IEEE 1584.1 Guide for Specification of Scope and Deliverable Requirements for an Arc-Flash Hazard Calculation Study in Accordance with IEEE Std 1584 provides detailed guidance on how to complete an arc flash hazard incident energy analysis study and recommended content for the P.Eng. authenticated report.  This is a complimentary Standard to IEEE 1584.

It has been my experience in my work as an independent electrical safety consultant working in industry across Canada that not many P.Eng. Electrical Engineers are aware that the IEEE 1584.1 Guide for Specification of Scope and Deliverable Requirements for an Arc-Flash Hazard Calculation Study in Accordance with IEEE Std 1584 exists.

This is unfortunate as IEEE 1584.1 is a complimentary document to the core IEEE 1584 Standard and provides additional explanatory information and specific guidance on what content should be included in the report generated.  IEEE 1584.1 was published in 2013 to attempt to ensure that arc flash hazard incident energy analysis studies were completed correctly and with a report issued that was detailed and aligned with good engineering practice.

The IEEE 1584.1 Standard is a companion Standard to IEEE 1584 IEEE Guide for Performing Arc-Flash Hazard Calculations.  You should ensure that you have a copy of both IEEE 1584 and IEEE 1584.1 if you are performing arc flash hazard incident energy calculations and submitting reports to client.  This will allow you to substantiate any assumptions or disclaimers you may include in your report.

Currently the IEEE 1584.1 Standard is been updated from its 2013 Edition to a new Edition that will reference applicable content from the recently updated and published IEEE 1584-2018 Standard.  As is the IEEE 1584.1-2013 Standard content that is generic in nature and is applicable.  Where the updated IEEE 1584-2018 includes additional new content please ensure you reference it as a priority. 

With respect to completing arc flash hazard incident energy calculations the following steps are required to be completed in order as summarized in IEEE 1584.1:

Step 1:    Collect the system and installation data.  Start with an available Single Line Diagram.  Use specific electrical equipment data sheets.  Request Electrical Utility Fault Data for each service. Create the digital single line diagram model and enter electrical equipment data into the component editor with specific electrical equipment data in the power engineering software. Ensure you configure the “software arc flash module” and document your parameter selections before you start the incident energy analysis calculations.

Step 2:    Determine the system modes of operation.  This is a different requirement from strictly completing a short circuit analysis.  You need to consider single mode or multiple modes when determining bolted fault currents.  The number of scenarios and configurations to be considered for an arc-flash hazard analysis are dependent on the power distribution system and modes of operation (e.g., switching configurations for voltage sources, utility transformer(s), stand-alone prime power, cogeneration, emergency power generation) under normal and special conditions.

Step 3:    Short-Circuit Study.  Complete a short-circuit study that reflects the existing installation, alternate system configurations, and different operating scenarios where applicable.  Confirm electrical equipment withstand ratings.  Report any electrical equipment that is not correctly rated.

Step 4:    Protective Device Selection & Coordination Study, Time Current Curves (TCCs).  Available fault current conditions should be evaluated to determine the effect on protective device clearing times and incident energy calculations.  The existing protective devices and related settings shall be recorded as-built for existing power systems or as determined for new power systems for effective protection and coordination for system reliability.  The system design is then used to model abnormal arcing faults on specific electrical equipment and calculate incident energy and the arc flash boundary distance.  Time current curves shall be generated, referenced as required in the P.Eng. report and included for reference in the Appendices of the report issued.

Step 4:            With respect to 208V three phase electrical equipment. Previously there was a 125kVA transformer rule in IEEE 1584 2002 Edition. IEEE 1584 2018 Edition now quotes arcing faults for 208V three phase: “Sustainable arcs are possible but less likely in three-phase systems operating at 240V nominal or less with an available short-circuit current less than 2000A.” For 208V three phase 2000A available fault current is typically a 45kVA or higher transformer size depending on %Z. All panelboards sourced with a 45kVA or higher transformer where the available fault current is higher than 2000A will now require calculations. Alternately the CSA Z462 Arc Flash PPE Category Method could be applied for transformer up to 300kVA depending on impedance in %Z. Minimum recommendations are all 208V three phase energized electrical work tasks minimum 8.0 cal/cm2 Arc Thermal Performance Value (ATPV) arc flash PPE.

No incident energy analysis calculations are required for single phase 120VAC or 240VAC.

Step 5:    Determine the typical gap for the electrical equipment and enclosure sizes based upon system voltages and classes of equipment.  Reference IEEE 1584-2018 Table 8 Classes of Equipment and Typical Bus Gaps.  If you increase the gap from the default values incident energy calculated will go up.  Use typical data and no field measurements required unless electrical equipment is identified that is not typical. Verify with manufacturer’s shop drawings if available. Gap does impact incident energy calculations but is not as significant compared to other parameters.

Step 6:    Determine the box correction factor, shallow vs typical. Field measurements are not required, use typical data. Assume worst case for MCC starter buckets or other power distribution equipment that may have variable box sizes. Box correction factor doesn’t impact incident energy results significantly compared to other parameters (e.g., box/electrode configuration).

Step 7:    Determine the electrical equipment box/electrode configuration.  IEEE 1584-2018 Table 9 provides guidance of VCB, VCBB, HCB, VOA and HOA.  HCB will yield the highest calculated incident energy, then VCBB, and VCB lowest incident energy. Consider the work task description that may be performed on the electrical equipment. In some cases, two separate box/electrode configurations may be required for a single piece of electrical equipment and two separate Arc Flash & Shock Equipment Labels required for a single piece of electrical equipment.

Step 8:    Determine the working distances.  This is the anticipated distance from the arcing fault location to the Qualified Electrical Workers face and torso.  Reference IEEE 1584-2018 Table 10. Use typical working distances unless electrical equipment is unique and typical working distances are not appropriate. Increasing the working distance, lowers incident energy. If there is an application where working distance can be increased in the field by QEW then use larger working distance but document in report.

Step 9:    Calculate arcing current. Note: The system grounding does not affect the incident energy calculation as per the formulas in IEEE 1584 2018 Edition.

Step 10:  Determine the arc duration. Use the 2 Second guideline if required (adequate egress from the work task area is required and should be noted in report).

Step 11:  Calculate the incident energy at the assumed working distance for each specific location on the electrical equipment where an energized work task may be completed. You may have two calculations for a specific piece of electrical equipment if you decide to use two box/electrode configurations and related to specific energized electrical work tasks. Most likely worst-case option was utilized and would be indicated in Results Table.

Step 12:  Determine the Arc Flash Boundary distance for the electrical equipment where energized work tasks will be completed.

Step 13: Draft and issue P.Eng. Stamped Report.  See below for guidance and specifically reference IEEE 1584.1.

As identified in IEEE 1584.1 the recommended content of the P.Eng. Stamped Report would include:

  1. Eng. Stamped Cover Page.
  2. Executive Summary.
  3. Scope of Study & Results Summary.
  4. Disclaimer & Notes.
  5. Background Information. Requirement for completing the incident energy analysis as a method to determine “Additional Protective Measures” specifically arc flash PPE and the Arc Flash Boundary distance as outlined in CSA Z462 Clause 4.3.5.6 and CSA Z462 Clause 4.3.5.5. Additional information can be summarized here with explanation such as system modes of operation (e.g., single or multiple) that were short listed and utilized in completing the short circuit and arcing fault current calculations.  Analysis software used and configuration settings.
  6. Review of System Data.  Identify basis of electrical equipment data used to create the power system model, utility available fault currents, cable sizes, motor data and the motor hp cut off for using the lumped load feature in the power system analysis software (e.g. <200hp). 
  7. Any data assumptions made shall be listed. Include AutoCAD single line diagrams and data sheets in Appendix of report.
  8. Short Circuit Analysis Results. Summarize the basis for the calculations and findings. Identify if any electrical equipment was found to be outside of its current withstand ratings.
  9. Protective Device Coordination Study. Review the findings and discuss results and reference applicable Time-Current-Curves. Discuss basis for any potential changes to protective device settings to lower incident energy and ensure any implications are documented.
  10. Arc Flash Hazard Incident Energy Analysis. List the results of the base incident energy calculations with existing power system configuration in a summary table in the body of the report. Make recommendations for incident energy reduction.  There is no 40 cal/cm2 “Dangerous” incident energy level, where “No PPE Exists.”  This information was included in the power system software and historically has been used in error.  Incident energy doesn’t correlate directly to arc blast pressure.  You can have higher incident energy levels at lower available fault currents and on low voltage equipment over high voltage electrical equipment.  Technically incident energy over 140 cal/cm2 is high risk energized electrical work as there is no available arc-rated clothing greater than 140 cal/cm2 ATPV (e.g., Oberon Company).  The arc flash calculations results table should not include any reference to HRC #, Cat #, Level # or “letter” for arc flash PPE related to the incident energy results. 
  11. With respect to any recommendations made and documented in the report related to Arc Flash & Shock Equipment Labels the content on the label needs to meet the minimum requirements identified in CSA Z462 Clause 4.3.5.7 and the presentation of the information and use of signal pane wording should comply with ANSI Z535.  The Equipment Label should not include any reference to HRC#, Cat #, Level # or “letter” for arc flash PPE, the employer will define the arc flash PPE they provide to their workers.  CSA Z462 Workplace electrical safety Standard, Annex Q Arc flash and shock equipment labels, Figure Q.3 illustrates a compliant arc flash & shock equipment label.
  12. Recommendations for Incident Energy Reduction.  Advise client for Management of Change purposes recommended protective device setting changes.  Where required provide cost benefit analysis of any other incident energy reduction methods that are technically feasible 
  13. (e.g., arc flash relay, maintenance mode switch, more complex relaying schemes, IR scanning windows, etc.). Establish a realistic incident energy target level (e.g., 75 cal/cm2).
  14. Conclusion
  15. Appendices include AutoCAD single line diagram, analysis software single line diagram, field data sheets, provided utility short circuit data report, short circuit analysis report, TCCs, arc flash incident energy analysis results table(s), example Arc Flash & Shock Equipment Labels. Anything else?

Based on my experience in reviewing Arc Flash Hazard Incident Energy Analysis Reports for clients across Canada many of the reports I have reviewed were deficient in content and included errors & omissions based on the detailed requirements and basis of the incident energy calculations as documented in IEEE 1584.  With the new updated 2018 Edition of the IEEE 1584 Standard it will be even more important that the responsible P.Eng. Electrical Engineer documents in detail the assumptions made, any disclaimers, field data validation, etc..

It is also extremely important that any Arc Flash & Shock Equipment Label recommendations provided to a client in a report meet the minimum requirements of Equipment Labeling as identified in CSA Z462 Workplace electrical safety Standard, Clause 4.3.5.7 and also reference CSA Z462 Annex Q Arc flash and shock warning and information labels as noted above.  It is important to note that the “Danger” signal pane should only be used if the calculated incident energy is greater than 140 cal/cm2 NOT 40 cal/cm2.  Make sure the footer of the label indicates the protective device ID and location of the incident energy (e.g. load side, line side or bus).

This article is a simplified summary of the IEEE 1584.1 Guide for Specification of Scope and Deliverable Requirements for an Arc-Flash Hazard Calculation Study in Accordance with IEEE Std 1584.  You are advised to purchase a copy of IEEE 1584.1 and review its content in detail when completing your incident energy analysis study and drafting the report that is issued to clients.

Terry Becker, P.Eng., Certified Electrical Safety Compliance Professional (CESCP), IEEE Senior Member is the first past Vice-Chair of the CSA Z462 Workplace electrical safety Standard Technical Committee and currently a Voting Member and Clause 4.1 and Annexes Working Group Leader.  Terry is also a Voting Member on the CSA Z463 Maintenance of electrical systems Standard and a Voting Member of the IEEE 1584 Guide for Performing for Arc-Flash Hazard Calculations.   Terry has presented at Conferences and Workshops on electrical safety in Canada, the USA, India and Australia.  Terry is a Professional Engineer in the Provinces of BC, AB, SK, MN and ON.  Terry is an Electrical Safety Specialist, Management Consultant at TW Becker Electrical Safety Consulting Inc., and can be reached at 1-587-433-3777 or by email terry.becker@twbesc.ca.

Title: Ready, Set, Scale: How to Grow Your Field Service Business

SimProThrough many trials and tribulations, you’ve grown your business to where it is today. It’s taken blood, sweat, tears, long hours and sacrifice. But, it’s all been worth it to have something which you can call your own. It’s even more worth it when you can finally take that next step to grow your business even further and expand your service, project and maintenance work.

Read More


 

Changing Scene

  • Prev
43 years ago, Steve Silverstein bought a table saw and a delivery van and began a revolution in the ...
E.B. Horsman & Son (EBH) has announced their Victoria location will be officially moving to a ...
 The Maritime’s largest Mechanical and Electrical event took place last Wednesday and ...
IDEAL INDUSTRIES, INC. is calling all professional and student-apprentice electricians to come out ...
Vivi White has been appointed to the Board of Directors of the Electrical Safety Authority ...
The Sonepar Ontario Region is proud to announce the relocation of their SESCO Central Distribution ...
The Electrical Safety Authority (ESA) is looking for a seasoned business executive drawn from an ...
David Rellinger, Vice President of Systems Transformation for Schneider Electric (SE), has been ...
The National Electrical Trade Council (NETCO) is pleased with the direction of the 2022 budget with ...
The Executive of Gerrie Electric Wholesale Limited is very pleased to announce the acquisition of ...

Become a Wiser Approved Installer

Schneider Wiser Installer

Get access to exclusive benefits, product discounts and resources that will help you drive more business, and lower energy bills for your clients.

 

 

 

Read More


 



Vivi WhiteVivi White has been appointed to the Board of Directors of the Electrical Safety Authority (ESA) by the Honourable Ross Romano, Minister of Government and Consumer Services.

“As Chair, I am pleased that the Ontario Government recently appointed Vivi White to the Board,” said Annette Bergeron. “The Electrical Safety Authority’s efforts over the years have greatly improved the safety of the people of Ontario. It’s an important mandate and requires a strong, talented and diverse board as we transform into a modern regulator.”

 

Read more


 

Omnicable joins ETIMETIM North America announced that OmniCable has joined the product classification standards organization. Headquartered in West Chester, PA, OmniCable has 24 locations throughout North America, and also owns Houston Wire & Cable (HWC). The company partners with many electrical manufacturers and only sells to distributors.

According to John Dean, Director of Marketing & E-Commerce, OmniCable/HWC, “The wire and cable industry is often called commodities, but there are very distinct features and attributes for the different products our manufacturers produce. 

Read More

 


 

Canadian Electrical Contractor Discussion Group: Can You Count the Deficiencies?

EIN CECD 400Have you ever been called to fix the work of a 'handyman'?

"Was supposedly done by a"certified ' electrician....told the homeowner that he got a $266 permit....no record at TSBC. Can you count the deficiencies?"

"There is a second panel change in the triplex also.......even more deficiencies. Think the guy was a glorified handyman. Ones not obvious: 240 BB heat hooked up 120....drier on 2p20....range on 2p50....water heater fed with 2c14 Bx on 2p15."

Go HERE to join the discussion

 


 

Switch to Smart, Switch to Easy, Switch to Beautiful

Schneider Connected LivingScrewless wall plates. Smart Outlets. Square D™ Switches and Receptacles are raising the bar on aesthetics, ease of installation, remote lighting control and connectivity.

 

 

 

Read More


 



 

FlukeElectrical distribution problems are not always immediately identified as issues with power quality. An example of this is a thermal-magnetic circuit breaker. When it trips, the indication is generally a short circuit, ground fault, or overload. At times this can be put down to an old breaker that needs replacing.

However, it’s important to investigate the types of loads on the system and monitor harmonics for a potential disturbance. This article explores common issues with power quality and how to troubleshoot those issues.

 

 

Read More


 

EIN Romex 12 2 Recall 400This recall involves a yellow electrical wire, 12/2 NMD90 75M Romex SIMpull cable, sold by the spool. Products were also sold at Home Depot designated as article 108196.  Only cables with a time stamp between 12:41 and 18:02 are affected by this recall. 

The recalled product contains a neutral wire that is a smaller 14-gauge wire, contrary to the stamp on the wire identifying both the neutral and “hot” wires as 12-gauge (i.e., "12/2"). 

The recalled product contains a 14-gauge neutral wire instead of 12-gauge (as labelled), thus it may not perform as expected in 12-gauge applications, resulting in a risk of those applications having impaired performance and/or compliance with safety codes or standards.

Go HERE for more information


 

Product News

  • Prev
Klein Tools introduces the new Advanced Circuit Tracer Kit, offering tracing of breakers and ...
The SYM-IN "In Table" model provides an attractive user interface while solid construction ...
The NEW Contractor Select™ version of the Juno Podz™ Canless Downlight is now easier than ever ...
Introducing the NEW Hi-Tech Valiant™ full-range current-limiting fuse for fire mitigation. No one ...
Appleton™ explosionproof and dust-ignition proof GR, GRF and GRTS conduit outlet boxes are ...
Southwire's new 100' LED string lights with 12,000 Lumens.    
Help provide comfort and functionality to your bathroom with the addition of the Broan BHF110 ...
The PWB-CMU8 is the first dedicated Masonry Wall Box engineered for installation in 8” block walls. ...
Now with pre-sized labels and even more materials to take on the toughest on-site labelling jobs. ...
The STACK Family is now complete! These four performance-tiered solutions were designed to help you ...

Liteline Continues Canadian Investment

EIN BC Liteline 400Adding continued investment in Canada to its core foundation of innovative Design, installation efficiency, and personal customer service, Liteline has just announced the opening of its 12,729 square foot Showroom and Lighting Distribution Center in Langley BC.

The new Liteline Facility is located at 26550 Gloucester Way, Unit A110 and will house the new Liteline Distribution Center along with a product showroom. 

Read More




Greenlee Mobile Bending Table for 881 Series Hydraulic BendersGreenlee is bringing secure and easy-to-transport conduit bending capabilities to jobsites with the introduction of its Mobile Bending Table for 881 Series Hydraulic Benders. The new product combines the latest in anti-theft protection with enhanced mobility, easy set-up and quick teardown.

“Electricians are constantly trying to do work more efficiently. Anytime we can shave time off a job, it’s a win – and this product delivers that with easier set-up and portability. At the same time, we know that protecting equipment from theft is an issue for a lot of tradespeople. The new Greenlee Mobile Bending Table for the 881 Series Hydraulic Benders is our latest solution to help professionals safeguard their investments and increase productivity,” 

Read More


 

 

Klein Tools Upgraded Testing KitKlein Tools introduces the Premium Electrical Test Kit.

Premium Electrical Test Kit (Cat. No. 69355)

  • Refreshed kit that features three new product releases geared towards a variety of electrical testing applications.
  • Kit includes instructions and all required batteries.

Manual-Ranging Digital Multimeter with Right-Angle Test Leads (Cat. No. MM320 – Exclusive to Cat. No. 69355 and Cat. No. MM320KIT)

  • Measures up to 600V AC/DC voltages, 10A DC current and 2-ohm resistance
  • Also tests batteries, diodes and continuity.

Read More


 

 

Brady M211Design, preview and print – all from your phone. Simple and intuitive, the M211 Label Printer is built for the job site, running all day on a full charge while resisting drops, shocks and crushes.

  • Simple. Easy. Intuitive.  Seamlessly design, preview and print labels from the industry leading Express Labels App on your familiar smartphone and swiftly connect to your printer.
  • Label it once.  Now with both pre-sized and continuous labels in 90+ cartridges, filled to the brim with reliable, tested and dedicated label materials that stay attached and remain legible on every surface and in any environment.

 

Read More


 

Peers & Profiles

  • Prev
Watt’s the Word is a recently launched Electrical Industry Podcast hosted by Zack Hartle and ...
Allana Kellett-Jamieson loves working in the electrical sector and is proud of the great focus ...
As the head of ABB Canada's electrification business unit, Éric Deschênes is no newcomer to the ...
Karen Pullen knows what it’s like to be the only woman on a construction site, and as a proud ...
As of February 2021, Martin Stephenson is the new President and CEO of Signify Canada.   ...
This past July, Kerith Richards, who has worked for Service Wire Company for the last seven years, ...
EngWorks was formed in 2004 as an electrical engineering and consulting firm by Allan Bozek, “After ...
Headquartered in Concord, Ontario, Mercury Lighting services national retail, ...
Among the recipients of the 2021 Clean50 Awards announced last month is Carolina Gallo, Vice ...
Sarah Silverstein is a principal with Liteline along side her two brothers Mark and Daniel. ...


Brent NeillyBy Blake Marchand

Brent Neilly is the Group Marketing Manager with Milwaukee, he has a background in business communications with a B.A. from Brock University, as well as experience working in the construction industry.

“When I joined TTI (Milwaukee’s parent company) it was kind of a perfect match, I had some marketing knowledge from my business degree and some industry experience from working in the trades.” Neilly gained his experience covering an area from Orillia to Timmins, Ontario when he first joined the company as a Field Sales Rep, as well as on their Job Site Core Trade Specialists in the GTA where he found his niche working with utility clients. 

Read More


 

Copper $US Dollar price per pound

Kerrwil Publications Great Place to Work. Certified December 2019 - December 2020

538 Elizabeth Street, Midland,Ontario, Canada L4R2A3 +1 705 527 7666
©2022 All rights reserved

Use of this Site constitutes acceptance of our Privacy Policy (effective 1.1.2016)
The material on this site may not be reproduced, distributed, transmitted, cached or otherwise used, except with the prior written permission of Kerrwil