Section 32 – Fire Alarm Systems, Smoke and Carbon Monoxide Alarms, and Fire Pumps, as outlined in Rule 32-000 Scope, is a supplementary or amendatory section of the code and provides additional and specific requirements for the location, installation, wiring, and protection, of

• local fire alarm systems

• permanently connected smoke and carbon monoxide alarms

• fire pumps required by the National Building Code of Canada as referenced in Appendix G

For further information, reference should also be made to Canadian Standard CAN/ULC – S524 Standard for the Installation of Fire Alarm Systems published by https://canada.ul.com/. Appendix B contains important additional helpful notes and the CEC Handbook also contains helpful information.

Fire alarm systems

Rule 32-100 specifies the requirements for insulated conductors and cables in fire alarm systems which include:

• copper material

• ampacity

• use of optical fiber cables

• use of stranded conductors

• insulation rated at 300 volts

• determining wire size for raceways or integral assemblies

• selection in accordance with rules 12-102(3) or 12-122(1)

Rule 32-102 outlines wiring methods for installation of insulated conductors:

• either in metal, non-metallic raceway, or having a metal armour or sheath

• where installed in buildings of combustible construction, conductors must be installed in accordance with Section 12

• conductors need to be installed independent of any other wiring except for point of supply, signal, ancillary device, or communication circuits and must be insulated for the highest voltage rated conductor

• communication circuits must conform to Section 60

Rule 32-104 requires that all exposed non-current-carrying parts of electrical equipment must be bonded to ground in accordance with Section 10, and that non-metallic fire alarm wiring systems must incorporate a bonding conductor. sized in accordance with Rule 10-616.

Rule 32-106 denotes that for electrical supervision, each circuit conductor terminal shall be independently terminated.

Rule 32-108 specifies that the fire alarm system power supply, except for included additional control units or transponders, be on a separate circuit and that the overcurrent devices and disconnecting means be permanently identified as a fire alarm system, be coloured red, and lockable in the on position.

Rule 32-200 provides installation requirements for permanently connected smoke alarms and carbon monoxide alarms in dwelling units that are required by the National Building Code of Canada (see Appendix G). The rule requires that

• smoke and carbon monoxide alarms be supplied from a circuit, such as a lighting only or mixed lighting and receptacle circuit

• that will provide an indication if shut off

• have no disconnect between the alarms and the branch circuit overcurrent device

• have no GFCI or AFCI device between the alarms and the branch circuit overcurrent device, except where a smoke, carbon monoxide or a combination smoke and carbon monoxide alarm has an integral battery as a secondary supply source

As an exception to the requirements of Rules 32-100 and 32-102, where a smoke alarm, carbon monoxide alarm and associated equipment circuit utilizes a Class 2 power supply for interconnection, Class 2 wiring methods may be used for buildings of combustible construction, in accordance with Rules 12-506 to 12-524.

Fire pumps

Rule 32-300 requires that insulated conductors for the supply of a fire pump supplied from the emergency power source have an ampacity not less than 125% of the full load current rating of the motor or sum of multiple motors and auxiliary motors, and be protected from fire exposure to provide continuing operation during a fire as required by the National Building Code of Canada (see Appendix G).

Rule 32-302 outlines the requirements for insulated conductors of fire pumps to be installed in metal raceways, in armour or metal sheathed cable, selected in accordance with Rule 12-102 (3) in rigid non-metallic conduit embedded in concrete, or electrical non-metallic tubing embedded in concrete.

Rule 32-304 provides that a separate service box for a fire pump and equipment may be installed in conformance with rule 32-306 below and, notwithstanding rule 6-102(2), may be located remote from other service boxes.

Rule 32-306 requires that no disconnecting means, overcurrent protection or device capable of interrupting the fire pump circuit may be placed between the service box from the normal power supply and the fire pump transfer switch or controller:

• except a circuit breaker that is permanently labeled identifying it as a fire pump disconnect.

• In addition, the circuit breaker must be lockable in the closed position and may be in the separate service box as in Rule 32-304 above.

• In the case where this circuit breaker is installed in an emergency power supply circuit between the emergency power source and the fire pump transfer switch, the rating of the circuit breaker shall be

◦ as per rule 28-200

◦ be set or rated to not less than the rating of the overcurrent protection provided integral with the fire pump transfer switch

◦ indefinitely carry the locked rotor current of the fire pump

◦ where it is installed in a normal supply circuit be rated not less than the overcurrent protection of the fire pump controller

• where the circuit breaker is installed in an emergency supply feeder between the emergency generator and the fire pump transfer switch, the feeder must bypass the generator main circuit breaker and be connected directly to the emergency generator.

Rule 32-308 requires that where an on-site electrical transfer switch is used to provide emergency power supply to a fire pump, it must be provided solely for the fire pump, located in a barriered or separate compartment or enclosure, permanently labeled as the fire pump power transfer switch, and suitable and marked for fire pump service. Where more than one fire pump is provided, a transfer switch is required for each fire pump.

Rule 32-310 provides that overload and overheating protection for branch circuit, control or equipment conductors shall not be required but shall be protected by the motor branch circuit overcurrent device.

Rule 32-210 specifies that ground fault protection shall not be installed in a fire pump circuit.


In the next installment, we will be discussing Section 34 – Signs and Outline Lighting.

William (Bill) Burr is the former Chair of the Canadian Advisory Council on Electrical Safety (CACES), former Director of Electrical and Elevator Safety for the Province of BC, and former Director of Electrical and Gas Standards Development and former Director of Conformity Assessment at CSA Group. Bill can be reached at Burr and Associates Consulting billburr@gmail.com.

* Source: CSA C22.1:21, Canadian Electrical Code, Part 1 - Safety Standard for Electrical Installations. © 2021 Canadian Standards Association. Please visit store.csagroup.org. With the permission of CSA Group, material is reproduced from CSA Group standard CSA C22.1:21, Canadian Electrical Code, Part 1 - Safety Standard for Electrical Installations. This material is not the complete and official position of CSA Group on the referenced subject, which is represented solely by the Standard in its entirety. While use of the material has been authorized, CSA Group is not responsible for the manner in which the data are presented, nor for any representations and interpretations. No further reproduction is permitted. For more information or to purchase standard(s) from CSA Group, please visit store.csagroup.org or call 1-800-463-6727.

Changing Scene

  • Prev
ECAO and OEL are working on obtaining more contractor experiences with the ESA permit system. ...
Agents of Change is an event for stakeholders from Canada's electricity and beyond to build ...
Schneider Electric is introducing a personalized digital experience for logged in customers ...
Teledyne Technologies Incorporated announced the successful completion of the acquisition of FLIR ...
Stanpro (Standard Products Inc.) announced the start of its 60th anniversary celebrations. ...
The Government of Canada is taking action to cut pollution from all sectors of the economy – ...
E.B. Horsman & Son has recently announced that their Terrace branch will be moving down the ...
On June 23, the EDA’s Teresa Sarkesian, President and CEO, signed the Electricity Human Resources ...
The Electrical Safety Authority (ESA), announced the launch of its inaugural podcast series, ...
Delta Transformers launches its online training courses for its distribution and power ...


 

Teledyne FlirTeledyne Technologies Incorporated announced the successful completion of the acquisition of FLIR Systems, Inc. At each of the respective company’s special meeting of stockholders held on May 13, 2021, the stockholders approved and adopted merger proposals related to the Agreement and Plan of Merger dated January 4, 2021.

FLIR will now be included in Teledyne’s Digital Imaging segment and operate under the name Teledyne FLIR.



Read More


 

Canadian Electrical Contractor Discussion Group: Can You Count the Deficiencies?

EIN CECD 400Have you ever been called to fix the work of a 'handyman'?

"Was supposedly done by a"certified ' electrician....told the homeowner that he got a $266 permit....no record at TSBC. Can you count the deficiencies?"

"There is a second panel change in the triplex also.......even more deficiencies. Think the guy was a glorified handyman. Ones not obvious: 240 BB heat hooked up 120....drier on 2p20....range on 2p50....water heater fed with 2c14 Bx on 2p15."

Go HERE to join the discussion

 


 



 

Terry BeckerTerry Becker, P.Eng., CESCP, IEEE Senior Member

IEEE 1584.1 Guide for Specification of Scope and Deliverable Requirements for an Arc-Flash Hazard Calculation Study in Accordance with IEEE Std 1584 provides detailed guidance on how to complete an arc flash hazard incident energy analysis study and recommended content for the P.Eng. authenticated report.  This is a complimentary Standard to IEEE 1584.

It has been my experience in my work as an independent electrical safety consultant working in industry across Canada that not many P.Eng. Electrical Engineers are aware that the IEEE 1584.1...

Read More


 

Swati Vora-PatelBy Swati Vora-Patel


The electrical market is at the helm of innovation — from robotics and automation products that support advanced manufacturing to smart technology in homes and businesses, our industry leads innovation and competitiveness in Canada. With advanced electrical and automation products shaping how we work, live and play, our industry is continually at the forefront of designing technologies that meet the needs of Canadians today.

Over the past year, we have all been reminded that clean, hygienic spaces are critical to our health and well-being.

Read More


 

Product News

  • Prev
JSBT SlimBasics™ Tapered LED Disk Light Series comes in 4" and 6" sizes and provides even ...
An all-in-1, low-profile, linear and narrow wraparound with 18 possible color/lumen configurations ...
EdgeEnergy™, a subsidiary of Single Phase Power Solutions, introduces the EdgeEV70™ single phase ...
New energy technologies, like solar, require specialized test tools to efficiently provide critical ...
The Allia hub is essential for creating your smart home. It connects all network-compatible smart ...
Legrand AV announced the addition of five new models to its popular On-Q In-Wall Power & Cable ...
Excelitas TechnologiesÒ Corp., a global technology company delivering innovative, customized ...
Designed to visually scan large areas for moisture issues, air leaks, electrical problems, and ...
JSBT SlimBasics™ Tapered LED Disk Light Series comes in 4" and 6" sizes and provides even ...
Get an easy, flush receptacle installation in new concrete with Arlington's FLB6230MBLR Cover Kit. ...

 

Rittal VX SE Free-Standing EnclosureRittal introduces the new VX SE free-standing enclosure system that offers greater versatility. For applications where Rittal’s AX compact enclosures are too small, and the TS 8 baying enclosures are too large - the VX SE is an ideal midway alternative for applications where baying is not required. Additionally, the VX SE size range includes a 300 mm deep version that is suitable for applications where space is limited.

The VX SE offers quicker time-to-delivery and faster, streamlined assembly, enhanced reliability, greater safety, and compatibility with other Rittal systems. 

 

Read More


 

 

HPS CenturionHammond Power Solutions (HPS) has a new addition to their line of power quality products – HPS Centurion P Passive Harmonic Filter.

It is specifically engineered to mitigate harmonic currents created by non-linear loads. The initial product release has ratings from 5 to 500 horsepower. It improves power quality by simultaneously reducing harmonics and improving true power factor, resulting in an efficient and reliable solution.

 

 

 

Read More


 

 

Peers & Profiles

  • Prev
Bryan Smith started his now 20-year career at the ground floor, so to speak, as a draftsperson and ...
From small construction to sophisticated industrial projects, House of Electrical Supplies has been ...
Kyle Manfredi is the owner of ARK Electrical alongside his wife, Shannon. Operating out of ...
Like most major events over the last year, the COVID-19 pandemic put serious restrictions on the ...
This past December Jennifer Green was honoured with Canada’s Most Powerful Women Top 100 Award for ...
“It was quite surprising,” said Stephanie Smith of being named EHRC’s Leader of the Year. ...
As an advanced networked lighting controls company serving the industrial and large commercial ...
Trilliant, an international provider of utility solutions for advanced metering and smart grid ...
For more than a century, ABB has been investing in Canadian technologies and products to support ...
Mackenzie Gillan, a bright young lady from Baysville, Ontario, tells us about how she learned ...


House of Electrical SuppliesFrom small construction to sophisticated industrial projects, House of Electrical Supplies has been servicing clients in the industrial, OEM, entertainment, and construction markets across the Greater Toronto Area for just over 40 years. The company has earned a reputation for providing a high-quality customer experience.

As per President Austin Brennan, their experienced and knowledgeable team can be depended upon in any situation to deliver quick and efficient service. On top of their product solutions — ranging from electrical, automation, safety, lighting and portable power distribution — 

Read More


 

Copper $US Dollar price per pound

Kerrwil Publications Great Place to Work. Certified December 2019 - December 2020

538 Elizabeth Street, Midland,Ontario, Canada L4R2A3 +1 705 527 7666
©2021 All rights reserved

Use of this Site constitutes acceptance of our Privacy Policy (effective 1.1.2016)
The material on this site may not be reproduced, distributed, transmitted, cached or otherwise used, except with the prior written permission of Kerrwil