Section 40 — Electric Cranes and Hoists

The Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the information you need. This series of articles provides a guide to help users find their way through this critical document. This is not intended to replace the notes in Appendix B or the explanations of individual requirements contained in the CEC Handbook, but will hopefully provide some help in navigating the Code. These notes are based on the 25th edition.

40-000 Scope - This is a supplementary or amendatory section of the code and applies to the installation of electrical equipment and circuits for electric cranes, hoists,

and monorails. The CEC Handbook provides additional notes and diagrams to better explain this section.

40-002 Supply conductor sizes – Because of the short duty of crane and hoist motors, insulated supply conductors are selected from Table 58, which specifically applies to Crane and Hoist installations.

40-004 Conductor protection – Insulated supply conductors for the main contactors of cranes and hoists must be in raceway, armoured cable, or Mineral Insulated, Aluminum-sheathed or Copper-sheathed cable. There is an exception to this where a conducting track of conducting rails is used as per Rule 40-018.  Where insulated conductors supply the crane or hoist equipment directly and where a flexible connection is necessary, flexible type cord or festoon cable is permitted provided there is a take-up device provided to prevent damage and contact with the floor.

40-006 Overcurrent protection – For main contact insulated supply conductors or directly supplied equipment, the overcurrent protection must be selected as per Rule 28-200 and Tables 29 and D16 for the motor load, plus any allowance as per Rule 14-104 where conductors have been selected with capacity for the other loads on the crane or hoist.

40-008 Disconnecting means – All ungrounded conductors of the main contact conductors must be capable of being simultaneously disconnected quickly for safety in an emergency and for maintenance. The disconnect must be within sight of the main contact conductors or the equipment. In addition, the disconnect must be accessible and be operable from the ground or floor over which the crane or hoist operates.

40-010 Main contact conductors – This rule requires that where there are bare main contact conductors, they must have an ampacity not less than the conductors supplying them and, if wire conductors, shall be not smaller than No. 4 AWG copper, or No. 2AWG aluminum. If the conductors are more than 18 m long, then the minimum size must be No. 2 AWG copper or No. 1/0 AWG aluminum unless intermediate strain relief is provided by clamp type insulating supports. Bare conductors may be hard drawn copper, aluminum wire, or steel or other suitable metal in the form of angles, tees, T-rails, or other rigid shapes.

40-012 Spacing of main contact conductors – Because bare main contact conductors depend on free air space to provide insulation between phases and to ground, this rule outlines the minimum support separation required of main contact conductors installed in a horizontal plane of 75mm for monorail hoists and 155 mm for other than monorail hoists. If installed in other than a horizontal plane, the separation of the main contact conductor supports must be 200mm. They should also be supported so that the extreme limit of displacement maintains a separation of 38mm from any surface. Where the bare main contact conductors are rigid, the supports must provide a minimum separation of 25mm between conductors, collectors, and any surface.

40-014 Supporting of main contact conductors – In addition to the spacing required in Rule 40-012, the main contact conductors must be stretched between strain insulators at each end and supported throughout the length at 6m intervals.  If building conditions preclude supporting at 6m intervals, it may be increased to a maximum of 12m intervals providing the separation between contact conductors is increased by the same proportion. In the case of rigid main contact conductors, insulated supports must be spaced at intervals of up to 80 times the vertical height of the conductor but not more than 4.5m. Refer to the CEC Handbook for diagrams illustrating support spacing and calculation notes.

40-016 Joints in rigid contact conductors – This rule outlines the importance of ensuring that any joints made in rigid main contact conductors must maintain the same ampacity of the conductors over the joint to eliminate any overheating.

40-018 Use of track as a conductor – This rule permits a single monorail, tramrail or crane runway track to be used as one of the main contact conductors or supply circuit conductors for one phase of a 3-phase circuit, providing it is derived from a single isolating transformer, does not exceed 300 v, is bonded to ground (see Rule 10-1100 to 10-1108), and any joints meet Rule 40-016.

40-020 Guarding of contact conductors – Requires that all contact conductors be guarded against inadvertent contact with bare current-carrying parts unless incorporated in an enclosed contact assembly. In addition, as long as a minimum clearance of 6 m between bare contact conductors and grade, floor, or any working surface (including a catwalk) is maintained, guarding of bare contact conductors may not be required.

40-022 Contact conductors not to supply other equipment – This rule prohibits the contact conductors supplying the crane, hoist or monorail feeding other equipment not essential to the operation of the crane, hoist or monorail.

40-024 Bonding – As per Rule 10-406 all exposed non-current carrying parts shall be bonded to ground. In addition, in the case of a track or rail used as a conductor, it shall be bonded in accordance with Rule 40-018. Note that metal wheels on metal rails may provide a low impedance grounding path. A flexible supply connection as per Rule 40-004(2) must contain a bonding conductor.

In the next installment, we will be discussing Section 42 — Electric Welders.

[1] Source: CSA C22.1:21, Canadian Electrical Code, Part 1 - Safety Standard for Electrical Installations. © 2021 Canadian Standards Association. Please visit store.csagroup.org. With the permission of CSA Group, material is reproduced from CSA Group standard CSA C22.1:21, Canadian Electrical Code, Part 1 - Safety Standard for Electrical Installations. This material is not the complete and official position of CSA Group on the referenced subject, which is represented solely by the Standard in its entirety. While use of the material has been authorized, CSA Group is not responsible for the manner in which the data are presented, nor for any representations and interpretations. No further reproduction is permitted. For more information or to purchase standard(s) from CSA Group, please visit store.csagroup.org or call 1-800-463-6727.

[1] William (Bill) Burr is an associate member of the Canadian Electrical Code, Part 1, Technical Committee and formerly Chair of the Canadian Advisory Council on Electrical Safety (CACES), Chief Electrical and Elevator Inspector for the Province of BC & the Northwest Territories, Director of Electrical and Gas Standards Development and Director of Conformity Assessment at CSA Group. Bill can be reached at Burr and Associates Consulting billburr@gmail.com.

Changing Scene

  • Prev
 Canada’s National Electrical Trade Council (NETCO) is pleased to announce that IDEAL ...
The Government of Saskatchewan is engaging the public to help ensure health and safety legislation ...
Despite electrical shock being a serious and potentially dangerous event, it is frequently ...
Acuity Brands, Inc. has announced its Care222® filtered far-UVC module with patent-pending ...
LEDVANCE, the makers of SYLVANIA general lighting in the United States and Canada, recently ...
The federal governemnt launched a Call for Proposals under the new Apprenticeship Service, to ...
ECAO and OEL are working on obtaining more contractor experiences with the ESA permit system. ...
Agents of Change is an event for stakeholders from Canada's electricity and beyond to build ...
Schneider Electric is introducing a personalized digital experience for logged in customers ...
Teledyne Technologies Incorporated announced the successful completion of the acquisition of FLIR ...


 

SaskatchewanThe Government of Saskatchewan is engaging the public to help ensure health and safety legislation meets the needs of employers and workers in the province. From August 16 to October 18, 2021 citizens can provide input on part III (occupational health and safety) of The Saskatchewan Employment Act.

"Our province has a plan for growth that includes ensuring we have safe and healthy workplaces" Labour Relations and Workplace Safety Minister Don Morgan said. 

 


Read More


 

Canadian Electrical Contractor Discussion Group: Can You Count the Deficiencies?

EIN CECD 400Have you ever been called to fix the work of a 'handyman'?

"Was supposedly done by a"certified ' electrician....told the homeowner that he got a $266 permit....no record at TSBC. Can you count the deficiencies?"

"There is a second panel change in the triplex also.......even more deficiencies. Think the guy was a glorified handyman. Ones not obvious: 240 BB heat hooked up 120....drier on 2p20....range on 2p50....water heater fed with 2c14 Bx on 2p15."

Go HERE to join the discussion

 


 



 

Desert HomeA combination of stunning design, a spectacular desert setting, and exceptional architectural lighting is a winning combination for a private residence just outside of St. George, Utah. JRC Lighting was hired by the homeowner to create the lighting concept for the showpiece home.

"The house has an almost industrial look to it, with a focus on clean lines," said Kevin Meredith, principal at JRC Lighting. "My goal was to keep the lighting understated and let the architecture, and the views, sell themselves.”

 

Read More


 

 

David GordonBy David Gordon

This summer EiKO is launching its Z10 product offering. I know, what is Z10 other than the sports cars some of us remember (’69 Z10 Camaro or a 2009 BMW Z10, but let’s go with an American muscle car!)?

So, since it seemed like a sports car “name” (since sports car naming seems to be in numbers), we reached out to Sarah Eastman, VP Marketing for EiKO, who shared that Z10 is an alliance of manufacturers who have developed standards to support an easier lighting controls process within fixtures (remember, I’m not a product maven).
Read More


 

Product News

  • Prev
With Cerberus Cloud Apps, accessing fire protection systems has never been easier. Cerberus ...
Milwaukee Tool adds to their fish tape lineup with new 120’ and 240’ 1/8” Stainless Steel Fish ...
Stanpro’s L2WMG is a LED linkable wrap that is perfectly suited for utility rooms, corridors, ...
Klein Tools Rechargeable Safety Lamp with Magnet, a quad-directional visual alert beacon that ...
Mersen's finger safe IP20-rated Power Distribution Blocks are part of the new Compact EP® line of ...
Whether you’re working on a single-family, multi-family, or commercial construction project, the ...
INEXO is the electrical box designed specifically for insulated concrete form construction (ICF). ...
DLC Premium listed for maximum energy rebates. No need to discard of entire original fixture -- ...
Specifications: Easily adjustable LED strips for multiple beam angles. 1200-1300 lumen output. ...
Installing a robust control or contactor box in the field can be a lot of work. From gathering ...

 

Milwaukee M12 Cable StripperM12™ Cable Stripper Kit for Cu THHN / XHHW aims to improve the cable stripping experience. With no exposed blades, the cordless cable stripper provides safer stripping than with a knife. The cable stripper's compact, right-angle design allows you to maneuver it more easily in tight spaces with less strain on the wrist. The bushing design and adjustable depth gauge deliver cleaner, more accurate and consistent strips across all sizes.

The cable jacket stripping tool is not only compatible with all MILWAUKEE® bushings but is also compatible with competitive quick-change bushings.

 

Read More


 

 

Incoplas HybridThe Incoplas® LED Hybrid is a durable multi-purpose and corrosion-resistant LED lighting solution that can be used in heavy industrial applications where hazardous location lighting is required.

Certifications

Class 1:

Flammable Gases and Liquids

Division 2: The hazardous atmosphere is only available infrequently (i.e. in case of spill).

 

Read More


 

 

EarthTronics 25-Watt Emergency Driver for Linear HighbayEarthTronics LED emergency drivers regulate the power supplied to the LED fixture so that it can operate as a light source in the event of a power failure. The purpose of emergency lighting is to ensure that lighting is provided promptly, automatically and for a suitable time when the normal power supply fails.

This insures that people within the building can evacuate safely in the event of an emergency. All EarthTronics emergency drivers meet specific UL, CSA and NFPA requirements. Always consult local code requirements when specifying emergency lighting products.

Read More


 

Peers & Profiles

  • Prev
As of February 2021, Martin Stephenson is the new President and CEO of Signify Canada.   ...
This past July, Kerith Richards, who has worked for Service Wire Company for the last seven years, ...
EngWorks was formed in 2004 as an electrical engineering and consulting firm by Allan Bozek, “After ...
Headquartered in Concord, Ontario, Mercury Lighting services national retail, ...
Among the recipients of the 2021 Clean50 Awards announced last month is Carolina Gallo, Vice ...
Sarah Silverstein is a principal with Liteline along side her two brothers Mark and Daniel. ...
As a 34-year-old female owner of an electrical contracting business, Danielle Gray may be unique. ...
Mark Klein is Co-President of Klein Tools, managing Sales & Marketing activities, alongside ...
Bryan Smith started his now 20-year career at the ground floor, so to speak, as a draftsperson and ...
From small construction to sophisticated industrial projects, House of Electrical Supplies has been ...


EngWorksBy Blake Marchand

EngWorks was formed in 2004 as an electrical engineering and consulting firm by Allan Bozek, “After a short time we realized there was a niche in hazardous locations, in particular in hazardous area classification design requirements for various facilities. And also helping people understand just how the Canadian Electrical Code applies to hazardous locations.”

Given the complexity of hazardous locations, Bozek saw a need for education while working in the field and began developing training courses designed.

Read More


 

 

Eric TordjmanBy Blake Marchand

Headquartered in Concord, Ontario, Mercury Lighting services national retail, multi-residential/commercial property management, energy service companies (ESCO), and auto dealerships. “From design to specifications, we offer turn-key services that go beyond the typical distributor model,” explained Mercury Lighting Vice President, Eric Tordjman. Their value-added approach leverages well-established supplier relations to help clients find a lighting solution that suits their needs.

“How we differentiate ourselves is we’re lighting specific, we do very little in the way of electrical, and really emphasizing our expertise towards solutions selling...

Read More


 

Copper $US Dollar price per pound

Kerrwil Publications Great Place to Work. Certified December 2019 - December 2020

538 Elizabeth Street, Midland,Ontario, Canada L4R2A3 +1 705 527 7666
©2021 All rights reserved

Use of this Site constitutes acceptance of our Privacy Policy (effective 1.1.2016)
The material on this site may not be reproduced, distributed, transmitted, cached or otherwise used, except with the prior written permission of Kerrwil