Terry Becker

By Terry Becker, P.Eng.

The arc flash hazard has overwhelmed employers in all industries across Canada and in the United States.  In most cases unfortunately, employers have been purely reactive!  I call it “bottom up hierarchy of risk controls.”  The employer sends worker’s on “Arc Flash Awareness” or “Arc Flash Training,” buys arc flash PPE kits and pays for an engineering arc flash hazard analysis study without issuing a technical specification or controlling the format of the arc flash & shock equipment labels.  Qualified Persons that receive the arc flash training will not apply the training if there is no documented policies, practices and procedural requirements.

The electric shock hazard has been neglected when in reality it should be a higher priority for employers than arc flash.  Myths and misinformation related to arc flash have propagated over the last ten years from multiple sources and continue to influence industry negatively.  There is a perception that energized electrical equipment is inherently “not safe” and there is a high risk in just operating it that workers will be exposed to the arc flash hazard.  Over the last 10 years engineering arc flash hazard analysis reports have wrongly advised the client that greater than 40 cal/cm2 of incident energy is “Dangerous” and “No PPE exists” which are FALSE statements.  In some cases, Journeymen Electricians believe it is against the law to work energized!

Figure 1 – Hierarchy of Risk Control Methods – Top Down

Figure 1

 

 

 

 

 

 

 

 

 

 

Employers need to take control of the narrative, step back and assess a plan, then work the plan to ensure long term sustainable and measurable results to prove that they have done adequate due diligence to OHS Acts, Codes & Regulations and have reduced risk to workers to as low as reasonably practicable.  Ensuring that defendable documented policies, practices and procedural requirements are documented and implemented in a compliant Electrical Safety Program will ensure that the risk related to energized electrical work tasks when tested will “pass!”  In alignment with Occupational Health & Safety Management System Standards (e.g. ISO 45001, ANSI Z10, CSA Z45001) a an electrical safety PLAN-DO-CHECK-ACT philosophy is recommended.


Figure 2

 

 

 

 

 

 

 

 

 

 

 

Over the last decade in Canada and the United States myths and misinformation related to abnormal arcing fault probability and an arc flash occurring and interpreting OH&S law and Electrical Safety Standards Acts for CE Code Part I compliance have led to Journeyman Electricians doubting that they can continue to perform energized electrical work tasks at all.  This in turn will increase the likelihood of occurrence when they do complete energized work tasks and in the long run will not service our societies continued and growing use of electrical energy.  Additionally, non-electrical workers (e.g. homeowners, construction workers) completing construction of electrical systems and installing electrical equipment (e.g. installing solar panels, inverters, EV car chargers, etc.) will also lead to increased risk of shock for these individuals.

Some of the myths and misinformation out there related to arc flash as noted above are:

  1. It is against the law for a Journeyman Electrician to complete energized electrical work tasks.
  2. 40 cal/cm2 of incident energy is “Dangerous” and “No PPE Exists.”
  3. Our Journeyman Electricians do not work “live” it is a company policy, we do not need an Electrical Safety Program.
  4. Testing for absence of voltage is NOT energized electrical work.
  5. An arc flash & shock equipment label is installed on the electrical equipment so the “Arc Flash Boundary” is real at all times. We should paint lines on the floor in front of the electrical equipment.
  6. If an arc flash occurs the related arc blast pressure will be very, very, very high and can pulverize me and impale me with shrapnel.

This information continues to be communicated in non-compliant “arc flash training” or “arc flash awareness training,” in P.Eng. authenticated arc flash hazard incident energy analysis reports, and posts on LinkedIn, Webinars, and some YouTube videos.

You may ask, what do I need to do to take control and in order to “Stop Reacting to Arc Flash?” The answers are provided in the CSA Workplace electrical safety Standard: an employer needs to develop, implement and audit a compliant Electrical Safety Program, PLAN-DO-CHECK-ACT!

Just sending a Journeyman Electrician on arc flash training, buying them arc flash and shock PPE and commissioning an arc flash hazard incident energy analysis study without issuing a formal technical specification is not sustainable and defendable due diligence.  It also leads to uncontrolled spending and the lack of the ability to budget year over year.

The CSA Z462 Workplace electrical safety Standard, 2021 Edition that was just published on January 5, 2021, Clause 4.1 General requirements for electrical-safety-related work practices and procedures is where employers should start with respect to establishing policies, practices and procedural requirements.  Ensure you get the facts and are not conservative in your interpretation of information provided to you, question it and as provided in CSA Z462 Clause 4.1.7.8 Risk Assessment Procedure use a qualitative risk assessment for Jobs and related discrete work tasks assigned to electrical workers as a credible, defendable tool to make decisions.

Specifically, as stated in CSA Z462 Clause 4.1 the employer shall:

  1. Develop, implement and train workers on an employer’s compliant Electrical Safety Program.
  2. Document an Electrical Safety Policy in their Electrical Safety Program.
  3. Implement the procedural requirement of Establishing an Electrically Safe Work Condition.
  4. Document justification for energized electrical work tasks.
  5. Implement the use of an Energized Electrical Work Permit.
  6. Identify energized work tasks that workers would perform and complete a qualitative Risk Assessment Procedure. Ensure the Hierarchy of Risk Control Methods that will be applied to reduce risk are identified.
  7. The Qualified Person shall document an Energized Electrical Job Safety Plan that will include the work task’s Shock Risk Assessment and Arc Flash Risk Assessment and the risk control methods they will apply to eliminate exposure to arc flash and shock or reduce their risk to as low as reasonably practicable.
  8. Ensure electrical incidents are appropriately managed and reported if they occur.
  9. Ensure workers receive compliant Lockout Program training.
  10. Provide compliant arc flash & shock training. The training provided shall include emergency release of a shock worker.
  11. Provide training on your company’s Electrical Safety Program to Qualified Persons.
  12. Ensure workers are trained on proper use of portable cord-and-plug-connected electrical equipment, extension cords and when/how to use a GFCI.

You need to ensure your company has a compliant Electrical Safety Program developed, implemented and audited.  This will allow you to take control of shock and arc flash hazards in your workplace.  Ensure your company prioritizes identification of Job’s and related discrete work tasks where workers are exposed to the electric shock hazard, use risk assessment as a powerful tool to make decisions.  Give your workers confidence and certainty, control costs and budgeting and be able to defend your due diligence for arc flash & shock hazards. Stop reacting to arc flash!

Terry Becker, P.Eng., Certified Electrical Safety Compliance Professional (CESCP), IEEE Senior Member is the first past Vice-Chair of the CSA Z462 Workplace electrical safety Standard Technical Committee and currently a Voting Member and Clause 4.1 and Annexes Working Group Leader. Terry is also a Voting Member on the CSA Z463 Maintenance of electrical systems Standard and a Voting Member of the IEEE 1584 Guide for Performing for Arc-Flash Hazard Calculations. Terry has presented at Conferences and Workshops on electrical safety in Canada, the USA, India and Australia. Terry is a Professional Engineer in the Provinces of BC, AB, SK, MN and ON. Terry is an Electrical Safety Specialist, Management Consultant at TW Becker Electrical Safety Consulting Inc., and can be reached at 1-587-433-3777 or by email terry.becker@twbesc.ca.

Changing Scene

  • Prev
Last week's disastrous floods have left many B.C. residents homeless, stranded or in desperate need ...
The Canadian Apprenticeship Forum (CAF-FCA) will launch a new program to empower skilled trades ...
Sean Dunnigan, President of Techspan Industries Inc., is pleased to announce the appointment of ...
The Electrical Safety Authority (ESA) would like to advise that the Minister of Government and ...
LabTest Certification Inc. is proud to announce its most recent recognition by OSHA as a Nationally ...
On November 13th, the Universal Women’s Network virtually hosted the 2021 Women of ...
Soussanna Karas, Director of Licensing at ESA, breaks down the risks of the underground economy ...
BCEA U40 group invites you to their Professional Development virtual series...     ...
Three accomplished women with diverse backgrounds are the newest members of Ontario Power ...


 

EIN ABB logo 400ABB is an international company with a large global presence, but did you know that a significant percentage of the products sold in Canada are also designed and manufactured locally?

ABB’s Installation Products division, formerly known as Thomas & Betts, operates seven manufacturing facilities in Canada, six of them in Quebec and one in Alberta.

Many of their most well-known brands, including IBERVILLE®️️, Marrette®️️, Microlectric®️️, and Star Teck®️️, are products that started in Canada and are still manufactured locally to meet Canadian standards.

 

 


 

Canadian Electrical Contractor Discussion Group: Can You Count the Deficiencies?

EIN CECD 400Have you ever been called to fix the work of a 'handyman'?

"Was supposedly done by a"certified ' electrician....told the homeowner that he got a $266 permit....no record at TSBC. Can you count the deficiencies?"

"There is a second panel change in the triplex also.......even more deficiencies. Think the guy was a glorified handyman. Ones not obvious: 240 BB heat hooked up 120....drier on 2p20....range on 2p50....water heater fed with 2c14 Bx on 2p15."

Go HERE to join the discussion

 


 



 

 Siemens Built In Isolation Products 400By Alyssa Kerslake

Life safety today is top of mind for nearly everyone. There is a certain level of trust that fire alarm systems continue to work within a fire incident. With system survivability being a key concern to regulators, building managers, and the public, Siemens has developed systems that are designed to meet and exceed regulations that protect people, property, and assets. 

One of the most significant concerns, particularly in a large multi-story building, is implementing a secure and fully functional fire alarm system. Today, it is not uncommon to have power and data for hundreds of fire alarm devices connected over a single pair of wires. The concern is, if a fault occurs somewhere between the devices, the zone and location of the device may no longer be known, or the operation of that circuit reduced or possibly impaired. These scenarios could allow an undetected catastrophic event to develop within the space due to inoperable life safety devices. 

 

Read More


 

 

David Gordon

By Terry Becker, P.Eng., CESCP, IEEE Senior Member

The CSA Z462 Workplace electrical safety Standard published its 2021 Edition in January.  A mandatory requirement for an employer is developing, implementing, and auditing an Electrical Safety Program.  If you have an Electrical Safety Program, is it up to date in its policies, practices and procedural requirements, is it performing as expected?  Workers do not necessarily do what you expect, they do what you inspect!  Management of change is required.

I have been involved in supporting industry with respect to shock and arc flash hazards in the workplace and in understanding what needs to be done to ensure worker safety, that effective defendable due diligence is established, and evidence of compliance is available related to occupational health & safety regulations both Provincial, Territorially or Federally.  I am in Ontario this week completing a detailed Electrical Safety Audit at multiple enterprise facilities.


Read More


 

Product News

  • Prev
On the hottest days of the summer and the coldest of the winter, the Napoleon NS18 heat pump and ...
Lumenwerx is pleased to launch Aera, an innovative lighting family that marks a new era in recessed ...
Eaton’s humidity sensor and fan control (HDFS3P1) device is a single pole humidity sensor for ...
With an EC motor and smart control, ORA-EC40 series air curtains are ideal for commercial and ...
Klein Tools expands its line of insulated screwdrivers with new lengths and tips, as well as a new ...
EarthTronics LED High Lumen Wattage & Color Selectable Series to provide flexibility and full ...
Eaton’s astronomic programmable timer (AT18HM) device reduces energy consumption by automating ...
The HomeGuard LED family of residential security lights, with rugged die cast aluminum ...
This preassembled constant wattage heating cable from Ouellet is specialized for roof and gutter ...


 

Milwaukee M12 Cable Stripper

Connect plug-in lamps, holiday lighting, and small appliances to the top “Controlled” outlet, while the bottom “Powered” outlet remains always on. The DW15R features tamper resistant receptacles with built-in shutters to prevent the insertion of unintended foreign objects. As well, the integrated button with vanishing feedback LED provides manual push-button on/off control and clear indiciation at any time.

Simplify control of the residence - schedule lamps and connected loads to turn on/off at specific times or based on sunrise/sunset, easily group smart devices into rooms, and create scenes to activate multiple loads at once. Utilize the auto-shutoff feature as a countdown timer in closets, hallways and bathrooms.

Read More


 

 

Incoplas Hybrid

Now available for Siemens Class 52 Actuators and Indicator Lights are the new Class 1, Div. 2 contact blocks. Suitable for use in Hazardous Location, Class 1, Div. 2 applications when used in a suitable enclosure. No matter which style actuator you use, the common base provided attaches to the hazardous location contact blocks easily.

Hazardous Location (HL) Series Contact Blocks are good for Hazardous Location CL1, DIV2 Applications using a Standard Enclosure NEMA 1, 12, 13, 4, 4X.

HL Series Contact Blocks are rated for switching high inrush loads like Tungsten Lamps.

 

Read More


 

 

EarthTronics 25-Watt Emergency Driver for Linear Highbay

The 20A Outlet and 15A Outlet have the ability to allow function specific Inserts to be installed/removed/swapped making this platform an optimal choice for renovations and new construction. The Swidget Outlet is installed using the same wiring as a standard wall receptacle and when paired with a Swidget Insert turns into a powerful and flexible Smart Home device. The swapability of the Inserts ensures that this will work with Smart Home wireless systems now and in the future.

The Swidget product line targets the Home Automation and Smart Home markets with a unique future-proof solution. Swidget currently offers eight smart Inserts with different functionalities including Wi-Fi control, indoor air quality sensor, temperature, humidity, and motion sensors, as well as a USB charger guide light, and emergency lighting. They can all be controlled from anywhere with the Swidget App for iOS/Android or Alexa and Google Home.

Read More


 

Peers & Profiles

  • Prev
Allana Kellett-Jamieson loves working in the electrical sector and is proud of the great focus ...
As the head of ABB Canada's electrification business unit, Éric Deschênes is no newcomer to the ...
Karen Pullen knows what it’s like to be the only woman on a construction site, and as a proud ...
As of February 2021, Martin Stephenson is the new President and CEO of Signify Canada.   ...
This past July, Kerith Richards, who has worked for Service Wire Company for the last seven years, ...
EngWorks was formed in 2004 as an electrical engineering and consulting firm by Allan Bozek, “After ...
Headquartered in Concord, Ontario, Mercury Lighting services national retail, ...
Among the recipients of the 2021 Clean50 Awards announced last month is Carolina Gallo, Vice ...
Sarah Silverstein is a principal with Liteline along side her two brothers Mark and Daniel. ...
As a 34-year-old female owner of an electrical contracting business, Danielle Gray may be unique. ...


EngWorksBy Blake Marchand

EngWorks was formed in 2004 as an electrical engineering and consulting firm by Allan Bozek, “After a short time we realized there was a niche in hazardous locations, in particular in hazardous area classification design requirements for various facilities. And also helping people understand just how the Canadian Electrical Code applies to hazardous locations.”

Given the complexity of hazardous locations, Bozek saw a need for education while working in the field and began developing training courses designed.

Read More


 

Éric DeschênesBy Line Goyette

As the head of ABB Canada's electrification business unit, Éric Deschênes is no newcomer to the electrical industry. He has a long track record and a passion for finding practical solutions to optimize technology adoption. Deschênes took on his current role with ABB January of 2020, he joined ABB in 2017 as Executive VP of the Electrification business after 15 years with Schneider Electric.

We met with him recently to discuss his new role at the helm of ABB Canada and his plans moving forward. He began by pointing out that the recent change to ABB Canada's structure, as elsewhere in the world, was made to make customer relations more straightforward. 

Read More


 

Copper $US Dollar price per pound

Kerrwil Publications Great Place to Work. Certified December 2019 - December 2020

538 Elizabeth Street, Midland,Ontario, Canada L4R2A3 +1 705 527 7666
©2021 All rights reserved

Use of this Site constitutes acceptance of our Privacy Policy (effective 1.1.2016)
The material on this site may not be reproduced, distributed, transmitted, cached or otherwise used, except with the prior written permission of Kerrwil