiency. Together with EiKO’s distributor partner, Platt Electric Redmond located in Redmond, Oregon, Pro Electric selected the EiKO 200W BAY-C high bay fixture, which puts out an impressive 30,000+ lumens at a 5000K color temperature. This high lumen output and the long life of the fixture – 72,000 hours – made it an ideal choice for the application.

Obviously, when lighting a barn, the security and safety of the animals, riders, and care givers is paramount. EiKO’s LED high bay products fill the space with light, eliminating shadows and blind spots.

Read More

Product News

  • Prev
Beluce has developed a line of social distancing signs and “face covering required” signs to remind ...
Eaton's Wiring Devices AL series dimmers offer a versatile option for any dimming application - ...
The YDD-L is an energy-efficient dusk to dawn yard light. It was designed for barns and ...
Arani's single-sided LED plastic running man sign comes in 2 versions: with battery, and without ...
With three shapes and 14 sizes available, Lumewerx’s latest addition to the Pop family comes in ...
Midwest’s Metallic RV power centers are a cost-effective favorite among campground owners ...
The IDEAL SLK® Disconnect Fuse Kit is a waterproof breakaway safety device that ...
The LED Edge-Lit ceiling luminaire has a very slim design for a modern and minimalist ...
The Green Cable Surface is synonymous with flexibility.      
Bri-Thin cables are an alternative to floor heating mats for tile and stone flooring. With high ...


 

Yard LightThe YDD-L is an energy-efficient dusk to dawn yard light. It was designed for barns and farms. It is a versatile and economic light source that is good on the environment and uses long-life LED’s. The YDD-L comes standard with photo control which helps to provide significant power savings.

Lens
Polycarbonate diffused lens encloses high performance LEDs.

 

 

 

Read More

 


 

Peers & Profiles

  • Prev
At fourteen, Tom Miguel was sitting in the counselor’s office of Silverthorn Collegiate ...
Meredith Halfpenny is a Wind Site Technician with Boralex where she inspects, maintains, and ...
Rutul Bhavsar is a final year Electrical Engineering student at Mohawk College. He recently ...
Shannon Tymosko is a first-year apprentice with IBEW (International Brotherhood of Electrical ...
ELG Electric is an electrical contractor based out of Goderich, Ontario serving the area’s ...
Founded by Warren Osak, Electromate specializes in Robotic and Mechatronic Solutions, distributing ...
 Will West is a first-year apprentice working in the solar industry with Hakai Energy ...
“It’s definitely the Olympics of our trade,” said Lance Giesbrecht of the Ideal National ...
Tommy Carducci is a 14-year industry veteran working with Seneca Electrical and was one of 18 ...
Legend Power Systems is an innovative Canadian company headquartered out of Vancouver, B.C. Their ...


Tom MiguelBy Sarah PickardTom Miguel

At 14, Tom Miguel was sitting in the counselor’s office of Silverthorn Collegiate Institute in Etobicoke with his entire life ahead of him. In 1981, the world was changing, and like so many young men and women, he was faced with a world of choices that would go on to define both his career and his life.

It was in this office that some counsellor suggested becoming an electrician, and Tom’s interest was piqued. “I knew from that point on what field of studies I needed to focus on to become an electrician,” Tom said.

 

Read More

 


Rutul Bhavsar 1 400By Blake Marchand

Rutul Bhavsar is a final year Electrical Engineering student at Mohawk College. He recently co-authored a whitepaper on Mohawk College’s Joyce Centre for Partnership & Innovation discussing the technologies utilized in the state-of-the-art zero-carbon/carbon-neutral facility. Rutul was the lead author on the project, supported by Dr. Mariano Arriaga, General Manager of Mohawk’s Energy and Power Innovation Centre (EPIC) and Dr. Tony Cupido Research Chair, Sustainability at Mohawk College. Rutul’s interests lie in the more progressive areas of the industry, automation, control, and energy efficient technologies.

Read More


 

Copper $US Dollar price per pound

Kerrwil Publications Great Place to Work. Certified December 2019 - December 2020

538 Elizabeth Street, Midland,Ontario, Canada L4R2A3 +1 705 527 7666
©2020 All rights reserved

Use of this Site constitutes acceptance of our Privacy Policy (effective 1.1.2016)
The material on this site may not be reproduced, distributed, transmitted, cached or otherwise used, except with the prior written permission of Kerrwil