In this article: Section 58 — Passenger Ropeways and Similar Equipment. Rule 58-000 states that Section 58 is a supplementary or amendatory section of the code and applies to passenger ropeways as defined in the CSA Z98, Passenger Ropeways and Passenger Conveyers standard, which includes tramways, chairlifts, gondolas, surface ropeways, passenger conveyors, and similar equipment. In addition, ANSI B77.1, Passenger Ropeways – Aerial Tramways, Aerial Lifts, Surface Lifts, Tows and Conveyers - Safety Requirements, and Can/CSA-C22.3 No.1, Overhead Systems should be referenced.

 

 

Appendix B and the CE Code Handbook provide additional information.

Rule 58-002 provides special terminology definitions for Cabin, Messenger, Passenger Conveyor and Station.

General requirements

Rule 58-010 requires that, in addition to the spacing requirements of Rule 2-308, the headroom in working spaces around controllers, disconnecting means, and other electric equipment must be no less than 2.0 m. Part 2 of the rule provides that the requirements for headroom may be relaxed provided that

  • Only authorised persons have access to the area
  • The working space is kept clear of obstructions, and either
    • o live parts are guarded, isolated or insulated and the equipment can be examined, adjusted, serviced or maintained while energized without removing the protection, or
    • o a cautionary label advising that the equipment cannot be examined, adjusted, serviced, or maintained while energized is applied, or
    • o the applied voltage is equal or less than 30 V RMS or 42 V peak

Rule 58-012 specifies that circuits of less than 50 volts must be bonded to ground as per Rule 10-114.  Communication, control, remote control, monitoring, supervision, and signal circuits may be isolated, and grounded in accordance with Rule 10-206. The haul rope for these circuits may be isolated and ungrounded.

Rule 58-014 limits voltage for all circuits to 300 volts-to-ground except for

  • 750 volts-to-ground for motors, machine brakes, motor-generator sets, floodlighting, and heaters
  • 120 volts-to-ground for motor control circuits
  • 48 volts-to-ground for communication, control, remote control, monitoring, supervision, and signal circuits except for hand-crank-type telephone signal bell circuits
  • 30 volts-to-ground or 40 volts-to-ground peak for aerial conductors carried between towers that support the passenger ropeway, except hand-crank-type telephone signal bell circuits

Rule 58-016 provides that luminaires for night skiing or similar floodlighting applications may be installed on passenger ropeway towers and stations if there is a circuit breaker, installed in a lockable enclosure that disconnects all ungrounded conductors, and that each circuit to the luminaires is protected by a ground fault circuit interrupter (Class A GFCI).

Conductors

Rule 58-102 specifies that the minimum size of conductors for all communication, control, remote control, monitoring, supervision, and signal circuits shall be No. 26 AWG copper, except for circuits contained in travelling cables where the minimum size must be No. 20 AWG.

Rule 58-104 permits that

  • optical fibre cables, shielded cables, and conductors for operating devices, power, motor, heating, air conditioning, operating, signal, communication, control, safety, fire alarm, and lighting circuits may be grouped in raceway systems or travelling cables, providing the insulation rating for each conductor is not less than the conductor with the maximum circuit voltage
  • optical fibre cables, shielded cables, and conductors for operating devices, operating, signal, communication, control, safety, and fire alarm circuits may be run in the same aerial cable, providing that the insulation rating for each conductor is not less than the conductor with the maximum circuit voltage

Note that optical fibre cables include conductive, non-conductive and hybrid types as defined in Rule 56-102.

Wiring methods

Rule 58-200 outlines acceptable wiring methods in passenger ropeways and similar equipment:

  • Generally, all conductors, including optical fibre cables in machinery spaces, control spaces, in or on cabins, in machine rooms and control rooms must be installed in rigid metal conduit, EMT, rigid PVC conduit or wireways, except for travelling cables connecting the movable drive carriage or movable return carriage.
  • In addition, the following wiring methods may be used:
    • o mineral-insulated cable
    • o aluminum-sheathed cable
    • o armoured cable
    • o cable trays installed in accordance with Rules 12-2200 to 12-2210
    • o flexible conduit or liquid-tight flexible conduit between raceways and limit switches, interlocks, operating devices, or similar devices
    • o flexible conduit or liquid-tight flexible conduit between control panels and motors, machine brakes, motor-generator sets, disconnecting means, or pumping unit motors and valves
    • o jacketed cables installed between raceways and signal equipment and between raceways and operating devices where mechanical protection is provided and where the cables are supported including:
      • cables used in Class 1 extra-low voltage and Class 2 low-energy circuits, including but not limited to travelling cables connecting the movable carriage or movable return carriage
      • extra-low-voltage control cable
      • communication cable
      • fire alarm and signal cable
      • multi-conductor thermoplastic-insulated cable
      • hard-usage and extra-hard-usage cables
      • auxiliary gutters between controllers, starters, and similar apparatus
      • jacketed flexible cords and cables used in extra-low-voltage circuits (30 V or less), not greater than 2 m in length, supported and provided with mechanical protection

Rule 58-202 requires that supports for travelling cables be located and provided with suitable guards to prevent damage to the cables and contact with other equipment.

Protection and control

Rule 58-300 requires that motor control devices be arranged, as per rules 28-312 and 28-400, to prevent automatic restarting after shutdown where restarting could cause injury to persons.

Rule 58-302 provides that disconnecting means for the ungrounded conductors of the main drive motor and auxiliary drive motor, including their ventilation and control circuits, for each passenger ropeway or passenger conveyor must not contain a provision to automatically close the disconnecting means, and must be

  • a single disconnect which also disconnects power to the driving machine brake(s) control circuit directly or through an auxiliary contact that is positively opened mechanically (the opening not being solely dependent on springs)
  • an externally operated fusible switch or a circuit breaker, capable of being locked in the open position, and clearly labelled describing the connected load
  • readily accessible to authorized persons and located where it is visible on entry to the control room or machinery area
  • provided with a sign to identify the location of the supply side overcurrent protective device
  • a single disconnect for motors and control circuits of multiple driving machines or motors connected to a single passenger ropeway or passenger conveyor

Rule 58-304 provides that disconnecting means for utilization equipment must be

  • a single disconnect for all ungrounded conductors
  • capable of being locked in the open position and located in the machine room, control room, machine space, or control space
  • provided with a sign to identify the location of the supply side overcurrent protective device

Rule 58-306 requires that overcurrent protection be coordinated with any upstream overcurrent protective devices.

Rule 58-308 requires that every 125 V, single-phase receptacle installed in machine rooms, control rooms, machine spaces, control spaces, and counterweight enclosures be protected with a Class A type ground fault circuit interrupter.

Rule 58-310 specifies that motor controllers be rated to comply with Rule 28-500(1) except where the controller limits the available power and is labelled “power limited”. 

Branch circuits

Rule 58-400 requires that each machine room, control room, machinery space, and control space must have

  • luminaires, not supplied from the load side of the ground fault circuit interrupters required by Rule 58-308, and controlled by lighting switches within easy reach of the point of entry
  • a 125 V, single-phase, duplex receptacle, having a configuration in accordance with Diagram 1
  • a separate branch circuit for the supply of luminaires and receptacles

Rule 58-402 requires that where counterweights are installed in a building or room, luminaires, not supplied from the load side of the ground fault circuit interrupters required by Rule 58-308, must be provided and a separate branch circuit must supply lighting and receptacles.

Rule 58-404 specifies that utilization equipment other than that identified in rules 58-400 and 58-402, must be supplied by a separate branch circuit with overcurrent devices located in the machinery room, control room, machinery space or control space.

Regenerative power

Rule 58-500 requires that means must be provided to absorb regenerative power that cannot be absorbed under overhauling load or braking conditions.

In the next installment, we will be discussing Section 60 — Electrical Communications Systems.

The source for this series of articles is the Canadian Electrical Code, Part I, published by CSA. Note the CEC Handbook is also published by CSA.

William (Bill) Burr is the former Chair of the Canadian Advisory Council on Electrical Safety (CACES), former Director of Electrical and Elevator Safety for the Province of BC, and former Director of Electrical and Gas Standards Development and former Director of Conformity Assessment at CSA Group. Bill can be reached at Burr and Associates Consulting; billburr@gmail.com

 

Changing Scene

  • Prev
ESA’s response team has been working diligently to address the emerging issues. We are moving into ...
Littelfuse invites plant engineers, facility managers, and maintenance professionals to join its ...
This recall involves Legrand / Pass & Seymour commercial-grade tamper resistant duplex ...
In response to the current COVID-19 crisis, IDEAL Canada was looking for ways to contribute to the ...
Join Nexans for a free webinar as Isaac Müller, Applications Engineer for Nexans discusses this ...
IDEAL INDUSTRIES has made the difficult but necessary decision to cancel the original ...
The Regional Electrical Inspector performs physical inspections on all types of electrical ...
The Alberta Electrical Alliance (AEA) released a video message from their Provincial Board of ...
A new white paper published by Mohawk College’s Energy and Power Innovation Centre explains how ...
With the COVID-19 crisis underway, EFC is working diligently to provide current electrical ...

Vallen CanadaIn the midst of the pandemic crisis, safety & MRO specialist Vallen Canada moved its 6,000 square foot West Edmonton, Alberta branch to a new 20,000 square foot location, enabling the branch to triple its inventory. How did the company keep everyone safe during the transition? Vallen Canada simply relied on its own expertise.

“We had to really do a good gut check on whether this was the right decision to move the branch during the pandemic,” says Vallen Canada President Karen Chester. “The reality is the show must go on… our culture is such that we pull together in tough times and we need to get the job done. The final step in the process was to make sure we keep people safe.”

Read More

 

Emergency HospitalsAs the battle against COVID-19 continues, medical providers all over the world are expanding their capacity to treat patients through the construction of temporary hospital facilities and tents. Eaton and its partners recently helped realize a project by the United States Army Corps of Engineers at Stony Brook University Hospital in New York, supplying essential power distribution equipment for four temporary medical facilities with the capacity to treat more than 1,000 patients. Construction on the facility is expected to be completed this week, with nearly 100 Eaton heavy-duty safety switches providing reliable power distribution to support life-saving ventilators and other devices.

Read More

 

 

Latest Articles

  • Prev
Many organizations are at risk of continued interruption to operations due to coronavirus and ...
It is very scary to realize that our entire world has changed so drastically with the COVID-19 ...
My feet were cold. In my haste to run out the door that night when the pager chirped and ...
It's a nearly 2,100-mile drive from his home in Newfoundland to the jobsite in western ...
As the spread of COVID-19 rapidly increases around the world, companies are beginning to prepare ...
With their new REEL-X fish tape line, Greenlee aimed to alleviate the aggravation and wasted energy ...
I once took a class where the professor would explain concepts in two ways. First, he would dive ...
A broadening of the role of luminaires and a continued focus on people and energy efficiency are ...
We are in an Age of Disruption. Extant and emerging technologies are driving significant evolution ...
Often, code users encounter situations where they find themselves at odds with the rules contained ...

Step-Down TransformersBy Max Ezzati

Step-down transformers allow any electrical product to be installed on 347V circuits, which is why many electrical contractors keep a few in their car stock. Selecting the correct step-down transformer ensures the physical dimensions of the transformer are as small as possible to fit easily in the junction box while keeping costs as low as possible. Here are our tips on selecting the best step-down transformer for your job.

 

 

Read More

 

 

 

 

Bill BurrBy William (Bill) Burr

The code is a comprehensive document. Sometimes, it can seem quite daunting to quickly find the information you need. In this current series of articles, I will provide a guide to help users find their way through this critical document. This is not intended to replace the notes in Appendix B or the explanations of individual requirements contained in the CEC Handbook, but will hopefully provide some help in navigating while reading the code. Here in this issue: Section 18.

 

Read More

 

Product News

  • Prev
In 2020, Louis Poulsen and BIG Ideas present a comprehensive new lamp series, Keglen, especially ...
Architectural sound absorbing 100% Merino Wool Felt. Made from carbonized wool treated with ...
Universal Lighting Technologies recently introduced 180W PWX LED drivers. These drivers are ideal ...
Venture Lighting International has partnered with Synapse Wireless to enhance the capabilities of ...
In its aim to develop high-performance, long-lasting, and robust lighting solutions, LUBO Lighting, ...
The highly-efficient Juno® UPLD swivel LED undercabinet in 9, 14, 22 and 30” lengths have an easily ...
Lumenpulse has launched the Lumenblade family: a collection of contemporary classic rectilinear ...
The Lithonia Lighting FML4W is a new wide housing LED Wraparound. While suitable for new ...
Douglas Lighting Controls, a member of the Panasonic family of companies, recently introduced the ...
Arlington's new low profile 5x8" TV Box™ features a steel back box for use with MC, AC and flexible ...

 

Louis Poulsen Lamp SeriesIn 2020, Louis Poulsen and BIG Ideas present a comprehensive new lamp series, Keglen, especially characterised by its distinctive design as well as classic superior lighting quality.

The key pieces in the Keglen series are four pendants (Ø175), (Ø250), (Ø400) and (Ø650) that each provide their very own diffusion of light using a curved glass insert, which is built into and adapted to each version of the shade.

The main feature of the lamp is the organic shaped glass that sits perfectly beneath the cone as a small water droplet shaped by physics and cohesive forces in nature, says Jakob Lange, Partner, BIG Ideas.

 

Read More

Universal Lighting EVERLINE PWX LED DriversUniversal Lighting Technologies recently introduced 180W PWX LED drivers. These drivers are ideal for outdoor luminaire applications, such as street, roadway and site area lighting, as well as, indoor highbays using non-Class 2 drivers.

“As the outdoor and industrial lighting segments continues to expand, Universal is focused on providing solutions that help our customers capture more market opportunities by increasing controllable options,” said Kevin Boyce Director of Product Management for Universal. “The PWX drivers are available with 12Vdc or 24Vdc auxiliary power for lighting applications with on-board sensors or radios.”

Read More

 


HazmastersHazmasters was founded with a dedication and focus on creating safer work environments. It is distributor of safety products servicing customers in the industrial, construction, commercial, institution, and government markets.

The company supplies safety products, conduct safety inspections and tests, as well as service and repair safety products it. A company that educates and trains. A company that delivers every aspect of workplace safety to the employer and follows up to make those solutions easy to implement and sustain.

 

Read More

 

 

Copper $US Dollar price per pound

Kerrwil Publications Great Place to Work. Certified December 2019 - December 2020

538 Elizabeth Street, Midland,Ontario, Canada L4R2A3 +1 705 527 7666
©2020 All rights reserved

Use of this Site constitutes acceptance of our Privacy Policy (effective 1.1.2016)
The material on this site may not be reproduced, distributed, transmitted, cached or otherwise used, except with the prior written permission of Kerrwil