PfannenbergCooling units are necessary for hot enclosures, but selecting the proper temperature set point for yours can mean the difference between failure and enhanced performance

Electrical enclosures serve to protect electrical devices from adverse environmental influences, such as dirt, other particulates, moisture, or chemicals that could damage components. Plus, by housing electrical devices inside a secure enclosure or box, personnel are protected from electrical hazards such as electric shock, arc flash, and burns. However, electrical devices generate heat as a byproduct of their operation. When the heat load of the electrical devices within an enclosure exceeds the heat dissipation achieved through natural convection, the temperature inside the enclosure will rise. Since the performance and lifespan of electrical devices will degrade as temperature increases, this excessive heat must be removed in order to keep the temperature within acceptable operating limits. The “rule of thumb” warns that for every 10° C over their rated temperature limit, the life expectancy for electrical components gets cut in half.

When convection cooling would fail to successfully regulate temperature in an enclosed environment, cooling units can preserve the lifespan and performance of enclosed electrical components. Cooling units provide closed-loop cooling, using a refrigeration cycle to move heat to the outside of a sealed enclosure while maintaining the enclosure’s mechanical isolation from the ambient environment. Excessive moisture condenses on the evaporator, located on the enclosure side of the closed loop, where it can be effectively removed to keep the humidity level down and electrical components dry. These functions usually provide great value; however, too much of a good thing can diminish the efficacy of these units—and actually damage components. To avoid risking the safety and efficiency an enclosure is designed to ensure, operators must optimally set the temperature set point for any enclosure cooling unit.

When to Use a Cooling Unit for an Electrical Enclosure

1.jpgMany components commonly housed within electrical enclosures generate heat: variable frequency drives (VFDs), servo drives, programmable logic controllers (PLCs), starter kits, power supplies, inverters, relays, terminal blocks, indicator lights, transformers, and more. Many of these devices are rated for operation to 60 °C (140 °F); however, heat-producing semiconductor devices, such as diode rectifiers and transistor inverters, produce significant amounts of heat, which radiates to adjacent circuitry. In order to keep this temperature in check, heat sinks are used for dissipation, and a lower operating environment temperature rating is needed for the heat sink’s convection to be effective. As a result, a common rating for VFDs is significantly lower at 40 °C (104 °F).

When unfavorable, high temperature ambient conditions exist, convection alone—whether passive through venting of the enclosure and surface area dissipation, or forced, by using fans to exhaust the heat—cannot adequately maintain an acceptable operational temperature. In other words, if the temperature outside the box exceeds the target temperature intended inside the box, convection cooling is not going to work. In these cases, active cooling must be utilized. The enclosure air conditioner or “cooling unit” is often used to serve this purpose.

 

Factors for Determining Optimal Set Point

The enclosure cooling unit is intended to keep electrical equipment in an acceptable working environment, but this environment is not the same as the 72 °F (22.2 °C) comfort space that people would like to experience. Rather, a higher working environment temperature is acceptable—and in most instances desired for electrical equipment. As previously stated, the acceptable working environment temperature for most electrical devices exceeds 40 °C (104 °F) and excessive cooling can lead to several pitfalls.

Energy consumption and efficiency are ongoing concerns for operation managers and enclosure cooling units should not be exempt from scrutiny in these areas since compressor-based refrigeration technology consumes a fair 2.jpgamount of electricity. Excessive cooling leads to wasted energy, increased costs, and unnecessary wear and tear on the cooling units themselves. Additionally, the needless run time circulates more air through the cooling unit—resulting in increased maintenance needs for changing filters, rinsing condensers, and cleaning components. This is particularly true in environments with dusty, dirty airborne contaminants. Even highly efficient units with maintenance free, filterless designs like Pfannenberg DTS Series Side Mount Cooling Units, which are less susceptible to clogging from dirt buildup, might suffer over time if the temperature is set too low. Heat energy is also a necessary component for the optimal performance of the refrigeration cycle of the cooling unit. The evaporator is the heat exchanger responsible for transferring the heat energy of the enclosure air to the refrigeration circuit where it can be exhausted to the ambient environment at the condenser. This heat energy transfer increases as the temperature difference between the surface temperature of the evaporator and the air temperature within the enclosure increases. In other words, the refrigeration circuit operates in a less efficient manner when the enclosure air temperature is lower.

Condensation—always a concern for electrical equipment since moisture will cause corrosion, compromise resistivity, and increase the risk of short circuiting, equipment failure, sparking, and fire—forms on surfaces whose temperature falls below the dew point. It is common for the evaporator to be colder than the dew point, and Pfannenberg cooling units facilitate the management of condensation that forms on the evaporator through collection and drainage or burn-off. Problems occur when the air temperature within the enclosure falls below the dew point, leading to the formation of condensation on the electrical components themselves. The risk of condensation problems increases as the temperature set point of the cooling unit is lowered, or the dew point temperature is raised by an increase in relative humidity.

Another performance risk involves both the formation of condensation on the evaporator and, due to the set point being too low, the lack of adequate heat energy transfer to the refrigeration cycle. Since the evaporator itself can become quite cold, a lack of heat energy transfer can cause condensation which forms on the evaporator to turn to ice. Since ice will compromise the ability of the evaporator to exchange heat, the problem will cascade and more ice will form—ultimately causing a breakdown of the refrigeration cycle altogether. Should this occur, heat is not removed from the enclosure and the high temperature sensed by the cooling unit’s controller signals demand for additional work by the refrigerant compressor. That, in turn, support the continued formation of ice and leads to a compounded negative situation.  Eventually, this leads to compromise or failure of the electrical equipment inside the enclosure due to excessive heat.

Troubleshooting Hot Spots

3-1.jpgAn important performance characteristic to be aware of with enclosure cooling units is the set point hysteresis (or dead band). The manufacturer could design the controller set point at the low-point of the dead band, the high-point, or the mid-point. Pfannenberg uses the mid-point technique with a 4 °C hysteresis (+2 °C / -2 °C) and a factory default setting of 95 °F (35 °C). This means the refrigeration cycle will turn on at +98.6 °F (+37 °C) and then will turn off at +91.4°F (+33 °C). This default setting is adequate for most applications; however, the user has the ability to change the set point to suit specific circumstances and requirements.

The control temperature recognized by the cooling unit is that of the airflow being returned to the cooling unit after being pushed through the enclosure. This is not the temperature within the enclosure. It is important to note that the temperature inside of the enclosure is not homogenous; since heat is generated by components located in specific locations throughout the enclosure. Since the electrical components themselves represent an impediment to airflow, hot spots are entirely possible and should be of concern. Hot spots can be caused by an inefficient layout of components, poor or ineffective air circulation, or both. When a critical component such as a VFD experiences problems due to excessive heating, the first reaction might be to turn down the thermostat of the cooling unit on the enclosure. Although tempting, this may not be the most desirable corrective action and may actually lead to a more damaging situation since the root cause of the problem may not be getting addressed. Thermal imaging can help identify hot spots and the preferred corrective action would be to either relocate the critical components into an area of improved air circulation or add strategically placed circulating fans within the enclosure to mitigate the hot spot.

Cooling Units Provide Effective, Efficient Temperature Regulation

In conclusion, cooling units—when properly set up—provide an excellent method for active cooling of an electrical enclosure in order to keep electrical devices from exposure to temperatures that are beyond their acceptable operating limits. The acceptable operating temperature for most electrical devices is 40 °C (104 °F) or greater, and excessive cooling wastes energy, unnecessarily increases costs, adds to the maintenance burden, and can actually pose operational threats. Normally, the optimal temperature set point for electrical enclosure cooling units is approximately 95 °F (35 °C), but the hysteresis function of the cooling unit must be understood in order to achieve the actual target temperature for the airflow of the cooling unit, as this may not be the set point temperature. By utilizing Pfannenberg Cooling Units and consulting Pfannenberg expertise to ensure the proper setting of temperature set points, operators of enclosed electronics can preserve the performance and extend the lifetime of their devices.

 Cablofil® Wire Mesh Cable Tray - The Conduit Alternative 

Legrand CablofilAs the safest, easiest-to-install alternative to labor-intensive conduit, wire mesh cable management tray has been the most widely adopted wiring support method for 40 years. Electrical contractors continue to rely on tried-and-tested, code-compliant cable tray for all of their installations, including those in some of the world’s harshest environments.

5 ways Cablofil beats conduit: 1. Fewer parts 2. All you need is a bolt cutter 3. Adopts to any installation 4. One person can usually install a whole system 5. Sweeps and bends can be formed on site. 

 

 

Watch the video HERE..

 

Changing Scene

  • Prev
Jacques Fiset, the new president of the EFC Quebec section, told us in a recent interview that his ...
Organised by the Hong Kong Trade Development Council (HKTDC), the twin lighting shows - the  ...
A Friday night, the end of summer, the weather is mild, and 2,500 people — customers, ...
Eaton focuses on developing personable connections in every aspect. In September, our team will be ...
During the recently held IMARK Canada 2019 meeting in Niagara Falls, executives from 14 of the ...
Valard has been selected by Wataynikaneyap Power LPto provide engineering, procurement ...
The Canadian Apprenticeship Forum-Forum Canadien sur l’Apprentissage (CAF-FCA) has announced ...
Electricity Human Resources Canada has announced this year's keynote speakers for Agents of Change ...
Kiashke Zaaging Anishinaabek (KZA)/Gull Bay First Nation (GBFN) and Ontario Power Generation (OPG) ...
The BCEA's Woman's Network THRIVE Summit is taking place on October 4th at the Executive Inn ...

Green PlugndriveThe Government of Quebec, Ingka Group (IKEA), City of Madison and several other industry and organization innovators have pledged to join CALSTART’s Global Commercial Vehicle Drive to Zero (Drive to Zero) program. 

“By joining the Drive to Zero pledge, Québec is committing to share its transportation electrification knowledge and expertise and coordinate its efforts with those of all partners to make zero-emission technology commercially viable by 2025 in the heavy vehicle sector...

 

Read More

 

 

 

Signify“Another year of record heat waves, fires in the Amazon and Siberia, and the ice caps at their smallest for centuries. The time for debate is over – now it’s time to take urgent action,” said Eric Rondolat, CEO of Signify, who spoke during the opening ceremony of Climate Week New York City.

According to Rondolat, governments worldwide need to help realize a carbon neutral world by 2050 at the latest with companies committing to a more aggressive target of 2030. When it comes to what he described as the “low-hanging fruit of energy saving actions,” Rondolat calls for the following commitments:

Read More

 

 

Codes and Regulations Brought to You by the CSA Group

  • Prev
The Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the ...
The Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the ...
In this article: Tables — Part B. This section of the Code contains 99 tables of essential ...
In this article: Section 58 — Passenger Ropeways and Similar Equipment. Rule 58-000 ...
  Unauthorized CSA Group certification marks have been found on wiring by Triumph Cable ...
In this article: Section 52 — Diagnostic imaging installations. The CE code is a ...
In this article: Section 46 — Emergency Power Supply, Unit Equipment, Exit Signs, and ...
  In this article: Section 44 — Theatre Installations. The CE Code is a ...
CSA has published C22.2 No. 60947-7-3, the harmonized standard for low-voltage switchgear and ...
  Electric welders. The CE Code is a comprehensive document. Sometimes it can seem ...

 

Flir Application SpotlightWithout power, factory operations cannot continue. That’s why regular scheduled maintenance is important to ensure your electrical distribution system is in working order. A combination of a thermal imager and a clamp meter can help you detect hot spots and diagnose electrical issues at the point of failure before an outage occurs, quickly and safely.  Download the Application Spotlight today.

 

 

 

 

 

Read More  

 

3M WebinarRegister for 3M Canada’s upcoming webinar: How TTS™ Heat Trace Cables can help you on site.

3M Canada will be hosting a heat trace cables webinar, where you’ll learn about heat trace, heat trace applications (i.e.: pipe freeze protection, roof and gutter, and surface snow and ice melting), and the benefits of self-regulating heat trace cables—TTS™ Heat Trace Cables.

Self-regulating heat trace cables can adjust their output to the surrounding temperature down the cable length.

Read More

 

 

Tools for the Trade

  • Prev
  IDEAL Industries has introduced Combination Drill Taps to its tool lineup. Combining the ...
  Stripping and crimping device, 100 - 240 V input voltage, for insulated ferrules with a ...
Professional all-in-one cutter/stripper for coaxial and twisted pair cables     ...
  Klein Tools' Coax Explorrer 2 tests coaxial cable and maps up to 4 locations   ...
  Ideal Industries' T-14 wire stripper s are ideal for all professionals working within the ...
  The ATS850 conveyor eliminates all types of electro static discharge requirements. ...
  Lorik Tool & Automation has the experience and ability to manufacture a variety of ...
  Ideal Industries' 26 piece insulated Journeyman kit is ideal for new electricians or for ...
  Klein Tools Deluxe Fish Rod Set comes in 19 pieces that when assembled can fish wire and ...
  BendWorks Software was designed to help electrical contractors adopt this new process ...

Product News

  • Prev
The SYLVANIA ValueLED UFO High Bay is a DLC Premium LED fixture that has a lightweight, impact ...
Power Integrations announced new high-power-density members of ...
Tray portrays a picture frame design. The intention was to evoke the idea of empty picture frames, ...
Magic Lite introduces the next generation of their hugely successful LED Brick ...
The adorne Collection has expanded their line of designer switches and outlets to now come in the ...
Remee Wire & Cable, a leading manufacturer of electronic wire and cable, announces its new line ...
Remee Wire & Cable, a leading manufacturer of electronic wire and cable, announces new ...
The new CU81xx uninterruptible power supply (UPS) series is designed for universal use in the ...
The GRV-TEX-26F6 cable provides neat, protected wiring from the terminal connector of a groov ...
Eaton announced its latest release of the XLR-51 supercapacitor module.     ...

 

LYTSwitch DriversPower Integrations announced new high-power-density members of its LYTSwitch™-6 family of safety-isolated LED-driver ICs for smart-lighting applications. The new ICs with PowiGaN™ technology enable designs that deliver up to 110 W with 94% conversion efficiency using a simple, flexible flyback topology.

The high efficiency of the new LYTSwitch-6 ICs eliminates the need for heatsinks – greatly reducing ballast size, weight and cooling airflow requirements. The 750 V PowiGaN primary switches provide very low RDS(ON) and reduced switching losses. 

 

Read More

 

 

Peers & Profiles

  • Prev
Electrical Industry Canada had the pleasure of interviewing Matt Davis of Newfoundland Power, ...
An electrician by trade, Daniel Lacovetsky is the founder and President of Powertec Electric, an ...
Mike Morneau began his professional career in graphic arts after earning a Bachelor of Technology ...
AimLite offers a vast choice of lighting lines to facilitate any lighting project’s needs. ...
John Krill has been in the energy and construction industries for 35-years, now he serves as Canem ...
Ali Heighton is the Program Coordinator for IBEW Local 37 who has found success as a young ...
Flextherm was founded in 1991 by current company President, Philippe Charron. For more than 25 ...
Ouellet Electric Heating began humbly in 1960 with Charles-Emile Ouellet, who started manufacturing ...
Justin Harris is a Programmer/Electrician for COREngineering, a New Brunswick based mechanical ...
Bill Maki is an Electrical Engineer from Thunder Bay, Ontario working as a Control Systems ...

Copper $US Dollar price per pound

Kerrwil Publications

538 Elizabeth Street, Midland,Ontario, Canada L4R2A3 +1 705 527 7666
©2019 All rights reserved

Use of this Site constitutes acceptance of our Privacy Policy (effective 1.1.2016)
The material on this site may not be reproduced, distributed, transmitted, cached or otherwise used, except with the prior written permission of Kerrwil