Changes in the CSA Z462 Workplace electrical safety standard are slowing down. Good news! The 2021 edition will see significant reorganization of content in Clause 4.1, changes to existing annexes, some new annexes and a significant change to the arc flash PPE category method of determining “additional protective measures” for a work task’s arc flash risk assessment are included in the 2021 edition. CSA Z462 2021 edition will not be 100% technically harmonized with the 2021 edition of NFPA 70E.

The following information is provided for the benefit of the reader in understanding the CSA Z462 Workplace electrical safety standard and the updates/changes anticipated to the 2021 edition, and in order to update an employer’s established electrical safety program. A completed electrical safety program internal electrical safety audit would identify the need to update the electrical safety program whenever a new edition of CSA Z462 publishes.

The information provided in this article is the technical interpretation of the author and is not an official interpretation from CSA Group. The author assumes no liability for the information presented and the reader is advised to contact CSA Group after the 2021 edition publishes for any official interpretation. The information presented is based on the public review draft of CSA Z462 2021 edition. It is also noted this article doesn’t include all changes or the specific changes that are anticipated to be published.

CSA Group will publish the fifth edition of CSA Z462 Workplace electrical safety standard in January 2021. Since its inception in 2006 following CSA and NFPA executing a memorandum of understanding (MOU) to harmonize standards for North America, CSA Z462 has had a positive impact on electrical safety and the identification and effective management of arc flash and shock hazards. Lives have been saved!

The first edition was published in January 2009. Over the first four editions, a significant evolution of the standard has occurred. CSA Z462 moved from focusing on hazard identification and PPE selection to a more mature standard aligned with occupational health and safety management system standards (e.g. CSA Z45001, ISO 45001) to include a mandatory risk assessment procedure. CSA Z462 in the 2018 edition is 100% work task risk assessment based, including two unique risk assessments completed under the overall job’s risk assessment: shock risk assessment and arc flash risk assessment.

Technical harmonization of the core clauses and articles for the most part between CSA Z462 and NFPA 70E has been maintained in the first four editions. CSA Z462 includes additional annexes that were not adopted into NFPA 70E, we will see that again in the 2021 edition of CSA Z462. In the 2021 edition of CSA Z462 additional changes will be included of a technical nature related to the arc flash PPE category method that will not be published in NFPA 70E. NFPA 70E 2012 edition will include a significant new Article 360 Safety-Related Requirements for Capacitors and associated Annex R Working with Capacitors that is NOT included in the CSA Z462 2021 edition.

It is noted that the CSA Z462 2021 edition public review draft closed July 29, 2020. You are encouraged in future revision cycles to submit public comments and influence the direction of the CSA Z462 standard. The CSA Z462 Technical Committee met on October 27, 2020 to review and approve any final amendments to the draft and a final vote occurred to the draft. The 2021 edition of CSA Z462 as noted above should be published in late January 2021.

With respect to the changes as documented in the public review draft, the following changes are anticipated to be published. Not all changes are potentially included in this article.

Clause 3: definitions

The following definitions have been altered, or updated: Accessible, Balaclava (sock hood), Barrier, Equipment, Arc-Resistant, Fault Current, Available (Note), Receptacle, Shock Hazard, Voltage Nominal (Note on float voltage for DC to change the threshold for arcing fault to 60VDC from 30VDC), and Work On (Notes).

The following definitions are deleted: Branch-Circuit Overcurrent Device, Switchgear, Arc-Resistant.

The following new definitions are added: Normal Operation, Policy, Procedure, Process, and Program.

Clause 4: safety-related work practices

A substantial reorganization of content from Clause 4.1 and Clause 4.3 is anticipated to occur. This is a positive change to further clarify the framework/contents of an employer’s electrical safety program and the elements that need to be considered when completing a work task’s risk assessment procedure. Content may be deleted altogether, updated or relocated between clauses. Significant clause number changes will occur with this realignment of content.

Clause 4.1 will now identify that an employer shall create and document an “Electrical Safety Policy” that affirms the organization’s commitment to identify electrical hazards, eliminate exposure or assessment and control risks, and as a priority establish an electrically safe work condition. This policy should be documented in the employer’s electrical safety program. Clause 4.1 will now include a new clause with a general requirement that an electrically safe work condition shall be established as identified in Clause 4.2. Practices as identified in CSA Z462 Clause 4.1 and 4.3 shall be used if an electrically safe work condition cannot be established.

Justification statements for energized electrical work will be relocated from Clause 4.3 to Clause 4.1. With respect to the applicable voltage level that CSA Z462 applies to in the 2021 edition, 30VAC will be retained, but the threshold voltage for DC will be increased to 60VDC.

Reference will now be made to CSA Z45001 instead of CSA Z1000 as CSA Group adopted ISO 45001 with respect to occupational health and safety management systems. Annex A in turn has been completely updated with respect to the comparison table of how CSA Z462 aligns with the requirements of CSA Z45001.

Some updated content will be added to the risk assessment procedure clause, and specifically Clause 4.3.2.2.4 Normal operating condition will be relocated to Clause 4.1 under risk assessment procedure. This is an appropriate update as the requirements of a normal operating condition relate directly to risk assessment (e.g. likelihood of occurrence) and are not related to justification for energized electrical work.

Additionally in Clause 4.1.6.9 from the 2018 edition (this clause will be renumbered), new Annex I content will be added providing an example of a job safety planning checklist. Updated Clause 4.1 content will be included for “Lockout program and procedures.”

A significant change in the 2021 edition related to type of training will see the addition of language in the Notes for the existing Clause 4.1.7.1.5 that now recognizes that “classroom training can include interactive electronic or interactive web-based training.”

Some additional content is anticipated to be included in existing Clause 4.1.10 Portable (cord-and-plug-connected) electrical equipment related to maintenance, handling and storage.

In Clause 4.2 the two changes are anticipated to the existing Clause 4.2.5 Process for establishing and verifying an electrically safe work condition and Clause 4.2.6 Temporary protective grounding equipment. With respect to Clause 4.2.5 a note may be added with respect to where a shared neutral conductor may still carry current. Some wording changes are anticipated related to wording for a “permanently mounted absence of voltage tester.” A specific reference to UL 1436, Outlet Circuit Testers and Other Similar Indicating Devices is added. With respect to Clause 4.2.6 Temporary protective grounding equipment, expanded content may be added with respect to testing and inspection, and a new Annex T will be added with extensive additional information.

In Clause 4.3 as noted above significant content is relocated to Clause 4.1, which does enhance the flow of content. In Clause 4.3 some additional content modifications are included with respect describing the “estimate of likelihood and severity” for a work task’s shock risk assessment. CSA Z462 Table 2 Estimate of the likelihood of occurrence of an arc flash incident for ac and dc systems may see the deletion of the work task “For dc systems, insertion or removal of individual cells or multi-cell units of a battery system in an open rack,” which was a repeated work task. A new work task may be added: “Operation of a CB or switch that is not in a normal equipment condition,” for any equipment condition (the wording of this task will most likely change). An anticipated wording change to the “Removal or battery conductive intercell connector covers” to “Insertion or removal of connector covers or battery intercell connector(s).” The arc resistant switchgear work task description will be updated.

Some minor updates to Table 3 with respect to addition of “high visibility apparel” and clarifying in notes that outer wear arc-rated clothing worn over selected arc-rated PPE is not considered as part of the required ATPV for the anticipated incident energy exposure.

In Clause 4.3.7.3 Personal protective equipment, new content is added to the note providing risk control method options to consider when the incident energy exceeds the ATPV of available arc flash PPE to manage risk.

In Clause 4.3.7.3.7 Hand and arm protection, a new Table 4A Maximum use voltage for rubber insulating gloves is added to identify class number and maximum ac and dc use voltages. This table is taken from ASTM F496 Standard Specification for In-Service Care of Insulating Gloves and Sleeves, Table 1 Voltage Requirements.

The most significant anticipated change in CSA Z462 2021 edition relates to Clause 4.3.7.3.15 Arc Flash PPE category method. The existing Table 6A electrical equipment parameters were used with the new IEEE 1584 2018 edition formulas, and a new arc flash PPE category 5, minimum 75 cal/cm2 will be added for 600V class switchgear. As well, the arc resistant electrical equipment rows will clarify that the arc flash PPE category is N/A when doors are closed and secured and the available fault current does not exceed the arc-resistant rating of the electrical equipment.

A new alternate table to Table 6A, Table V.1 is also added in a new Annex V Arc flash PPE categories that will be a normative annex. The existing Table 6A Arc-flash PPE categories for alternating current (ac) systems has not been deleted and either Table 6A or Table V.1 can be used. Included in the new Annex V is Figure V.1, Table V.1 Arc flash PPE categories selection flow chart, which is provided as a guide to the use of the alternate Table V.1. Table V.1 and was added in an effort to simplify the information gathering required to use the arc flash PPE category method. Of significance this new Table V.1 includes electrical equipment that is “240VAC single phase,” indicating an arcing fault probability is sustainable for 240VAC single phase electrical equipment. Official clarification can be requested from CSA Group when the 2021 edition of CSA Z462 is published with respect to the addition of 240VAC single phase electrical equipment as capable of sustaining an abnormal arcing fault condition. Table 6C Personal protective equipment (PPE) is updated to include arc flash PPE category 5, minimum 75 cal/cm2.

Clause 5: safety-related maintenance requirements

A general rewrite of Clause 5 is anticipated. A lot of the existing content is retained but will be moved, and the clause numbering is completely updated. A new clause is added with respect to the owner of the electrical equipment establishing, implementing and maintaining a documented maintenance program for electrical equipment and references the CSA Z463 Maintenance of electrical equipment standard. The updates, revisions and additions to Clause 5 improve its readability and the interpretation of the information presented.

Annexes

In the CSA Z462 2021 edition several existing annexes are updated and we anticipate the provision of several new annexes to provide additional explanatory and supplemental information to reference with respect to the core clause content of CSA Z462.

Annex A will be updated referencing CSA Z45001 and a new cross reference table provided specific to CSA Z462 and the CSA Z45001 occupational health and safety management system intent or objective.

Annex D: the existing IEEE 1584 2002 edition content is deleted and a reference only (no detailed formulas content from IEEE 1584 will be included) to the new updated IEEE 1584 2018 edition added.

Annex I Sample job briefing and planning checklist: a new Figure I.2 Sample job planning checklist is added.

Annex J Sample energized electrical work permit Figure J.2 Energized electrical work permit flow chart will be amended to update the applicability of the permit for 30VAC or now 60VDC.

Annex K General categories of electrical hazards: a complete rewrite related to arc blast is now included indicating that arc blast pressure is not as significant as it has been presented in the past. Note I have quoted that 40 cal/cm2 of incident energy is not a stop point for energized work, which has been a true statement for over 10 years. This updated published information in Annex K will now provide additional substantiation for this. Energized work tasks can be performed up to 140 cal/cm2 of incident energy, as an arc flash suit is available from Oberon Company with an ATPV of 140 cal/cm2.

Annex O Safety-related design has been significantly updated with changes, and editions.

Annex P [NEW] Electrical switching and isolation is added to provide general information for low or high voltage complex switching and isolation, including a new Figure P.2 Example Switching Order form.

Annex Q Arc flash and shock warning equipment labels includes minor wording updates, and updated example equipment labels to correct the orange colour used to properly align with ANSI Z535. A specific note is now included that states electrical hazard information for supervised industrial installations can be provided in alternative methods other that the application of equipment labels.

Annex T [NEW] Temporary Protective Grounding is added provide additional application information further than the content of CSA Z462, Clause 4.2.6.

In closing, the CSA Z462 Workplace electrical safety standard has made a significantly positive impact in Canada since 2009 to worker safety related to energized electrical work. Many employers are referencing CSA Z462 when developing their electrical safety programs and in determining the hierarchy of risk control methods to apply to work tasks to eliminate exposure to arc flash and shock for qualified electrical workers and task qualified workers or to reduce risk to as low as reasonably practicable.

As above, this article is not an official interpretation from CSA Group and is based on the publicly released public review draft and the interpretation of the author of this article. You are advised to contact CSA Group when CSA Z462 2021 edition is published in late January 2021 for any official interpretation.

If you would like to discuss this article and the information presented please contact me: terry.becker@twbesc.ca or 1-587-433-3777.

[IT]Terry Becker, P.Eng., CESCP, IEEE Senior Member is the first past Vice-Chair of the CSA Z462 Workplace electrical safety Standard Technical Committee and currently a voting member and working group leader for Clause 4.1 and the Annexes. Terry is also a voting member on the CSA Z463 Maintenance of electrical systems Standard and a voting member of the IEEE 1584 Guide for Performing Arc-Flash Hazard Calculations. Terry has presented at conferences and workshops on electrical safety in Canada, the USA, India, and Australia. Terry is a Professional Engineer in AB, BC, SK, MN and ON. Terry is an Electrical Safety Specialist, Management Consultant at TW Becker Electrical Safety Consulting Inc. and can be reached at 1-587-433-3777 or by email: terry.becker@twbesc.ca.

Title: Ready, Set, Scale: How to Grow Your Field Service Business

SimProThrough many trials and tribulations, you’ve grown your business to where it is today. It’s taken blood, sweat, tears, long hours and sacrifice. But, it’s all been worth it to have something which you can call your own. It’s even more worth it when you can finally take that next step to grow your business even further and expand your service, project and maintenance work.

Read More


 

Changing Scene

  • Prev
43 years ago, Steve Silverstein bought a table saw and a delivery van and began a revolution in the ...
E.B. Horsman & Son (EBH) has announced their Victoria location will be officially moving to a ...
 The Maritime’s largest Mechanical and Electrical event took place last Wednesday and ...
IDEAL INDUSTRIES, INC. is calling all professional and student-apprentice electricians to come out ...
Vivi White has been appointed to the Board of Directors of the Electrical Safety Authority ...
The Sonepar Ontario Region is proud to announce the relocation of their SESCO Central Distribution ...
The Electrical Safety Authority (ESA) is looking for a seasoned business executive drawn from an ...
David Rellinger, Vice President of Systems Transformation for Schneider Electric (SE), has been ...
The National Electrical Trade Council (NETCO) is pleased with the direction of the 2022 budget with ...
The Executive of Gerrie Electric Wholesale Limited is very pleased to announce the acquisition of ...

Become a Wiser Approved Installer

Schneider Wiser Installer

Get access to exclusive benefits, product discounts and resources that will help you drive more business, and lower energy bills for your clients.

 

 

 

Read More


 



Vivi WhiteVivi White has been appointed to the Board of Directors of the Electrical Safety Authority (ESA) by the Honourable Ross Romano, Minister of Government and Consumer Services.

“As Chair, I am pleased that the Ontario Government recently appointed Vivi White to the Board,” said Annette Bergeron. “The Electrical Safety Authority’s efforts over the years have greatly improved the safety of the people of Ontario. It’s an important mandate and requires a strong, talented and diverse board as we transform into a modern regulator.”

 

Read more


 

Omnicable joins ETIMETIM North America announced that OmniCable has joined the product classification standards organization. Headquartered in West Chester, PA, OmniCable has 24 locations throughout North America, and also owns Houston Wire & Cable (HWC). The company partners with many electrical manufacturers and only sells to distributors.

According to John Dean, Director of Marketing & E-Commerce, OmniCable/HWC, “The wire and cable industry is often called commodities, but there are very distinct features and attributes for the different products our manufacturers produce. 

Read More

 


 

Canadian Electrical Contractor Discussion Group: Can You Count the Deficiencies?

EIN CECD 400Have you ever been called to fix the work of a 'handyman'?

"Was supposedly done by a"certified ' electrician....told the homeowner that he got a $266 permit....no record at TSBC. Can you count the deficiencies?"

"There is a second panel change in the triplex also.......even more deficiencies. Think the guy was a glorified handyman. Ones not obvious: 240 BB heat hooked up 120....drier on 2p20....range on 2p50....water heater fed with 2c14 Bx on 2p15."

Go HERE to join the discussion

 


 

Switch to Smart, Switch to Easy, Switch to Beautiful

Schneider Connected LivingScrewless wall plates. Smart Outlets. Square D™ Switches and Receptacles are raising the bar on aesthetics, ease of installation, remote lighting control and connectivity.

 

 

 

Read More


 



 

FlukeElectrical distribution problems are not always immediately identified as issues with power quality. An example of this is a thermal-magnetic circuit breaker. When it trips, the indication is generally a short circuit, ground fault, or overload. At times this can be put down to an old breaker that needs replacing.

However, it’s important to investigate the types of loads on the system and monitor harmonics for a potential disturbance. This article explores common issues with power quality and how to troubleshoot those issues.

 

 

Read More


 

EIN Romex 12 2 Recall 400This recall involves a yellow electrical wire, 12/2 NMD90 75M Romex SIMpull cable, sold by the spool. Products were also sold at Home Depot designated as article 108196.  Only cables with a time stamp between 12:41 and 18:02 are affected by this recall. 

The recalled product contains a neutral wire that is a smaller 14-gauge wire, contrary to the stamp on the wire identifying both the neutral and “hot” wires as 12-gauge (i.e., "12/2"). 

The recalled product contains a 14-gauge neutral wire instead of 12-gauge (as labelled), thus it may not perform as expected in 12-gauge applications, resulting in a risk of those applications having impaired performance and/or compliance with safety codes or standards.

Go HERE for more information


 

Product News

  • Prev
Klein Tools introduces the new Advanced Circuit Tracer Kit, offering tracing of breakers and ...
The SYM-IN "In Table" model provides an attractive user interface while solid construction ...
The NEW Contractor Select™ version of the Juno Podz™ Canless Downlight is now easier than ever ...
Introducing the NEW Hi-Tech Valiant™ full-range current-limiting fuse for fire mitigation. No one ...
Appleton™ explosionproof and dust-ignition proof GR, GRF and GRTS conduit outlet boxes are ...
Southwire's new 100' LED string lights with 12,000 Lumens.    
Help provide comfort and functionality to your bathroom with the addition of the Broan BHF110 ...
The PWB-CMU8 is the first dedicated Masonry Wall Box engineered for installation in 8” block walls. ...
Now with pre-sized labels and even more materials to take on the toughest on-site labelling jobs. ...
The STACK Family is now complete! These four performance-tiered solutions were designed to help you ...

Liteline Continues Canadian Investment

EIN BC Liteline 400Adding continued investment in Canada to its core foundation of innovative Design, installation efficiency, and personal customer service, Liteline has just announced the opening of its 12,729 square foot Showroom and Lighting Distribution Center in Langley BC.

The new Liteline Facility is located at 26550 Gloucester Way, Unit A110 and will house the new Liteline Distribution Center along with a product showroom. 

Read More




Greenlee Mobile Bending Table for 881 Series Hydraulic BendersGreenlee is bringing secure and easy-to-transport conduit bending capabilities to jobsites with the introduction of its Mobile Bending Table for 881 Series Hydraulic Benders. The new product combines the latest in anti-theft protection with enhanced mobility, easy set-up and quick teardown.

“Electricians are constantly trying to do work more efficiently. Anytime we can shave time off a job, it’s a win – and this product delivers that with easier set-up and portability. At the same time, we know that protecting equipment from theft is an issue for a lot of tradespeople. The new Greenlee Mobile Bending Table for the 881 Series Hydraulic Benders is our latest solution to help professionals safeguard their investments and increase productivity,” 

Read More


 

 

Klein Tools Upgraded Testing KitKlein Tools introduces the Premium Electrical Test Kit.

Premium Electrical Test Kit (Cat. No. 69355)

  • Refreshed kit that features three new product releases geared towards a variety of electrical testing applications.
  • Kit includes instructions and all required batteries.

Manual-Ranging Digital Multimeter with Right-Angle Test Leads (Cat. No. MM320 – Exclusive to Cat. No. 69355 and Cat. No. MM320KIT)

  • Measures up to 600V AC/DC voltages, 10A DC current and 2-ohm resistance
  • Also tests batteries, diodes and continuity.

Read More


 

 

Brady M211Design, preview and print – all from your phone. Simple and intuitive, the M211 Label Printer is built for the job site, running all day on a full charge while resisting drops, shocks and crushes.

  • Simple. Easy. Intuitive.  Seamlessly design, preview and print labels from the industry leading Express Labels App on your familiar smartphone and swiftly connect to your printer.
  • Label it once.  Now with both pre-sized and continuous labels in 90+ cartridges, filled to the brim with reliable, tested and dedicated label materials that stay attached and remain legible on every surface and in any environment.

 

Read More


 

Peers & Profiles

  • Prev
Watt’s the Word is a recently launched Electrical Industry Podcast hosted by Zack Hartle and ...
Allana Kellett-Jamieson loves working in the electrical sector and is proud of the great focus ...
As the head of ABB Canada's electrification business unit, Éric Deschênes is no newcomer to the ...
Karen Pullen knows what it’s like to be the only woman on a construction site, and as a proud ...
As of February 2021, Martin Stephenson is the new President and CEO of Signify Canada.   ...
This past July, Kerith Richards, who has worked for Service Wire Company for the last seven years, ...
EngWorks was formed in 2004 as an electrical engineering and consulting firm by Allan Bozek, “After ...
Headquartered in Concord, Ontario, Mercury Lighting services national retail, ...
Among the recipients of the 2021 Clean50 Awards announced last month is Carolina Gallo, Vice ...
Sarah Silverstein is a principal with Liteline along side her two brothers Mark and Daniel. ...


Brent NeillyBy Blake Marchand

Brent Neilly is the Group Marketing Manager with Milwaukee, he has a background in business communications with a B.A. from Brock University, as well as experience working in the construction industry.

“When I joined TTI (Milwaukee’s parent company) it was kind of a perfect match, I had some marketing knowledge from my business degree and some industry experience from working in the trades.” Neilly gained his experience covering an area from Orillia to Timmins, Ontario when he first joined the company as a Field Sales Rep, as well as on their Job Site Core Trade Specialists in the GTA where he found his niche working with utility clients. 

Read More


 

Copper $US Dollar price per pound

Kerrwil Publications Great Place to Work. Certified December 2019 - December 2020

538 Elizabeth Street, Midland,Ontario, Canada L4R2A3 +1 705 527 7666
©2022 All rights reserved

Use of this Site constitutes acceptance of our Privacy Policy (effective 1.1.2016)
The material on this site may not be reproduced, distributed, transmitted, cached or otherwise used, except with the prior written permission of Kerrwil