PfannenbergCooling units are necessary for hot enclosures, but selecting the proper temperature set point for yours can mean the difference between failure and enhanced performance

Electrical enclosures serve to protect electrical devices from adverse environmental influences, such as dirt, other particulates, moisture, or chemicals that could damage components. Plus, by housing electrical devices inside a secure enclosure or box, personnel are protected from electrical hazards such as electric shock, arc flash, and burns. However, electrical devices generate heat as a byproduct of their operation. When the heat load of the electrical devices within an enclosure exceeds the heat dissipation achieved through natural convection, the temperature inside the enclosure will rise. Since the performance and lifespan of electrical devices will degrade as temperature increases, this excessive heat must be removed in order to keep the temperature within acceptable operating limits. The “rule of thumb” warns that for every 10° C over their rated temperature limit, the life expectancy for electrical components gets cut in half.

When convection cooling would fail to successfully regulate temperature in an enclosed environment, cooling units can preserve the lifespan and performance of enclosed electrical components. Cooling units provide closed-loop cooling, using a refrigeration cycle to move heat to the outside of a sealed enclosure while maintaining the enclosure’s mechanical isolation from the ambient environment. Excessive moisture condenses on the evaporator, located on the enclosure side of the closed loop, where it can be effectively removed to keep the humidity level down and electrical components dry. These functions usually provide great value; however, too much of a good thing can diminish the efficacy of these units—and actually damage components. To avoid risking the safety and efficiency an enclosure is designed to ensure, operators must optimally set the temperature set point for any enclosure cooling unit.

When to Use a Cooling Unit for an Electrical Enclosure

1.jpgMany components commonly housed within electrical enclosures generate heat: variable frequency drives (VFDs), servo drives, programmable logic controllers (PLCs), starter kits, power supplies, inverters, relays, terminal blocks, indicator lights, transformers, and more. Many of these devices are rated for operation to 60 °C (140 °F); however, heat-producing semiconductor devices, such as diode rectifiers and transistor inverters, produce significant amounts of heat, which radiates to adjacent circuitry. In order to keep this temperature in check, heat sinks are used for dissipation, and a lower operating environment temperature rating is needed for the heat sink’s convection to be effective. As a result, a common rating for VFDs is significantly lower at 40 °C (104 °F).

When unfavorable, high temperature ambient conditions exist, convection alone—whether passive through venting of the enclosure and surface area dissipation, or forced, by using fans to exhaust the heat—cannot adequately maintain an acceptable operational temperature. In other words, if the temperature outside the box exceeds the target temperature intended inside the box, convection cooling is not going to work. In these cases, active cooling must be utilized. The enclosure air conditioner or “cooling unit” is often used to serve this purpose.

 

Factors for Determining Optimal Set Point

The enclosure cooling unit is intended to keep electrical equipment in an acceptable working environment, but this environment is not the same as the 72 °F (22.2 °C) comfort space that people would like to experience. Rather, a higher working environment temperature is acceptable—and in most instances desired for electrical equipment. As previously stated, the acceptable working environment temperature for most electrical devices exceeds 40 °C (104 °F) and excessive cooling can lead to several pitfalls.

Energy consumption and efficiency are ongoing concerns for operation managers and enclosure cooling units should not be exempt from scrutiny in these areas since compressor-based refrigeration technology consumes a fair 2.jpgamount of electricity. Excessive cooling leads to wasted energy, increased costs, and unnecessary wear and tear on the cooling units themselves. Additionally, the needless run time circulates more air through the cooling unit—resulting in increased maintenance needs for changing filters, rinsing condensers, and cleaning components. This is particularly true in environments with dusty, dirty airborne contaminants. Even highly efficient units with maintenance free, filterless designs like Pfannenberg DTS Series Side Mount Cooling Units, which are less susceptible to clogging from dirt buildup, might suffer over time if the temperature is set too low. Heat energy is also a necessary component for the optimal performance of the refrigeration cycle of the cooling unit. The evaporator is the heat exchanger responsible for transferring the heat energy of the enclosure air to the refrigeration circuit where it can be exhausted to the ambient environment at the condenser. This heat energy transfer increases as the temperature difference between the surface temperature of the evaporator and the air temperature within the enclosure increases. In other words, the refrigeration circuit operates in a less efficient manner when the enclosure air temperature is lower.

Condensation—always a concern for electrical equipment since moisture will cause corrosion, compromise resistivity, and increase the risk of short circuiting, equipment failure, sparking, and fire—forms on surfaces whose temperature falls below the dew point. It is common for the evaporator to be colder than the dew point, and Pfannenberg cooling units facilitate the management of condensation that forms on the evaporator through collection and drainage or burn-off. Problems occur when the air temperature within the enclosure falls below the dew point, leading to the formation of condensation on the electrical components themselves. The risk of condensation problems increases as the temperature set point of the cooling unit is lowered, or the dew point temperature is raised by an increase in relative humidity.

Another performance risk involves both the formation of condensation on the evaporator and, due to the set point being too low, the lack of adequate heat energy transfer to the refrigeration cycle. Since the evaporator itself can become quite cold, a lack of heat energy transfer can cause condensation which forms on the evaporator to turn to ice. Since ice will compromise the ability of the evaporator to exchange heat, the problem will cascade and more ice will form—ultimately causing a breakdown of the refrigeration cycle altogether. Should this occur, heat is not removed from the enclosure and the high temperature sensed by the cooling unit’s controller signals demand for additional work by the refrigerant compressor. That, in turn, support the continued formation of ice and leads to a compounded negative situation.  Eventually, this leads to compromise or failure of the electrical equipment inside the enclosure due to excessive heat.

Troubleshooting Hot Spots

3-1.jpgAn important performance characteristic to be aware of with enclosure cooling units is the set point hysteresis (or dead band). The manufacturer could design the controller set point at the low-point of the dead band, the high-point, or the mid-point. Pfannenberg uses the mid-point technique with a 4 °C hysteresis (+2 °C / -2 °C) and a factory default setting of 95 °F (35 °C). This means the refrigeration cycle will turn on at +98.6 °F (+37 °C) and then will turn off at +91.4°F (+33 °C). This default setting is adequate for most applications; however, the user has the ability to change the set point to suit specific circumstances and requirements.

The control temperature recognized by the cooling unit is that of the airflow being returned to the cooling unit after being pushed through the enclosure. This is not the temperature within the enclosure. It is important to note that the temperature inside of the enclosure is not homogenous; since heat is generated by components located in specific locations throughout the enclosure. Since the electrical components themselves represent an impediment to airflow, hot spots are entirely possible and should be of concern. Hot spots can be caused by an inefficient layout of components, poor or ineffective air circulation, or both. When a critical component such as a VFD experiences problems due to excessive heating, the first reaction might be to turn down the thermostat of the cooling unit on the enclosure. Although tempting, this may not be the most desirable corrective action and may actually lead to a more damaging situation since the root cause of the problem may not be getting addressed. Thermal imaging can help identify hot spots and the preferred corrective action would be to either relocate the critical components into an area of improved air circulation or add strategically placed circulating fans within the enclosure to mitigate the hot spot.

Cooling Units Provide Effective, Efficient Temperature Regulation

In conclusion, cooling units—when properly set up—provide an excellent method for active cooling of an electrical enclosure in order to keep electrical devices from exposure to temperatures that are beyond their acceptable operating limits. The acceptable operating temperature for most electrical devices is 40 °C (104 °F) or greater, and excessive cooling wastes energy, unnecessarily increases costs, adds to the maintenance burden, and can actually pose operational threats. Normally, the optimal temperature set point for electrical enclosure cooling units is approximately 95 °F (35 °C), but the hysteresis function of the cooling unit must be understood in order to achieve the actual target temperature for the airflow of the cooling unit, as this may not be the set point temperature. By utilizing Pfannenberg Cooling Units and consulting Pfannenberg expertise to ensure the proper setting of temperature set points, operators of enclosed electronics can preserve the performance and extend the lifetime of their devices.

Changing Scene

  • Prev
ABB recently won an order of eBus charging solutions to support TTC as it modernizes its service ...
A consortium of Canadian energy organizations has been shortlisted to develop the electricity ...
Skills Ontario Summer Camp is a week-long day program for kids entering Grades 7-9.   ...
  Glen Dimplex Americas is proud to announce that its Vancouver facility was recently ...
May 13 to 19 is Powerline Safety Week in Ontario, which is meant to inform people across the ...
Divisional Lighting Manager Salma Siddiqui, the initiative will focus on making Westburne the ...
As of April 30, Natural Resources Canada has new dry-type transformer energy efficiency ...
Ontario Power Generation (OPG), in partnership with the Six Nations of the Grand River Development ...
The Energy Council of Canada has chosen of Fort St. John, BC Mayor Lori Ackerman as Canadian Energy ...
The winners of the New Products Competition at the MCEE 2019 trade show were announced tonight; ...

Electrician Forum Brought to you by Schneider Electric

As industry experts you know the products you use everyday better than anyone and should have input on what information you receive about products and what could improve them.

Therefore, we want your insight on the biggest challenges or issues you face when installing loadcentres, breakers (CAFI, GFI's…) and other surge protection devices. We ask that you do not provide product specific details but rather your general issues and concerns or any questions that have come to mind while working with these product types. Provide us with your valued expert insight into the issues you have faced so manufacturers can better inform you about the installation and use of these products. Lets generate some discussion that will help guide the Industry.

Make your comments  HERE

 

Lovato EFCLovato Electric Corporation was founded in Canada in 2007 and is a subsidiary company of Lovato Electric S.p.A., which was originally founded in 1922. Based in Laval, Quebec, Lovato manufactures energy and automation products. The company has joined EFC’s Industrial Controls product section.

They stock over 1,800 products for Motor Control & Protection, Control & Signalling, Circuit Protection & Isolation, Automation & Control and Energy Management.



Read More

 

 

 

 

ABB Eco FactoryABB has an extensive portfolio of eco-efficient solutions and services that can help decouple economic growth from environmental impacts. In fact, over half of ABB's worldwide revenues are generated by technologies that combat the causes of climate change. The company’s goal is to increase this contribution from 57 percent in 2018 to 60 percent by 2020.

The company’s commitment to combatting climate change includes limiting the environmental impact of its own operations. ABB’s current target for climate action is to reduce its own GHG emissions by 40 percent by 2020 from a 2013 baseline.



Read More

 

 

Codes and Regulations Brought to You by the CSA Group

  • Prev
The Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the ...
The Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the ...
In this article: Tables — Part B. This section of the Code contains 99 tables of essential ...
In this article: Section 58 — Passenger Ropeways and Similar Equipment. Rule 58-000 ...
  Unauthorized CSA Group certification marks have been found on wiring by Triumph Cable ...
In this article: Section 52 — Diagnostic imaging installations. The CE code is a ...
In this article: Section 46 — Emergency Power Supply, Unit Equipment, Exit Signs, and ...
  In this article: Section 44 — Theatre Installations. The CE Code is a ...
CSA has published C22.2 No. 60947-7-3, the harmonized standard for low-voltage switchgear and ...
  Electric welders. The CE Code is a comprehensive document. Sometimes it can seem ...

 

Keith SonesBy Keith Sones

Some days it’s hard to find happiness in what can be a gloomy world.

Pick up a newspaper or scan your preferred electronic newsfeed and you’ll likely see a series of dramatic headlines, proclaiming the end of our planet as we know it. The global population explosion will soon have us unable to feed ourselves. The oceans will rise significantly in a matter of a few decades, leaving untold billions of people stranded and homeless in the aftermath. Political scandals have become normalized, with a parade of elected officials having their transgressions regularly revealed on the front pages.

Read more about Finding The Answer......

Lighting LEEDThe Rivierè-des-Mille-Îles Park encompasses an array of natural forest, waterways, marshland and shoreline in the city of Laval, Quebec. With its exceptional biodiversity, it’s a unique natural attraction for the city, and welcomes over 150,000 visitors annually.

The Exploration Centre is the latest addition to the park and was built as the main visitor welcome area. The pavilion stands out with its modern and avant-garde architecture, and magnificent view of the nearby river.

 


Read more about Lighting Design...

 

 

Tools for the Trade

  • Prev
  IDEAL Industries has introduced Combination Drill Taps to its tool lineup. Combining the ...
  Stripping and crimping device, 100 - 240 V input voltage, for insulated ferrules with a ...
Professional all-in-one cutter/stripper for coaxial and twisted pair cables     ...
  Klein Tools' Coax Explorrer 2 tests coaxial cable and maps up to 4 locations   ...
  Ideal Industries' T-14 wire stripper s are ideal for all professionals working within the ...
  The ATS850 conveyor eliminates all types of electro static discharge requirements. ...
  Lorik Tool & Automation has the experience and ability to manufacture a variety of ...
  Ideal Industries' 26 piece insulated Journeyman kit is ideal for new electricians or for ...
  Klein Tools Deluxe Fish Rod Set comes in 19 pieces that when assembled can fish wire and ...
  BendWorks Software was designed to help electrical contractors adopt this new process ...

Product News

  • Prev
Created with the future in mind by pushing the boundaries of the current landscape of recessed ...
Meet Soraa HEALTHY, the world’s first and only blue-free LED lamp that creates light ...
Explosion-proof lighting or hazardous locations luminaires are used in environments where ...
Power management company Eaton has launched a frequency response energy solution, called Energy ...
Designed for retrofit and new construction, Evolution Series 6” Poke-Thru devices ...
The MiniFlex Model MA114 is a compact flexible AC current transformer composed of a 14-inch ...
This new range of PINET concealed internally mounting parallelogram hinges was launched ...
Don't just rely on pen and paper for your maintenance and safety inspection. Add this ...
Whether you need to eliminate the surprise of an accidental battery connection, or have visual ...
AIS designed LED high bay lights and LED low bay lights to address the varied lighting ...

 

Fluke Insulated Hand ToolElectricians and facility maintenance technicians should ideally work on de-energized electrical equipment, but that isn’t always possible, so their hand tools should provide as much protection as possible. The new Fluke1000 V Insulated Hand Tools are designed to keep workers safe in hazardous areas and are rugged enough to use in the toughest environments without breaking.

Fluke Insulated Hand Tools are manufactured using state-of-the-art German steel to Fluke’s exacting standards for quality, ruggedness, and reliability. 

 


Read More

 

 

Maxlite TrimaxMaxLite has earned a U.S. patent for the innovative linking design features of its TriMax Vapor Tight fixture. This patent, issued as U.S. Patent No. 10,168,012, brings the number of MaxLite’s issued and pending patents worldwide to 106, a testament to MaxLite’s focus on developing cutting-edge innovation.

The TriMax is engineered with connections at the top of the fixture that maintain a hermetic seal when two or more 4’ fixtures are linked together. By simply snapping a toolless connection bracket into place, installers can uniquely create an IP66 rated lighting solution that is 8’ or longer. 

Read More...

 

Peers & Profiles

  • Prev
Mark Unsworth is an electrical engineer with over 35 years of experience in project management, ...
Manygo Ho is an electrical designer with AECOM’s Buildings and Places group. Manygo designs ...
Don Neigel is Manager of the CSA-certified panel shop at Delta, BC’s Optimil Machinery. ...
New Brunswick Power recently struck a deal with Joi Scientific to develop an innovative technology ...
The Shock Doctors is an electrical contracting company operating out of Orillia, Barrie and ...
Michael Gindalang works for Dupar Controls as a panel builder for the elevator and keypad industry. ...
Energy Efficient Lighting is a LED lighting manufacturer with nearly 30 years of industry ...
Matt Stanson is a master electrician with over 30 years of experience. He now leads a team of ...
After eight months, 263 events, 17 broken clocks, and thousands of competitors, Ideal ...
The National Electrical Trade Council (NETCO) is an industry-funded, not-for-profit organization ...

Copper $US Dollar price per pound

Kerrwil Publications

538 Elizabeth Street, Midland,Ontario, Canada L4R2A3 +1 705 527 7666
©2019 All rights reserved

Use of this Site constitutes acceptance of our Privacy Policy (effective 1.1.2016)
The material on this site may not be reproduced, distributed, transmitted, cached or otherwise used, except with the prior written permission of Kerrwil