In this article: Section 58 — Passenger Ropeways and Similar Equipment. Rule 58-000 states that Section 58 is a supplementary or amendatory section of the code and applies to passenger ropeways as defined in the CSA Z98, Passenger Ropeways and Passenger Conveyers standard, which includes tramways, chairlifts, gondolas, surface ropeways, passenger conveyors, and similar equipment. In addition, ANSI B77.1, Passenger Ropeways – Aerial Tramways, Aerial Lifts, Surface Lifts, Tows and Conveyers - Safety Requirements, and Can/CSA-C22.3 No.1, Overhead Systems should be referenced.

 

 

Appendix B and the CE Code Handbook provide additional information.

Rule 58-002 provides special terminology definitions for Cabin, Messenger, Passenger Conveyor and Station.

General requirements

Rule 58-010 requires that, in addition to the spacing requirements of Rule 2-308, the headroom in working spaces around controllers, disconnecting means, and other electric equipment must be no less than 2.0 m. Part 2 of the rule provides that the requirements for headroom may be relaxed provided that

  • Only authorised persons have access to the area
  • The working space is kept clear of obstructions, and either
    • o live parts are guarded, isolated or insulated and the equipment can be examined, adjusted, serviced or maintained while energized without removing the protection, or
    • o a cautionary label advising that the equipment cannot be examined, adjusted, serviced, or maintained while energized is applied, or
    • o the applied voltage is equal or less than 30 V RMS or 42 V peak

Rule 58-012 specifies that circuits of less than 50 volts must be bonded to ground as per Rule 10-114.  Communication, control, remote control, monitoring, supervision, and signal circuits may be isolated, and grounded in accordance with Rule 10-206. The haul rope for these circuits may be isolated and ungrounded.

Rule 58-014 limits voltage for all circuits to 300 volts-to-ground except for

  • 750 volts-to-ground for motors, machine brakes, motor-generator sets, floodlighting, and heaters
  • 120 volts-to-ground for motor control circuits
  • 48 volts-to-ground for communication, control, remote control, monitoring, supervision, and signal circuits except for hand-crank-type telephone signal bell circuits
  • 30 volts-to-ground or 40 volts-to-ground peak for aerial conductors carried between towers that support the passenger ropeway, except hand-crank-type telephone signal bell circuits

Rule 58-016 provides that luminaires for night skiing or similar floodlighting applications may be installed on passenger ropeway towers and stations if there is a circuit breaker, installed in a lockable enclosure that disconnects all ungrounded conductors, and that each circuit to the luminaires is protected by a ground fault circuit interrupter (Class A GFCI).

Conductors

Rule 58-102 specifies that the minimum size of conductors for all communication, control, remote control, monitoring, supervision, and signal circuits shall be No. 26 AWG copper, except for circuits contained in travelling cables where the minimum size must be No. 20 AWG.

Rule 58-104 permits that

  • optical fibre cables, shielded cables, and conductors for operating devices, power, motor, heating, air conditioning, operating, signal, communication, control, safety, fire alarm, and lighting circuits may be grouped in raceway systems or travelling cables, providing the insulation rating for each conductor is not less than the conductor with the maximum circuit voltage
  • optical fibre cables, shielded cables, and conductors for operating devices, operating, signal, communication, control, safety, and fire alarm circuits may be run in the same aerial cable, providing that the insulation rating for each conductor is not less than the conductor with the maximum circuit voltage

Note that optical fibre cables include conductive, non-conductive and hybrid types as defined in Rule 56-102.

Wiring methods

Rule 58-200 outlines acceptable wiring methods in passenger ropeways and similar equipment:

  • Generally, all conductors, including optical fibre cables in machinery spaces, control spaces, in or on cabins, in machine rooms and control rooms must be installed in rigid metal conduit, EMT, rigid PVC conduit or wireways, except for travelling cables connecting the movable drive carriage or movable return carriage.
  • In addition, the following wiring methods may be used:
    • o mineral-insulated cable
    • o aluminum-sheathed cable
    • o armoured cable
    • o cable trays installed in accordance with Rules 12-2200 to 12-2210
    • o flexible conduit or liquid-tight flexible conduit between raceways and limit switches, interlocks, operating devices, or similar devices
    • o flexible conduit or liquid-tight flexible conduit between control panels and motors, machine brakes, motor-generator sets, disconnecting means, or pumping unit motors and valves
    • o jacketed cables installed between raceways and signal equipment and between raceways and operating devices where mechanical protection is provided and where the cables are supported including:
      • cables used in Class 1 extra-low voltage and Class 2 low-energy circuits, including but not limited to travelling cables connecting the movable carriage or movable return carriage
      • extra-low-voltage control cable
      • communication cable
      • fire alarm and signal cable
      • multi-conductor thermoplastic-insulated cable
      • hard-usage and extra-hard-usage cables
      • auxiliary gutters between controllers, starters, and similar apparatus
      • jacketed flexible cords and cables used in extra-low-voltage circuits (30 V or less), not greater than 2 m in length, supported and provided with mechanical protection

Rule 58-202 requires that supports for travelling cables be located and provided with suitable guards to prevent damage to the cables and contact with other equipment.

Protection and control

Rule 58-300 requires that motor control devices be arranged, as per rules 28-312 and 28-400, to prevent automatic restarting after shutdown where restarting could cause injury to persons.

Rule 58-302 provides that disconnecting means for the ungrounded conductors of the main drive motor and auxiliary drive motor, including their ventilation and control circuits, for each passenger ropeway or passenger conveyor must not contain a provision to automatically close the disconnecting means, and must be

  • a single disconnect which also disconnects power to the driving machine brake(s) control circuit directly or through an auxiliary contact that is positively opened mechanically (the opening not being solely dependent on springs)
  • an externally operated fusible switch or a circuit breaker, capable of being locked in the open position, and clearly labelled describing the connected load
  • readily accessible to authorized persons and located where it is visible on entry to the control room or machinery area
  • provided with a sign to identify the location of the supply side overcurrent protective device
  • a single disconnect for motors and control circuits of multiple driving machines or motors connected to a single passenger ropeway or passenger conveyor

Rule 58-304 provides that disconnecting means for utilization equipment must be

  • a single disconnect for all ungrounded conductors
  • capable of being locked in the open position and located in the machine room, control room, machine space, or control space
  • provided with a sign to identify the location of the supply side overcurrent protective device

Rule 58-306 requires that overcurrent protection be coordinated with any upstream overcurrent protective devices.

Rule 58-308 requires that every 125 V, single-phase receptacle installed in machine rooms, control rooms, machine spaces, control spaces, and counterweight enclosures be protected with a Class A type ground fault circuit interrupter.

Rule 58-310 specifies that motor controllers be rated to comply with Rule 28-500(1) except where the controller limits the available power and is labelled “power limited”. 

Branch circuits

Rule 58-400 requires that each machine room, control room, machinery space, and control space must have

  • luminaires, not supplied from the load side of the ground fault circuit interrupters required by Rule 58-308, and controlled by lighting switches within easy reach of the point of entry
  • a 125 V, single-phase, duplex receptacle, having a configuration in accordance with Diagram 1
  • a separate branch circuit for the supply of luminaires and receptacles

Rule 58-402 requires that where counterweights are installed in a building or room, luminaires, not supplied from the load side of the ground fault circuit interrupters required by Rule 58-308, must be provided and a separate branch circuit must supply lighting and receptacles.

Rule 58-404 specifies that utilization equipment other than that identified in rules 58-400 and 58-402, must be supplied by a separate branch circuit with overcurrent devices located in the machinery room, control room, machinery space or control space.

Regenerative power

Rule 58-500 requires that means must be provided to absorb regenerative power that cannot be absorbed under overhauling load or braking conditions.

In the next installment, we will be discussing Section 60 — Electrical Communications Systems.

The source for this series of articles is the Canadian Electrical Code, Part I, published by CSA. Note the CEC Handbook is also published by CSA.

William (Bill) Burr is the former Chair of the Canadian Advisory Council on Electrical Safety (CACES), former Director of Electrical and Elevator Safety for the Province of BC, and former Director of Electrical and Gas Standards Development and former Director of Conformity Assessment at CSA Group. Bill can be reached at Burr and Associates Consulting; billburr@gmail.com

 

 Cablofil® Wire Mesh Cable Tray - The Conduit Alternative 

Legrand CablofilAs the safest, easiest-to-install alternative to labor-intensive conduit, wire mesh cable management tray has been the most widely adopted wiring support method for 40 years. Electrical contractors continue to rely on tried-and-tested, code-compliant cable tray for all of their installations, including those in some of the world’s harshest environments.

5 ways Cablofil beats conduit: 1. Fewer parts 2. All you need is a bolt cutter 3. Adopts to any installation 4. One person can usually install a whole system 5. Sweeps and bends can be formed on site. 

 

 

Watch the video HERE..

 

Changing Scene

  • Prev
Jacques Fiset, the new president of the EFC Quebec section, told us in a recent interview that his ...
Organised by the Hong Kong Trade Development Council (HKTDC), the twin lighting shows - the  ...
A Friday night, the end of summer, the weather is mild, and 2,500 people — customers, ...
Eaton focuses on developing personable connections in every aspect. In September, our team will be ...
During the recently held IMARK Canada 2019 meeting in Niagara Falls, executives from 14 of the ...
Valard has been selected by Wataynikaneyap Power LPto provide engineering, procurement ...
The Canadian Apprenticeship Forum-Forum Canadien sur l’Apprentissage (CAF-FCA) has announced ...
Electricity Human Resources Canada has announced this year's keynote speakers for Agents of Change ...
Kiashke Zaaging Anishinaabek (KZA)/Gull Bay First Nation (GBFN) and Ontario Power Generation (OPG) ...
The BCEA's Woman's Network THRIVE Summit is taking place on October 4th at the Executive Inn ...

Green PlugndriveThe Government of Quebec, Ingka Group (IKEA), City of Madison and several other industry and organization innovators have pledged to join CALSTART’s Global Commercial Vehicle Drive to Zero (Drive to Zero) program. 

“By joining the Drive to Zero pledge, Québec is committing to share its transportation electrification knowledge and expertise and coordinate its efforts with those of all partners to make zero-emission technology commercially viable by 2025 in the heavy vehicle sector...

 

Read More

 

 

 

Signify“Another year of record heat waves, fires in the Amazon and Siberia, and the ice caps at their smallest for centuries. The time for debate is over – now it’s time to take urgent action,” said Eric Rondolat, CEO of Signify, who spoke during the opening ceremony of Climate Week New York City.

According to Rondolat, governments worldwide need to help realize a carbon neutral world by 2050 at the latest with companies committing to a more aggressive target of 2030. When it comes to what he described as the “low-hanging fruit of energy saving actions,” Rondolat calls for the following commitments:

Read More

 

 

Codes and Regulations Brought to You by the CSA Group

  • Prev
The Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the ...
The Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the ...
In this article: Tables — Part B. This section of the Code contains 99 tables of essential ...
In this article: Section 58 — Passenger Ropeways and Similar Equipment. Rule 58-000 ...
  Unauthorized CSA Group certification marks have been found on wiring by Triumph Cable ...
In this article: Section 52 — Diagnostic imaging installations. The CE code is a ...
In this article: Section 46 — Emergency Power Supply, Unit Equipment, Exit Signs, and ...
  In this article: Section 44 — Theatre Installations. The CE Code is a ...
CSA has published C22.2 No. 60947-7-3, the harmonized standard for low-voltage switchgear and ...
  Electric welders. The CE Code is a comprehensive document. Sometimes it can seem ...

 

Flir Application SpotlightWithout power, factory operations cannot continue. That’s why regular scheduled maintenance is important to ensure your electrical distribution system is in working order. A combination of a thermal imager and a clamp meter can help you detect hot spots and diagnose electrical issues at the point of failure before an outage occurs, quickly and safely.  Download the Application Spotlight today.

 

 

 

 

 

Read More  

 

3M WebinarRegister for 3M Canada’s upcoming webinar: How TTS™ Heat Trace Cables can help you on site.

3M Canada will be hosting a heat trace cables webinar, where you’ll learn about heat trace, heat trace applications (i.e.: pipe freeze protection, roof and gutter, and surface snow and ice melting), and the benefits of self-regulating heat trace cables—TTS™ Heat Trace Cables.

Self-regulating heat trace cables can adjust their output to the surrounding temperature down the cable length.

Read More

 

 

Tools for the Trade

  • Prev
  IDEAL Industries has introduced Combination Drill Taps to its tool lineup. Combining the ...
  Stripping and crimping device, 100 - 240 V input voltage, for insulated ferrules with a ...
Professional all-in-one cutter/stripper for coaxial and twisted pair cables     ...
  Klein Tools' Coax Explorrer 2 tests coaxial cable and maps up to 4 locations   ...
  Ideal Industries' T-14 wire stripper s are ideal for all professionals working within the ...
  The ATS850 conveyor eliminates all types of electro static discharge requirements. ...
  Lorik Tool & Automation has the experience and ability to manufacture a variety of ...
  Ideal Industries' 26 piece insulated Journeyman kit is ideal for new electricians or for ...
  Klein Tools Deluxe Fish Rod Set comes in 19 pieces that when assembled can fish wire and ...
  BendWorks Software was designed to help electrical contractors adopt this new process ...

Product News

  • Prev
The SYLVANIA ValueLED UFO High Bay is a DLC Premium LED fixture that has a lightweight, impact ...
Power Integrations announced new high-power-density members of ...
Tray portrays a picture frame design. The intention was to evoke the idea of empty picture frames, ...
Magic Lite introduces the next generation of their hugely successful LED Brick ...
The adorne Collection has expanded their line of designer switches and outlets to now come in the ...
Remee Wire & Cable, a leading manufacturer of electronic wire and cable, announces its new line ...
Remee Wire & Cable, a leading manufacturer of electronic wire and cable, announces new ...
The new CU81xx uninterruptible power supply (UPS) series is designed for universal use in the ...
The GRV-TEX-26F6 cable provides neat, protected wiring from the terminal connector of a groov ...
Eaton announced its latest release of the XLR-51 supercapacitor module.     ...

 

LYTSwitch DriversPower Integrations announced new high-power-density members of its LYTSwitch™-6 family of safety-isolated LED-driver ICs for smart-lighting applications. The new ICs with PowiGaN™ technology enable designs that deliver up to 110 W with 94% conversion efficiency using a simple, flexible flyback topology.

The high efficiency of the new LYTSwitch-6 ICs eliminates the need for heatsinks – greatly reducing ballast size, weight and cooling airflow requirements. The 750 V PowiGaN primary switches provide very low RDS(ON) and reduced switching losses. 

 

Read More

 

 

Peers & Profiles

  • Prev
Electrical Industry Canada had the pleasure of interviewing Matt Davis of Newfoundland Power, ...
An electrician by trade, Daniel Lacovetsky is the founder and President of Powertec Electric, an ...
Mike Morneau began his professional career in graphic arts after earning a Bachelor of Technology ...
AimLite offers a vast choice of lighting lines to facilitate any lighting project’s needs. ...
John Krill has been in the energy and construction industries for 35-years, now he serves as Canem ...
Ali Heighton is the Program Coordinator for IBEW Local 37 who has found success as a young ...
Flextherm was founded in 1991 by current company President, Philippe Charron. For more than 25 ...
Ouellet Electric Heating began humbly in 1960 with Charles-Emile Ouellet, who started manufacturing ...
Justin Harris is a Programmer/Electrician for COREngineering, a New Brunswick based mechanical ...
Bill Maki is an Electrical Engineer from Thunder Bay, Ontario working as a Control Systems ...

Copper $US Dollar price per pound

Kerrwil Publications

538 Elizabeth Street, Midland,Ontario, Canada L4R2A3 +1 705 527 7666
©2019 All rights reserved

Use of this Site constitutes acceptance of our Privacy Policy (effective 1.1.2016)
The material on this site may not be reproduced, distributed, transmitted, cached or otherwise used, except with the prior written permission of Kerrwil